.3.
4
IPM protection
Outdoor display LED1 flash 2 times
Method of IPM protection is detected by checking the compressor running condition and so on
Malfunction
Detection
Malfunction
■
The system leads to IPM protection due to over current
Decision
■
The compressor faulty leads to IPM protection
Conditions
■
circuit component of IPM is broken and led to IPM protection
Supposed
■
IPM protection dues to the compressor faulty
Causes
■
IPM protection dues to faulty PCB of IPM module
■
Compressor wiring disconnected
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Turn on the unit.
whether the error is displayed before
compressor start?
The power module is fault,
need replaced
1
ǃ
The system may have been over or under charged with gas, which can be judged through the pressure of the
measuring system.
2
ǃ
The shaft of compressor is seized and the compressor needs replacing.
<(6
12
The compressor is started normally, but
malfunctions are reported after it has run for a
while.
Seivice diagnosis
Domestic air conditioner
37
Summary of Contents for 1U26QE4ERA
Page 14: ...Operation range Domestic air conditioner 5 Operation range 12 10 0 20 16 32 10 20 15 ...
Page 64: ...Circuit diagrams 62 Domestic air conditioner ...
Page 65: ...Circuit diagrams Domestic air conditioner 12 2 Module board Circuit Diagram 63 ...
Page 70: ...Removal Procedure 2 Removal of Electrical Box 3 Domestic Air Conditioner ...