Action

Settings 

Potentiometers

Use Auto settings 

(factory) or set by 

the programming 

tool to switch the 

light automatically 

for a defined time.

Auto Settings

Put the Lux potentiometer on “auto test”. 

The settings are predefined:

Lux = 400,  

time = 20 min. 

q

: test mode for 2 min.

Programming tool settings EEK001

(manual settings inhibited). 

auto

test

1 min

1 h

20 min 

on

lux

1 min

1 h

20 min 

on

lux

on

lux

on

lux

auto

test

auto

test

auto

test

Automatically switch 

on the light for a 

defined time.

Installer settings

auto

test

1 min

1 h

20 min 

on

lux

1 min

1 h

20 min 

on

lux

on

lux

on

lux

auto

test

auto

test

auto

test

Test and validate the 

detection zone.

Test mode 

Move the potentiometer 1 to “auto test”.  

On this position, the programming tool 

EEK001 can be used.

auto

test

1 min

1 h

20 min 

on

lux

1 min

1 h

20 min 

on

lux

on

lux

on

lux

auto

test

auto

test

auto

test

Technical characteristics

Electrical characteristics

Supply voltage 

230V~ +10/-15% 50/60Hz

  

240V~ +/-6% 50/60Hz

Consumption with no load 

2,4 VA / 270 mW

Upstream protection 

circuit breaker 16 A 

Functional characteristics

Lighting output operating time 

1 min. 

 1 h

Brightness level 

 1000 Lux

Recommended installation height 

2,5 

 3,5 m

Detection range 

Ø 7 m 

  

(installed product height: 2.5 m) 

Fixing accessorie 

  

Screws ( No 8), Protective cover

  

Products can be connected in parallel.

Hole size required  

60 mm

Environment

Storage  temperature 

-20 °C 

  +60 °C

Class of insulation 

II 

IK 03 

Index of protection 

IP41 

Fire  resistance 

650 °C

Connection capacity (EEK510B)

  

0.5 mm2 to 1.5 mm2 flexible, 

  

0.5 mm2 to 1.5 mm2 rigid

Operating altitude  

2000m

Operating  temperature :

Factory settings

Luminosity threshold

400 lux

Lighting time

20 min.

Mode

Presence

Power Up

OFF

Active cell (Luminosity Cell)

ON

Functional modes

The detector has 2 different modes.

-  Presence detection (automatic).

-  Absence detection (semi-automatic).

The power up and cell operation can be set for each 

mode. A normally open retractive switch connected 

to the product makes it possible to reverse the 

lighting output state.
This state is maintained for the time period set 

by the potentiometer 

2

 or the programming tool 

EEK001.

Presence detection (automatic mode)

In this mode the light is controlled by motion in the 

detection area and ambient light levels.
If presence is detected whilst the light levels are 

below the required Lux level, the sensor is activated 

and keeps the light on whilst there is still occupancy 

and for the time out period afterwards. Once the 

sensor has deactivated the lights, it will require 

a new occupancy whilst the ambient light levels 

are below the required Lux levels to activate the 

lights again. This mode can be changed via the IR 

remote control EEK001 (default mode is presence 

detection: automatic).

Absence detection (semi automatic mode)

The sensor needs to be activated by a normally 

open retractive switch or a user remote control 

input. Once the sensor is activated, it will hold the 

lights on whilst there is still occupancy and for the 

time out period afterwards. Once the sensor has 

deactivated the lights, it will require another input 

from the wallswitch or the programming tool to 

switch the lights on.

Power Up

A parameter of the detector allows the choice of 

state for the lighting after power up (mains return). 

During warm up phase, the green LED blinks. In the 

Power up ON state, the lighting will automatically be 

energised when mains power is initially supplied or 

returned to the sensor. In the Power up OFF state, 

the lighting will not be energised and the sensor will 

not operate during warm up period. This parameter 

is modified using the installer programming tool 

EEK001.
POWER UP state:
•  ON: the light is immediately switched on for 30 s 

after power up. In case of detection, the light 

(in automatic mode) remains on during the time 

delay; otherwise the light is switched off.

