HAI RC-90 Installation Instructions Manual Download Page 12

1

1

2

2

 

 

Setting 

Cycles per hour (maximum) 

5 6 
6 5 
7 4 
8 3.7 

10 3 

 
The recommended setting is 8 minutes.  A higher setting may be appropriate for buildings with low heat 
loss/gain.  The default setting is 8. 
 
12 

Heating minimum on/off time (minutes) 

 
This item is the same as the “Cooling minimum on/off time”, but for heating.  The default setting is 8. 
 
13 Not 

used

 

 
14 Clock 

adjust 

 
If the clock on the thermostat is running faster or slower than the actual time, you can have the thermostat 
automatically compensate up to 29 seconds per day.  The thermostat will add or subtract the selected amount of 
time daily. 
 
(1 = “- 29” to 59 = “+ 29” seconds per day; 30 = No change) 
 
The default setting is 30. 
 
Note:  If an HAI automation system is being used, the controller system time is sent to the thermostat every 
minute.  This adjustment will have no effect. 
 
15 Filter 

reminder 

 
The thermostat logs the amount of time the system fan has been running.  When this setting reaches 0, the 
thermostat will display a reminder to replace the filter.  The setting is the amount of days (24 hours of system 
operation) before this reminder is displayed. 
 
Days - Counting down from 10 - 0 
 
The filter reminder can be disabled by setting this item to 60. 
 
16 

System runtime (This week) 

 
This item logs the amount of time (hours) that the heating and cooling system was in operation this week. 
 
17 

System runtime (Last week) 

 
This item logs the amount of time (hours) that the heating and cooling system was in operation last week. 

Summary of Contents for RC-90

Page 1: ...eptable in the country in which this equipment is to be installed INSTALLATION Before installing this thermostat 1 Read all of the installation instructions carefully Read the Owner s Manual carefully...

Page 2: ...TING When mounting the RC 90 grasp the thermostat by the sides avoiding the keys and unsnap the base from the face Holding the base to the wall so that the word TOP is upright and facing you 1 Mark th...

Page 3: ...ation See Figures 9 10 Insert the cable into the connector on the thermostat circuit board marked COMM Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug th...

Page 4: ...check wiring be sure that there are no stray wires or wire strands at the connections 2 It is not necessary to connect the remote system COMM cable at this time 3 Connect power to the control transfo...

Page 5: ...5 5 Figure 5 Installation as a Master thermostat...

Page 6: ...6 6 Figure 6 Installation as a Slave thermostat Figure 7 Installation as a Zone thermostat with separate transformer Required by some zone panels...

Page 7: ...EAT COOL or OFF CONFIGURING THE BACKLIGHT ON THE RC 90B The backlight on the RC 90B can be configured to one of three different modes 1 on for 30 seconds when a key is pressed 2 always on or 3 always...

Page 8: ...play are the item number 2 The large blinking digits in the center of the display are the value of the item number 3 Press the Prog key to advance to the next item 4 Press the Hold key to return to th...

Page 9: ...ferent modes These modes are 0 300 baud RS 232 mode for use with personal computers 1 100 baud System mode OmniLT Omni Omni II OmniPro and OmniPro II systems 8 PESM mode use with Model 1503 automation...

Page 10: ...minder displays add 16 to each value The default setting is 1 04 Calibration offset This item is used to raise or lower the current temperature reading by 1 degree Fahrenheit or 1 2 degree Celsius If...

Page 11: ...d heat setting is reached This is done to avoid overheating the air while the walls and furniture catch up A setting of 0 will disable this feature 0 No anticipation 3 5 Normal anticipation 10 Maximum...

Page 12: ...y 30 No change The default setting is 30 Note If an HAI automation system is being used the controller system time is sent to the thermostat every minute This adjustment will have no effect 15 Filter...

Page 13: ...ing minimum on off time 8 12 Heating minimum on off time 8 13 Not used 14 Clock adjust 30 15 Filter reminder 10 16 System runtime This week 17 System runtime Last week REMOTE SYSTEM WIRING DIAGRAMS Th...

Page 14: ...TAT Connect the red COMM cable wire with the black COMM cable wire Make the connections as shown in Figure 9 using the supplied wire splices Note Do not connect the red COMM cable wire to 12V Figure 9...

Page 15: ...be set to 24 Run a two conductor wire from the remote system or remote switch to the thermostat location Make the connections using supplied wire splices See Figure 10 Red and yellow wires are not us...

Page 16: ...at keys for test remove jumper SYMPTOM ACTION TO TAKE 1 Check COMM connector and wiring 2 Check thermostat address setting 3 Check communications mode setting Control By Remote System Not Working 4 Ch...

Reviews: