background image

3

www.hager.com

6E 6101C

6E

61

01

C

OFF

EG010

§

1 channel time switch - daily cycle User instruction

Function

The EG010 is a programmable time switch for

the automatic control of electrical loads.

The clock contains 5 pre-programmed (user

adjustable) time periods, based on one, two or

three switchings per day.
The front cover is sealable preventing

unauthorised access after completion of

programming.

Presentation :

Display :

Œ

time



output contact (ON or OFF)

Ž

program selected

Buttons :



P

” to select the program to apply



to scroll program steps

‘

reset

’

+

” and “

-

” : change settings

Time setting

Press key “

+

” or “

-

”.

A continuous pressure on this key will scroll up

or down minutes and then hours.

Programming

1. select one of the programs described below.

2. modify switching time, if necessary.

3. the program selected will be applied on a daily

basis.

To modify a program

1. select with key “

P

” the program to modify.

2. scroll program steps with the key

.

3. modify the switching time with keys “

+

” or “

-

”.

4. press key

, to display the next program

step and modify it, if necessary.

5. press “

P

” to confirm all modifications are complete

and switch back to automatic mode.

6. a small mark (*) appears next to the program

number, to indicate that the program has been

modified.

To override the circuit ON or OFF

Press “

P

” and select P0 to override the circuit OFF.

Press “

P

” and select P1 to override the circuit ON.

To switch back to automatic mode, press key “

P

and select the program applied previously (P2, P3

or P4).

For example :

Control an electrical equipment with program P3.

1. press key “

P

until «P3» is displayed.

2. if the pre-programmed switching time meets your

requirements, then programming is complete.

OFF

P

-

+

6

7

4

3

1

5

2

P0

P1

P2

P3

P4

6.00

8.00

11.00

13.00

17.00

23.00

6.00

8.00

17.00

23.00

6.00

23.00

ON

OFF

P

Prog

Example :

You have selected the program P3, but you want to

switch on the electrical equipment at 16h45 instead

of 17h00.

1. press key “

P

to select the program P3.

2. press

until display «17:00».

3. press “

-

until display «16:45».

4. press “

P

” to confirm and switch

back to automatic mode.

L

N

6

5

2

1

4

3

EG 010

1 2

3

Technical specifications

Electrical characteristics

- supply voltage 230V

+10%/-15% 50Hz/60Hz

- power consumption

= 1 VA

- output

1 changeover contact

µ 16A - 230V

AC1

µ 3A - 230V

cos

φ

= 0,6

- protection degree

IP20

- insulation class

II

- maximum operating height

2000m

- rated impulse voltage

4 kV

Functional characteristics

- accuracy

± 1sec / day at 20 °C

- operating reserve

lithium battery total of three years

- action type

1B

- degree of pollution

2

- software class

A

Environment

- operating temperature

-10 to +50 °C

- storage temperature

-10 to +60 °C

- temperature for the ball pressure Test

75° to 125°C

Connection tunnel terminals

- flexible

0.5 to 2.5 mm

2

- rigid

0.5 to 4 mm

2

Standards

60730-1

60730-2-7

Electrical connections

OFF

OFF

ON

ON

*

To check your settings

Press repeatedly key

, to display program

steps : switching time and circuit status

(ON or OFF).
To switch back to automatic mode press key

P

”.

To reset the time switch

Press the “

reset

” button. This will cancel all

modifications made on pre-programmed

settings.

§

Warranty

NOT APPLICABLE FOR AUSTRALIA

A warranty period of 24 months is offered on hager

products, from date of manufacture, relating to any material

of manufacturing defect. If any product is found to be

defective it must be returned via the installer and supplier

(wholesaler). The warranty is withdrawn if:

- after inspection by hager quality control dept the device is

found to have been installed in a manner which is contrary

to IEE wiring regulations and accepted practice within the

industry at the time of installation.

- The procedure for the return of goods has not been

followed. Explanation of defect must be included when

returning goods.

This device must be installed only by

a qualified electrician according to the

installation standards in force in the

country.

Usable in all Europe

å

and in Switzerland

Reviews: