Tools needed
1
Panelboard
User Instructions
Indication position
performa elite400
Note: Only licensed Electrical
Installer
s are
to do any installation to panelboards.
The electrical
installer
is to ensure that the
panelboard meets site specific requirements.
Final installation is to meet all rules as
described
in AS/NZS 3000:20
1
8.
Switchboard Mounting
The electrical
installer
must ensure that the
support structure or wall is adequate to support
the weight of the panelboard. All cables
entering
or exiting the switchboard are to be via
a gland
or sealed as required. All panelboards
have
lockable doors suitable for restricted areas
as per AS/NZS 61439
Switchgear mounting in Panelboard
The electrical
installer
is to ascertain that
all installed devices are suitable to meet the
appropriate fault current ratings required.
The chassis on this panel board is suitable for
Hager 10kA type of MCBs and RCBOs and
was designed to suit only Hager MCBs. Hager
recommends fitting only Hager approved
switchgear otherwise this may void warranty.
If the fault level at the switchboard is greater
than the MCB fault rating, they must be backed
up by current limiting fuses or current limiting
circuit breakers. For backup protection levels,
refer to Hager. Devices are to be mounted with
the DIN clip toward the centre of the enclosure.
Transportation may cause terminations,
mechanical supports and other connections to
become loose. The electrical
installer
is
to ensure all these connections are tightened
prior to any energisation.
Final overview prior to Energisation
Review alignment of all devices and ensure
there has been no damage during final
terminations. The panelboard is to be cleaned
and vacuumed from filings and other foreign
objects after final terminations are completed.
Board Mounting
Earth and Neutral Links
Neutral bars
integrated neutral bars
Neutral bar size (mm)
12x9
Split neutral
As standard
Earth bars
Earth bars both sides
Earth bar size (mm)
12x9
Earth and neutral
bar tunnels
Single screw tunnel
Ø7mm (up to 25mm
2
cable) solid and
stranded conductors
Earth and neutral
bar connection
Single stud
(M6 = 2.5Nm)
Earth and neutral
bar rating
250A
H
D
W
C
E
A
B
F
E = Central keyhole fixing point
A
E
Pozidrive
PZ3
4.5mm
performa elite400 user instruction
1
6 7
8
9
10
11
12
13
14
15
16
2
3
4
5
Enclosure dimensions (mm)
Standard
Chassis
H
W
D
A
B
C
F
JPE3600
1200 600
250
350 900
560
1222
JPE4800
1200 600
250
350 900
560
1222
JPE6000
1400 600
250
350 1100 560
1422
JPE7200
1400 600
250
350 1100 560
1422
JPE9600
1600 600
250
350 1300 560
1622
JPE0EX
elite extension
400
600
250
350 150
560
422
Hybrid
Chassis
H
W
D
A
B
C
F
JPE0612
1
0
00 600
250
350 700
560
1022
JPE0624
1
2
00 600
250
350 900
560
1222
JPE0636
1
2
00 600
250
350 900
560
1222
JPE1248
1400 600
250
350 1100 560
1422