SAFETY PRECAUTION
5
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent
or a similar qualified person. An extend cord is not recommended, the requirement of the
power supply cord is H07RN-F 3G 2.5mm
2
(suitable for installation in European region)
3. If the fuse on PC board is broken please change it with the type of T. 3.15A /250V.
4. The waste battery shall be disposed properly.
5. The wiring method should be in line with the local wiring standard.
6. Use copper wire only. The connecting cable should be H07RN-F 2x2.0mm
2
, H05RN-F 4G
0.75mm
2
. (for heating pump unit) or H07RN-F 2x2.0mm
2
,H05RN-F 2G 0.75mm
2
. (for
cooling only unit). The power cable should be H07RN-F 3G 2.5mm
2
. All the cables shall
have got the European allthentication certificate.
7. The power supply connects from the indoor side.
8. The breaker of the air conditioner should be all-pole switch; and the distance between its
two contacts should be no less 3mm.
9. The indoor unit installation height is at least 2.5m.
1. Applicable ambient temperature range:
The machine is adaptive in following situation
Cooling
Heating
Indoor
Indoor
Outdoor
Outdoor
Maximum:
Minimum:
Maximum:
Minimum:
Maximum:
Minimum:
Maximum:
Minimum:
D.B / W.B
D.B / W.B
D.B / W.B
D.B / W.B
D.B / W.B
D.B / W.B
D.B
D.B
D.B
32 / 23
18 / 14
-7 / -8
24 / 18
43
15
15
27
/ 26
Note:
Part of the power supply of the air conditioner are not prepared because of the requirement
of the dealer, the power supply should be provided for oneself.
c
c
c
c
c
c
c
c
c
c
c
c
c