16

VP 30

Secure the elevation as high as possible
(approx. 100 mm)

A downhill grade of
1/100 or more

Drain hose

Joint for VP 25
(Local procurement)

600

(Maxi

m

um local drain up dimension)

Right overhead

290~325mm

Attached drain hose clamp

Drain piping

Main unit

Drain situation can be checked with transparent socket

Remove grommet.
Make sure to install
it back after test.

Insert water supply hose
for 20 mm ~ 30 mm to
supply water.
(Insert hose facing
toward bottom.)

Pour water into a convex joint.

When constructing drain piping for several units, position the
common pipe about 100 mm below the drain outlet of each
unit as shown in the sketch. Use VP-30(11/4") or thicker pipe
for this purpose.
Be sure to provide heat insulation to hard PVC pipes of indoor
placement.
Do not ever provide an air vent.
The height of the drain head can be elevated up to a point 500
mm above the ceiling, and when an obstacle exists in the
ceiling space, elevate the piping to avoid the obstacle using
an elbow or corresponding gadget. When doing this, if the
stretch for the needed height is higher than 500 mm, the back-
flow quantity of drain at the event of interruption of the
operation gets too much and it may cause overflow at the
drain pan. Therefore, make the height of the drain pipe within
the distance given in the sketch below.
Avoid positioning the drain piping outlet at a place where
generation of odor may be stimulated. Do not lead the drain
piping direct into a sewer from where sulfur gas may generate.

Drainage Test

Conduct a drainage test after completion of the electrical work.
During the trial, make sure that drain flows properly through the piping and that no water leaks
from connections.
In case of a new building, conduct the test before it is furnished with the ceiling.
Be sure to conduct this test even when the unit is installed in the heating season.

Procedures

Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.
Check the drain while cooling operation.

(d)

(e)

(f)

(h)

(g)

1

2

3

4

1

2

(In the electrical work has not been completed,
connect a convex joint in the drain pipe connection
to provide a water inlet. Then, check if water
leaks from the piping system and that drain flows
through the drain pipe normally.)

Installation Manual For Indoor Unit

Summary of Contents for AD182AMEAA

Page 1: ...ITIONER AD182AMEAA AD242AMEAA AD282AMEAA AD362AMEAA AD422AMEAA AD482AMEAA AD522AMEAA AD182AMERA AD242AMERA AD282AMERA AD362AMERA AD422AMERA AD522AMERA Please read this operation manual before using th...

Page 2: ...nction 7 8 Care and Maintenance 9 For Preparation of Heating Hot Keep 10 Is The Unit Installed Correctly 11 Installation Manual For Indoor Unit 12 18 Safety Precautions 3 5 Parts and Functions 6 Cauti...

Page 3: ...an appropriate anti pollution method of disposal Disposal of the packaging of your new air conditioner All the packaging materials employed in the package of your new air conditioner may be disposed w...

Page 4: ...ident by some improper handing Do not install nearby the place where may have leakage of flammable gas Depending on the place of installation a circuit breaker may be necessary Drain pipe should be ar...

Page 5: ...is operated at the vicinity of such equip ment which generates steam condensed water may drip during cooling operation or it could cause a fault current or short circuit When operating the system sim...

Page 6: ...hould be H05RN F 4G 0 75mm2 All the cables shall have got the European authentication certificate During installation when the connecting cables break off it must be assured that the grouding wire is...

Page 7: ...Parts and Functions 6 Air outlet Air inlet Duct Air outlet Air inlet Duct For series 182 242 282 For series 362 422 482 522...

Page 8: ...at the air inlet or outlet Cooling is not sufficient Isn t sun shine invading direct Isn t any unexpected heating load generated Isn t the room much crowded Isn t the swing louver horizontal At HEATIN...

Page 9: ...e FAN mode during cooling To prevent frost from being accumulated on the indoor unit heat exchanger it is sometimes automatically switched to the FAN mode but it will soon return to the cooling mode E...

Page 10: ...no obstacles blocking the air inlet and air outlet of both indoor and outdoor units Make sure that the air filter is not dirty Cut in the power supply switch 12 hours before starting run Post Season C...

Page 11: ...ver to ordinary heating operation WARMING OPERATION Heat pump type warming Defrosting operation Atmospheric temperature and warming capacity Period of warm up With the heat pump type warming the mecha...

Page 12: ...as generates Hot spring area etc The place where salt breeze blows Seaside etc The place where dense soot smoke exists The place where humidity is extraordina rily high The place where near the machin...

Page 13: ...hen strength is insufficient injury can result from a falling of the unit Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes et...

Page 14: ...of your client user a Places where chilled or heated air circulates freely When the installation height exceeds 3m warmed air stays close to the ceiling In such cases suggest your client users to ins...

Page 15: ...allation Manual For Indoor Unit For series 362 422 482 522 For series 182 242 282 3 Avoid installation and use at those places listed below a Places exposed to oil splashes or steam e g kitchens and m...

Page 16: ...drain pipe to unit pay suffcient attention not to apply excess force to the piping on the unit side Also fix the piping at a point as close as possible to the unit For drain pipe use hard PVC general...

Page 17: ...for the needed height is higher than 500 mm the back flow quantity of drain at the event of interruption of the operation gets too much and it may cause overflow at the drain pan Therefore make the h...

Page 18: ...duct flange Conduct the duct installation work before finishing the ceiling 8 Connection of suction exhaust ducts a Duct connection position i Fresh air inlet Inlet can be selected from the side or re...

Page 19: ...nit so that the power for the outdoor unit is supplied by terminals Item Model Phase Switch breaker A Circuit breaker Overcurrent protector rated capacity A Power source wire size minimum mm2 30 20 2...

Page 20: ...sly Sensor broken down or short circuit for more than 2m continuously Sensor broken down or short circuit for more than 2m continuously CT check abnormal 3 times in 30m High pressure switch acts 3 tim...

Page 21: ...HAIER GROUP Qingdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266500 P R China Web Site http www haier com...

Reviews: