The power source capacity must be the sum of the room air conditioner current and the current of other electrical
appliances. When the current contracted capacity is insufficient, change the contracted capacity.
When the voltage is low and the air conditioner is difficult to start, contact the power company the voltage raised.
CAUTION
FRESH AIR INTAKE
1. Open up the knockout hole for the fresh air intake. If using half-concealed
installation, open up the top knockout hole instead.
CAUTION
When removing the cabinet (iron plate), be careful not to damage the indoor
unit internal parts and surrounding area (outer case).
When processing the cabinet (iron plate), be careful not to injury yourself
with burrs,etc.
2. Fasten the round flange (optional) to the fresh air intake. If using half-
concealed installation, attach to the top.
3. Connect the duct to the round flange.
Duct
For half-concealed
Round duct (option part)
WARNING
The power cable and connecting cable are self-provided.
Always use a special branch circuit and install a special receptacle to supply power to the room air conditioner.
Use a circuit breaker and receptacle matched to the capacity of the room air conditioner.
The circuit breaker is installed in the permanent wiring. Always use a circuit that can trip all the poles of the wiring and
has an isolation distance of at least 3mm between the contacts of each pole.
Perform wiring work in accordance with standards so that the room air conditioner can be operated safely and positively.
Install a leakage circuit breaker in accordance with the related laws and regulations and electric company standards.
30
Installation Procedure
Wiring diagram
4. Seal with a band and vinyl tape,etc. so that air does not leak from the
connection.
For single phase
For three phase
Outdoor unit
terminal block
Indoor unit
terminal block
Power supply
380-400V, 3N~, 50Hz
Y/G
R S T N 1 2 3
Y/G
1 2 3
Power supply
1PH, 220-230V~, 50Hz
Outdoor unit
terminal block
Indoor unit
terminal block
Y/G
1 2 3
Y/G
1 2 3
L N
Y/G