Functions and control
1
6
Domestic air conditioner
If Tr<Ts-1
℃
, the outdoor system will be turned on again, the indoor fan will be at the cold air proof mode.
*Indoor fan control
manual control: You can choose high, medium, low and automatic speed control.
Automatic: When Tr<Ts, high speed.
When Ts
≤
Tr
≤
Ts+2
℃
, medium speed.
When Tr> Ts+2
℃
, low speed.
When the airflow speed has no delay from the high to low switching, the speed should be delayed for
3 minutes (remain at high speed for 3 minutes.) before the next switch.
*Airgate location control: the location for the airgate can be set according to your needs.
Coldair proof operation
1. The indoor operation within 4 minutes after the start up is as the following diagram, the air speed
can be raised only after the speed has reached a certain level.
2. 4 minutes after the start up of the indoor fan, the light airflow and the low airflow will be turned to the
set speed airflow.
3. In the cold air proof operation, the fan won’t stop after the start up.
4. During the cold air proof operation, the indoor system will continuously send ‘indoor high speed’
signals to the outdoor system.
* Residue heat sending. The indoor fan will send the residue heat at a low speed for 12 seconds.
If other conditions are satisfied, when the compressor stops, the indoor system will operate at a light
speed. The indoor fan will stop when the coil temperature is below the ‘heat start temp 4’.
* Defrosting. When the system receives the defrosting signal from outdoors, the indoor fan will stop
and the indoor temperature display won’t change. At the time, any indoor coil malfunctions will be
neglected. When the outdoor defrosting finishes, the coil malfunction will still be neglected until the
compressor has been started up for 30 seconds. The indoor temperature display will not change and
the system operates at the cold air proof mode.
* Automatic heating temperature compensation: when the system enters the heating mode, the
temperature compensation (4) will be added. When the status is switched off, the compensation will
be erased.
7.1.5 Strength operation
The system enters the mode after receiving the ‘strength signal’.
Send strength operation signal to the outdoor system.
The mode change finishes the strength operation.
Heat start temp 1
Heat start temp
2
Heat start temp
3
Heat start temp
4
Set speed
Low speed
Light speed
Fan/off
Fan/off
Keep the high
speed. The fan
doesn’t stop
Summary of Contents for AS12TB3HRA
Page 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 ...
Page 14: ...Printed circuit board connector wiring diagram 12 Domestic air conditioner PCB 1 ...
Page 53: ...three 6 Removal Procedure 4 Domestic Air Conditioner Remove the casing 1 2 3 ...
Page 57: ...Removal Procedure 8 Domestic Air Conditioner motor cover motor cover ...
Page 58: ...Removal Procedure 9 Domestic Air Conditioner ...