Service Conditions 

Hager distribution boards must only be fitted with Hager Equipment and 
arrangements specified in Hager Technical documents and catalogues. 
Indoor Use Only 
Pollution degree:  3 
Forms of separation:  Form 3b when outgoing shrouds are fitted.  A 
competent person must always complete a risk assessment and appropriate 
test to confirm that, the un-shrouded neutral within the Panelboard is not a 
hazardous live part.  In particular, The Electricity at Work Regulations 1989 
including any amendments must be complied with. 

Note 1 - 

or rating of main incomer whichever is lower 

(I

nc

Diversity/Loading Factor

/RDF

 

0.7  
0.6   

Performance Characteristics 

Panelboard to BS EN 61439-2 (unless stated otherwise)

 

690V a.c. 50Hz 

415V a.c. 50Hz 

6kV 

(Subject to 

compliance

 with relevant regulations in the current edition of BS

 

7671) 

Warranty 

This distribution board is offered with a 24 month warranty against defective 
material or manufacture. If a warranty claim is necessary, please call the 
technical support number given at the bottom of the page and we will be 
pleased to help. 

J

F6/JF8

 Incomer 

Ki

ts 

JF

6/JF8

 Accessories 

JF003BP 
JN001BP 
JFPLATE 
JF801E 
JF801EG
JF803E 
JF803EG 

JF805DK

JF805E 

JF

806E

JF806DK

3P BLANKING PLATE 250A FRAME 
1P BLANKING PLATE 125A FRAME 
JF4 & 8 ENDPLATE 
SMALL DIN RAIL BOX, PLAIN DOOR 
SMALL DIN RAIL BOX GLAZED DOOR

 

 

LARGE DIN RAIL BOX, PLAIN DOOR 
LARGE DIN RAIL BOX, GLAZED DOOR

 

DOOR KIT FOR SMALL SPREADER BOX

 

SMALL  SPREADER  BOX  (NO  DOOR) 

LARGE  S

PREADER  BOX  (NO  DOOR) 

DOOR KIT FOR LARGE SPREADER BOX

ZD0741

 Issue 

6

JF

6/JF8

 

Surge Protection Kit

JF8

61SPD

 

Type 1+2 Surge Protection Kit

 

JF

6/JF8

 

Incoming Meter Kit

 

JF8

03MID

 

MID Multifunction Meter Pack

6

0

0A

 

415 a.c.  50Hz  

800A 

415 a.c.  50Hz 

Maximum C

 

urrent (l

nA

JF6**/JF8** Using outgoing x160 / P250 MCCB

 

JF6**/JF8** 

Using outgoing x160 / P250 MCCB             

50Hz 

TNC-S, TN-S and

 TT

 

IK05

Electromagnetic compatibility (EMC) classification

 

EMC Environment B

 

Metallic Enclosure

 

Class 1

Wall mounted stationary 
assembly fixed

 Ui 

Ue 

Uimp 

Rated Frequ

ency

 

   

Suitable earthing system 

Mechanical Impact Protection

 

T

ype F

 

No. of Main Circuits

 with x Frame MCCB's

 

6 to 9 inclusive 
10 and above 

Diversity factor for P250 Frame devices           0.6 RDF for 6 way and above.

Range of out

 

going devices

 

MCCB x160 frame

         16 - 125A

MCCB x250 frame

         100 – 250A

MCCB p250 frame

         40 – 250A

MCCB

 BS EN 6

0947

-2

J

K222PK

 

KEY LOCK WITH ONE KEY

 

*NOTE - Dimensions can be found on the hager web site www.hager.com/uk.

IP3X with 

do

or closed 

IP2X

 

with

 

do

or

 

open

 

and

 

compliment

 

of outgoing devices and blanks fitted. Suitable

for Fixed Connection (FF) Forms of Internal Separation 3b 

Max cable capacity 

Cat Ref

JF844BSW

M12 Lug

JF864BSW

M12 Lug

M12 Lug

*800LBS
JF884BD

M12 Lug

JF843BM

M12 Lug

JF844BM

M12 Lug

JF863BM

*4 Pole 400A H3+ MCCB Incomer Kit Electronic LSI MCCB

*Note Compatible with P range of MCCB's

M12 Lug

JF864BM

4 Pole 400A Load Break Switch 25kA

4 Pole 630A Load Break Switch 25kA

4 Pole 800A Load Break Switch

800A Direct Connection Kit 4 Pole
3 Pole 400A MCCB Incomer Kit 50kA Electronic LSI MCCB 

