Installation work for air outlet ducts

Calculate the draft and external static pressure and select the length,

shape and blowout.

A   Blowout duct

2-spot, 3-spot and 4-spot with     200 type duct are the standard

specifications.

Note

  (1) Shield the central blowout hole for 2-spot.

          (2) Shield the blowout hole around the center for 3-spot.

Limit the difference in length between spots at less than 2:1.

Reduce the length of duct as much as possible.

Reduce the number of bends as much as possible. (Corner R should

be as larger as possible.)

Use a band. etc. to connect the main unit and the blowout duct

flange.

Conduct the duct installation work before finishing the ceiling.

Connection of suction, exhaust ducts
a.Fresh air inlet

Inlet can be selected from the side or rear faces depending on the

working conditions.

Use the rear fresh air inlet when the simultaneous intake and exhaust

is conducted. (Side inlet cannot be used.)

b.Exhaust (Make sure to use also the suction.)

Use the side exhaust port.

Good example

Bad example

Bad example

Exhaust hole

State seeing from top of unit

Side fresh air inlet

Rear fresh air inlet

Fig.1

Fig.2

Drainage Test

Conduct a drainage test after completion of the electrical work.

During the trial, make sure that drain flows properly through the

piping and that no water leaks from connections.

In case of a new building, conduct the test before it is furnished

with the ceiling.

Be sure to conduct this test even when the unit is installed in the

heating season.

Attached drain hose clamp

Drain piping

Main unit

Drain situation can be checked with transparent socket

Remove grommet.

Make sure to install

it back after test.

Insert water supply hose

for 20 mm ~ 30 mm to

supply water.

(Insert hose facing

toward bottom.)

Pour water into a convex joint.

Procedures

Supply about 1000 cc of water to the unit through the air outlet

using a feed water pump.

Check the drain while cooling operation.

Before the electrical work has not been completed, connect a convex

joint in the drain pipe connection to provide a water inlet. Then, check

if water leaks from the piping system and that drain flows through

the drain pipe normally.

(1)
(2)

(3)

(4)

(a)

(b)

Ceiling surface

Heat

insulation

Suction panel

(Silent panel)

Air conditioner main unit

Special

blowout

(Option)

Blowout duct

(Optional  or

marketed item)

Hole for check

s p e c i a l   i n l e t

(option) (with air

filter)

inlet duct

 (Optional or

 marketed item)

B

A

C

Drain Pipe

Air Duct

Installation Procedure

19

Installation Procedure

Summary of Contents for ADH071M1ERG

Page 1: ...d by qualified personnel Please read this manual carefully before installation Cautions Safety Precautions Parts and Functions Heating Mode Care and Maintenance Troubleshooting Accessories Precaution for Installation Is The Unit Installed Correctly Installation Procedure ADH105M1ERG ADH125M1ERG ADH140M1ERG ADH071M1ERG ADH071M3ERG ADH090M1ERG ADH105H1ERG ADH125H1ERG ADH140H1ERG ADH160H1ERG 3 4 7 8 ...

Page 2: ...gerant charge of the product see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging IMPORTANT INFORMATION REGA RDING THE REFRIGERANT USED Haier Industrial Park Qianwangang Road Eco Tech Development Zone Qingdao 266555 Shandong P R C A B C D kg kg kg R410A WARNING If the supply cord is damag...

Page 3: ... instructions set forth in the User s Guide Installation shall be done by professional people don t install unit by yourself For the purpose of safety the air conditioner must be properly grounded in accordance with specifications Always remember to unplug the air conditioner before opening inlet grill Never unplug your air conditioner by pulling on the power cord Always grip plug firmly and pull ...

Page 4: ...jury or death Installation by yourself is not encouraged because it could cause such problems as water leakage electrical shock or fire accident by some improper handing Installationbyyourselfisnotencouragedbecauseitcould cause such problems as water leakage electrical shock or fire accident by some improper handing Do not install nearby the place where may have leakage of flammable gas Depending ...

Page 5: ...ture of the unit for any damage after a use of long period of time Insufficient ventilation could cause an oxygen deficiency accident If the structure is not repaired immediately the unit could topple down to cause a personal injury When cleaning the system stop the operation and turn off the power switch Do not put water containers on the unit such as a flower vase etc Cleaning should never be do...

Page 6: ...ion Cut off the power supply to adjust the SW1 4 and SW1 5 or else the operation is invalid 10 2 For ADH071M3ERG ADH105M1ERG ADH125M1ERG ADH140M1ERG ADH105H1ERG ADH125H1ERG ADH140H1ERG ADH160H1ERG static pressure selection need achieved by wired controller refer wired controller s manual to get details SW1 1 2 3 4 5 6 7 8 Static pressure 10 Pa 30 Pa 50 Pa 70 Pa OFF OFF OFF ON ON OFF ON ON 6 Safety...

