The communication fault
between IPM and outdoor PCB
Outdoor display: LED1 flash 4 times
Method of Communication is detected by checking the IPM module and the outdoor PCB
Malfunction
Detection
Malfunction
■
The outdoor PCB broken leads to communication fault
Decision
■
The IPM module broken leads to communication fault
Conditions
Supposed
■
The outdoor PCB is broken
Causes
■
The IPM module is broken
■
Communication wiring disconnected
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
1) Check whether plug of MODULE COM and MODULE POWER on the outdoor
PCB and IPM module is tight connected
2) Check whether the connection of P & N wire between IPM and outdoor is tight
Is the connection OK?
1.Check whether the voltage between 1
and 2 of Module Power
is about DC5V,
2.Check whether the voltage between2
and 3 of Module Power is about DC15V,
Replace outdoor PCB
Replace power module
YES
NO
NO
YES
Malfunction unsolved
1) Pull out and reinsert the terminals.
2) Replace connected wire
Seivice diagnosis
Domestic air conditioner
39
Summary of Contents for 1U26QE4ERA
Page 14: ...Operation range Domestic air conditioner 5 Operation range 12 10 0 20 16 32 10 20 15 ...
Page 64: ...Circuit diagrams 62 Domestic air conditioner ...
Page 65: ...Circuit diagrams Domestic air conditioner 12 2 Module board Circuit Diagram 63 ...
Page 70: ...Removal Procedure 2 Removal of Electrical Box 3 Domestic Air Conditioner ...