4 Pole 400A MCCB Incomer Kit Electronic LSI MCCB

3 Pole 630A MCCB Incomer Kit 50kA Electronic LSI MCCB 

4 Pole 630A MCCB Incomer Kit 50kA Electronic LSI MCCB 

M10 Lug

*3 Pole 400A H3+ MCCB Incomer Kit 50kA Electronic LSI MCCB  M12 Lug

JF843

P4

M12 Lug

JF844

P4

Short Circuit Withstand Ratings:-
Main busbar:

  JF6/JF8 range  

  Icw 35 kA for 1 sec / Ipk 73.5 kA

  Icc 50 kA rms conditional / Ipk 105 kA 

Main Neutral arrangement:

  JF6/JF8 range  

  Icw 24 kA for 1 sec / Ipk 50.4 kA

Main Earth arrangement:

  JF6/JF8 range  

  Icc 25 kA 1-ph conditional / Ipk 52.5 kA

Distribution busbars:

  x160  

  Icc 25 kA rms conditional / Ipk 52.5 kA 

  x250  

  Icc 40 kA rms conditional / Ipk 84.0 kA 

  P250  

  Icc 40 kA rms conditional / Ipk 84.0 kA 

Main Incomers:

  JF884BD  

  Icw 35 kA for 1 sec / Ipk 73.5 kA

  Icc 40 kA rms conditional / Ipk 84.0 kA 

  JF843P4/JF844P4  

  Icc 50 kA rms conditional / Ipk 105 kA

  JF863BM/JF864BM  

  Icc 50 kA rms conditional / Ipk 105 kA

  JF843BM/JF844BM  

  Icc 50 kA rms conditional / Ipk 105 kA

  JF864BSW  

  Icc 50 kA rms conditional / Ipk 105 kA (backup fuses)

*800LBS 

  Icc 50 kA rms conditional / Ipk 105 kA (backup fuses)

Summary of Contents for Invicta 3 JF8 B Series

Page 1: ...Health and Safety at Work Act shall be complied with Only equipment and arrangements specified in Hager s technical documentation catalogue shall be used Install in the vertical plane only with the r...

Page 2: ...Fixing points with central keyhole ZD0741 Issue 6...

Page 3: ...erminal shrouds are removed before fitting JF6 8 3 Pole h 400A MCCB incomer kit 1 2 Connect the extension links to the busbar with the 3 x M10 coach bolts Hand tighten at this stage Now tighten the MC...

Page 4: ...mbly with the fixings provided Fit the spreader links to the bottom of the MCCB with the fixings Connect the extension links to the busbar with the 3 x M10 coach bolts Hand tighten at this stage Now t...

Page 5: ...n links to the busbar with the 3 x M10 coach bolts Hand tighten at this stage Now tighten the MCCB fixing screws to secure the MCCB to the pan assembly Once the MCCB is in place tighten all M10 electr...

Page 6: ...M10 coach bolts the M8 coach bolts Hand tighten at this stage Connect the 2 neutral links with the M8 coach bolts making sure they are fitted under the Neutral phase of the MCCB Hand tighten at this s...

Page 7: ...er and fit the switch to the pan assembly with the M6 fixings provided Fit the rear terminal shield A Connect the extension links to the busbar with the 3 x M10 coach bolts Hand tighten at this stage...

Page 8: ...ect strap o 3 x M6 bolt spring washer flat washer o 6 x M12 bolt flat washer carp nut o 1 x insulation barrier Lower direct connection shield o 4 x M6 fixing bolts for shield Front cover adapter plate...

Page 9: ...6Nm Only equipment and arrangements specified in Hager s technical documentation catalogue shall be used ZD0741 Issue 6 Mount the MCCB on to the busbar finger with the red trip button facing inwards...

Page 10: ...plete inner cut out width 10mm Cable 16mm Cable 15mm 25mm 13mm complete inner cut out width 25mm Cable 35mm Cable Achieving Form 3b type 2 on x250 P250 frame MCCB outgoing Using HYB021H 3 Pole HYB022H...

Page 11: ...ounted stationary assembly fixed Ui Ue Uimp Rated Frequency Suitable earthing system Mechanical Impact Protection Type F No of Main Circuits with x Frame MCCB s 6 to 9 inclusive 10 and above Diversity...

Page 12: ...D B No Voltage Supplied From Supply cable mm Incoming Isolator Ze P S C CIR AMPS TYPE CABLE MM C P C MM LOCATION DESCRIPTION Panel board circuit designation chart ZD0741 Issue 6...

Page 13: ...D B No Voltage Supplied From Supply cable mm Incoming Isolator Ze P S C CIR AMPS TYPE CABLE MM C P C MM LOCATION DESCRIPTION ZD0741 Issue 6...

Page 14: ...Hager Ltd Hortonwood 50 Telford Shropshire TF1 7FT www hager com uk National Sales Hotline 01952 675612 National Tech Support helpline 01952 675689 ZD0741 issue 6...

Reviews: