(2) Auto Selection of Wind Speed
In the following, Tr means room temperature while Ts means setting temperature.
a. During cooling program
conversion of wind speed from the low to high won’t work until
the present speed has continued for 3 minutes while conversion from the high to low needs
no time delay. The chart below is the sketch map of conversion:
Ts 2
Ts 1
Medium speed
Medium speed
Te
m
perature
falling
Te
m
perature
rising
Low speed
High speed
Low peed
High speed
Ts 3
Ts
b. During heating program
applicable for cooling-heating type , conversion of wind speed
from the low to high won’t work until the present speed has continued for 3 minutes while
conversion from the high to low needs no time delay. The hart below is the sketch map of
conversion:
Low speed
Ts 1
Ts 2
Medium speed
Medium speed
Te
m
perature
rising
High speed
High speed
Te
m
perature
falling
Ts
Low speed
Ts 3
(3) Dehumidifying program
In the following, Tr means room temperature while Ts means setting temperature.
a. After the system entering dehumidifying program, the compressor, outdoor and indoor
blowing fans run according to the following rules:
(1) Tr > Ts + 2 , the compressor and outdoor blowing fan run continuously while indoor
ELECTRICAL CONTROL FUNCTIONS
Summary of Contents for AC142ACNAC
Page 54: ...11 1 Wiring Diagram HCFU 14CL03 R1 HCFU 18CL03 R1 11 ELECTRICAL DATA ELECTRICAL DATA ...
Page 68: ...Model HCFU 14CL03 R1 HCFU 18CL03 R1 outdoor unit EXPLODED VIEWS PARTS LISTS ...
Page 70: ...12 2 Model HCFU 24CL03 R1 HCFU 28CM03 R1 indoor unit EXPLODED VIEWS PARTS LISTS ...
Page 72: ...Model HCFU 24CL03 R1 HCFU 28CM03 R1 outdoor unit EXPLODED VIEWS PARTS LISTS ...
Page 74: ...12 3 Model HCFU 36CM03 R1 HCFU 42CM03 R1 indoor unit EXPLODED VIEWS PARTS LISTS ...
Page 76: ...HBU 36CM03 R1 HBU 42CM03 R1 Outdoor Units EXPLODED VIEWS PARTS LISTS ...
Page 84: ...14 NOISE LEVEL TEST CHART NOISE LEVEL TEST CHART ...
Page 91: ...Sincere Forever Tel 86 532 8938356 Web site http www haier com ...