Tools needed

1

Panelboard

User Instructions

Indication position

performa elite400

Note: Only licensed Electrical 

Installer

s are 

to do any installation to panelboards.

 

The electrical 

installer

 is to ensure that the 

panelboard meets site specific requirements. 

Final installation is to meet all rules as 
described 

in AS/NZS 3000:20

1

8.

Switchboard Mounting 

 

The electrical 

installer

 must ensure that the 

support structure or wall is adequate to support 

 

the weight of the panelboard. All cables 
entering 

or exiting the switchboard are to be via 

a gland 

or sealed as required. All panelboards 

have 

lockable doors suitable for restricted areas 

as per AS/NZS 61439

Switchgear mounting in Panelboard

  

The electrical 

installer

 is to ascertain that 

all installed devices are suitable to meet the 

appropriate fault current ratings required.

 

The chassis on this panel board is suitable for 
Hager 10kA type of MCBs and RCBOs and 

was designed to suit only Hager MCBs. Hager 
recommends fitting only Hager approved 
switchgear otherwise this may void warranty. 

If the fault level at the switchboard is greater 
than the MCB fault rating, they must be backed 
up by current limiting fuses or current limiting 

circuit breakers. For backup protection levels, 
refer to Hager. Devices are to be mounted with 
the DIN clip toward the centre of the enclosure. 

Transportation may cause terminations, 
mechanical supports and other connections to 

become loose. The electrical 

installer

 is 

 

to ensure all these connections are tightened 

prior to any energisation.

Final overview prior to Energisation

Review alignment of all devices and ensure 

there has been no damage during final 
terminations. The panelboard is to be cleaned 
and vacuumed from filings and other foreign 
objects after final terminations are completed.

Board Mounting

Earth and Neutral Links

Neutral bars

integrated neutral bars

Neutral bar size (mm)

12x9

Split neutral

As standard

Earth bars

Earth bars both sides

Earth bar size (mm)

12x9

Earth and neutral 

bar tunnels

Single screw tunnel 

Ø7mm (up to 25mm

2

 

cable) solid and 

stranded conductors

Earth and neutral 

bar connection

Single stud  

(M6 = 2.5Nm)

Earth and neutral 

bar rating

250A

H

D

W

C

E

A

B

F

E =  Central keyhole fixing point

A

E

Pozidrive 
PZ3

4.5mm

performa elite400 user instruction

1

6 7

8

9

10

11

12

13

14

15

16

2

3

4

5

Enclosure dimensions (mm)

Standard 

Chassis

H

W

D

A

B

C

F

JPE3600

1200 600

250

350 900

560

1222

JPE4800 

1200 600

250

350 900

560

1222

JPE6000

1400 600

250

350 1100 560

1422

JPE7200

1400 600

250

350 1100 560

1422

JPE9600

1600 600

250

350 1300 560

1622

JPE0EX 

elite extension

400

600

250

350 150

560

422

Hybrid

Chassis

H

W

D

A

B

C

F

JPE0612

1

0

00 600

250

350 700

560

1022

JPE0624

1

2

00 600

250

350 900

560

1222

JPE0636

1

2

00 600

250

350 900

560

1222

JPE1248

1400 600

250

350 1100 560

1422