Page 7: ...ADH160H1ERG ADH071M3ERG 7 Parts and Functions The pump drain opening Electrical components Case Drain pan Evaporator Air outlet frame Air outlet frame Drain pan Evaporator The pump drain opening Electrical components Case Air outlet frame Fan Drain pan The drain opening Electrical components Case ...

Page 8: ...ver to ordinary heating operation Heat pump type warming With the heat pump type warming the mechanism of heat pump that concentrate heat of outdoor air with the help of refrigerant to warm the indoor space is utilized Defrosting operation When a room is warmed with a heat pump type air conditioner frost accumulates on the heat exchanger of outdoor unit along with the drop of indoor temperature Si...

Page 9: ... is consumed even the air conditioner is in stop Clean the air filter and set it in the place Care and Cleaning of the unit Clean with soft and dry cloth If it is very dirty dissolve neutral detergent in the lukewarm water and make the cloth wet with the water After wiping clean off the detergent using clean water 1 Clean the air filter by lightly tapping it or with the cleaner It is more effectiv...

Page 10: ...the flowing sound of the refrigerant and it is not a trouble Water flowing sound is heard This is caused by heat expansion or contraction of plastics Cracking sound is heard It smells Air which blows out from the indoor unit sometimes smells The smell results from residents of tobacco smoke or cosmetics stuck inside of unit When the air conditioner is used at restaurant etc where dense edible oil ...

Page 11: ...en or PCB hardware malfunction 0 12 0C Malfunction of drain system Pump motor disconnected or at wrong position or the float switch disconnected or at wrong position or the short circuit bridge disconnected 0 13 0D Zero cross signal wrong Zero cross signal detected wrong 0 14 0E Abnormal communication between main control PCB fan motor driver communication wire disconnected or wrong connected or P...

Page 12: ... the wired remote control and electric control board 1 Accessories supplied with the indoor unit Accessories Wired controller For Air conditioner operation For tightening the Connecting pipe For indoor side pipe joint gas side For indoor side pipe joint liquid side 1 Drainage fittings group For ADHM series only 1 Air conditioner operation 7 For fixing the heat insulation For ADHH series only 4 For...

Page 13: ...sult from a falling of the unit Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes etc Improper installations can result in accidents due to a violent falling over of the unit For electrical work please see that a licensed electrician executes the work while following the safety standards related to electrical equipment and l...

Page 14: ...The place where salt breeze blows Seaside etc The place where dense soot smoke exists The place where humidity is extraordinarily high The place where near the machine which radiates the electromagnetic wave The place where voltage variation is considerably large For details consult your sales dealer The electric work must be burden on the authorized engineer with qualification for electric work a...

Page 15: ...tional panel etc depending on the specific type Select places for installation satisfying following conditions and at the same time obtain the consent on the part of your client user Places where chilled or heated air circulates freely When the installation height exceeds 3m warmed air stays close to the ceiling In such cases suggest your client users to install air circulators Places where perfec...

Page 16: ...lightly lower Hanging bolt M10 nut Main unit M10 washer M10 spring washer 1 Preparation for suspending the unit a Size of hole at ceiling and position of hanging bolts b Hanger bolts installation Use care of the piping direction when the unit is installed Hanging bolt M10 Hole in anchor Hole in plug Insert Concrete Dimensions A mm B mm C mm Model Indoor Unit D mm E mm F mm 150 A B C Hanging bolt p...

Page 17: ...onnection of the drain socket and drain hose accessory Drain hose Stage difference part Drain socket Drain socket Main unit VP field purchased Pipe cover large for insulation accessory VP field purchased Pipe cover for insulation field purchased Drain hose accessory Pipe cover small for insulation accessory Clamp accessory Adhesion Installation Procedure 17 Unit model The size of drain opening 32m...

Page 18: ...tretch for the needed height is higher than 500 mm the back flow quantity of drain at the event of interruption of the operation gets too much and it may cause overflow at the drain pan Therefore make the height of the drain pipe within the distance given in the sketch below Right overhead Drain hose Joint for VP 25 Local procurement 600 Maximum local drain up dimension 290 325mm g Avoid positioni...

Page 19: ...st Conduct a drainage test after completion of the electrical work During the trial make sure that drain flows properly through the piping and that no water leaks from connections In case of a new building conduct the test before it is furnished with the ceiling Be sure to conduct this test even when the unit is installed in the heating season Attached drain hose clamp Drain piping Main unit Drain...

Page 20: ...connection Make wiring to supply power to the outdoor unit so that the power for the indoor unit is supplied by outdoor unit Item Model Phase Switch breaker A Circuit breaker Overcurrent protector rated capacity A Power source wire size minimum mm2 Switch breaker A Earth leakage breaker Leak current mA 30 1 40 30 6 0 40 Outdoor 3 phase type Outdoor unit terminal block Indoor unit terminal block Po...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...Address Haier Industrial Park Qianwangang Road Eco Tech Development Zone Qingdao 266555 Shandong P R C Contacts TEL 86 532 88936943 FAX 86 532 8893 6999 Website www haier com ...

Reviews: