400A Incomer kits contain:
•
3 x Phase extension links
(per Phase)
•
2 x Neutral links (doubled up
- 4 Pole only)
•
4
x spreader links
•
6 x Phase link Allen fixing bolts and washers (M10)
•
4 x Long fixing screws
•
1 x MCCB
•
3 x M
10 Bolts
•
Terminal covers
Ensure terminal shrouds are
removed before fitting.
JF6
/8
3&
4
Pole
P
400A
Electronic
MCCB incomer kit
JF
8
43P4 & JF
8
44P4
Fit the MCCB to the pan assembly with the fixings provided
Fit the spreader links to the bottom of the |MCCB with the
fixings
Connect the extension links to the busbar with the 3
x M10 coach bolts.
H
and tighten at this stage.
Now tighten the MCCB fixing screws to secure the MCCB to
the pan assembly.
Once the MCCB is in place tighten all M10 electrical
connections to
18
Nm
ZD0741
Issue
6
Remove the busbar shield.
Prepare the Phase links as shown (3 per Phase)
2 off Neutral links doubled up
if 4 pole
Fit the terminal shrouds
JF
8
44P4 Shown for illustration
Fit the MCCB to the
pan assembly with
the fixing screws