CONNECTING TO OMNI II / OMNIPRO II
Connect the "Yellow" and "Green" wires from the touchscreen to the "A" and "B" terminals
under the section marked "CONSOLE" on the controller, respectively. Connect the "Red" and
"Black" wires from the touchscreen to the "12V" and "GND" terminals under the section
marked "AUXILIARY" on the controller, respectively.
A maximum combination of 8 touchscreens and consoles can be used with Omni II and a
maximum combination of 16 with OmniPro II.
NOTE: Do not exceed the maximum current limitation of the controller. If more than 2
touchscreens are used, the additional touchscreens must be powered from an external
power supply. THE EXTERNAL POWER SUPPLY MUST BE GROUNDED TO THE
CONTROLLER EARTH GROUND TO AVOID DAMAGE TO THE TOUCHSCREEN.
BLACK
RED
GREEN
YELLOW
CONNECT ENDS OF SUPPLIED
CABLE TO CORRESPONDING ENDS
OF THE POWER/COMMUNICATION
CABLE FROM THE CONTROLLER
SUPPLIED CABLE
(PLUGS INTO J6)
GR
E
E
N
YEL
L
O
W
BL
AC
K
RE
D
Omni II / OmniPro II Controller Connections