 •  OFF: the detector switches to the selected mode 

after warm up.

Active / passive  cell

Active cell

The photocell will inhibit the output from the sensor 

if the ambient light level is sufficient.
If the sensor detects occupancy whilst the ambient 

light level is below the required Lux level, the lights 

will be activated. However if the ambient light level 

increases to a value where it is above the required 

Lux level during a certain time, the sensor will 

detect it and switch off the light.

Passive cell

The photocell will inhibit the output from the sensor 

if at the time of detection the ambient light level is 

sufficient. In case of detection, if the ambient light 

level increases, the photocell will not turn off the 

light. 

Product description  

and operating  principles

Occupancy sensors EEK are designed to detect 

low level movements (e.g. person sitting at a desk).

Different models are available:
-  without lead: EEK510B for standalone and BESA 

mounting

-  

with pre-wired lead (3 

m): EEK513W to be 

interfaced with the KLDS marshalling boxes

-  with pre-wired lead (3 m or 5 m) and klik.system 

plug to be interfaced with the KLMB marshalling 

boxes: EEK513P, EEK515P.

Detection is by means of a pyroelectric sensor 

located under the detection lens.

The occupancy sensor measures the brightness in 

the room on a continuous basis and compares it to 

the level preset on the potentiometer (or by means 

of the programming tool EEK001).

Settings

The Lux threshold and time out period can be set 

with the potentiometers or by using the installer 

programming tool (EEK001).

Test Mode - Walk test

This mode makes it possible to validate the 

detection area. To select this mode, set the 

potentiometer 

1

 to the position “auto test”. The 

green or red LED behind the lens is on for 2 seconds 

after detection. The red LED indicates that the light 

level measured is lower than current setting. If the 

green LED is on, the light level measured is higher 

than current setting.

There is a time out of 2 minutes which is reactivated 

after each detection. The output is also switched 

during 2 s. after each detection.

It is also possible to use the programming tool 

EEK001 to set the detector in test mode.

This device must be installed by a suitably 

qualified electrician according to the installa-

tion’s standards.

Correct Disposal of This product
(Waste Electrical & Electronic 

Equipment)

 

(Applicable in the European Union and other European 

countries with separate collection systems).
This marking shown on the product or its literature indicates 

that it hould not be disposed with other household wasted at 

the end of its working life. To prevent possible harm to the envi-

ronment or human health from uncontrolled waste disposal, 

please separate this from other types of wastes and recycle it 

responsibly to promote the sustainable reuse of material re-

sources.
Household users should contact either the retailer where they 

purchased this product, or their local government office, for 

details of where and how they can take this item for environ-

mentally safe recycling.
Business users should contact their supplier and check the 

terms and conditions of the purchase contract. This product 

should not be mixed with other commercial wastes of disposal.

Usable throughout Europe 

å

 

and in Switzerland

Hager Controls hereby declares that the PIR Occupancy 

Sensorsdevice complies with the essential requirements  

and other relevant provisions of Directive 2014/53/EU.

The CE declaration is available on the:

www.hagergroup.com 

16A

40°C

45°C

Temperature (C°)

Amperes (A)

10A

2

6LE000505C

Summary of Contents for EEK51 P Series

Page 1: ...et the following features if the potentiometer is set on auto test Lux levels Time Absence presence detection Power up behaviour Active passive cell Override remote control The remote control EEK002 allows the switching ON or OFF of the light The EEK002 allows the same functionality as the wallswitch M M Detection areas h Y X Y X h x y 2 5 m 2 5 m 2 5 m 6 m 1 m Overlap Occupancy Sensors standalone...

Page 2: ...gramming tool EEK001 POWER UP state ON the light is immediately switched on for 30s after power up In case of detection the light in automatic mode remains on during the time delay otherwise the light is switched off OFF the detector switches to the selected mode after warm up Active passive cell Active cell The photocell will inhibit the output from the sensor if the ambient light level is suffic...

Page 3: ...e potentiometers according to the desired values Ceiling mounting 1 Cut out a 60 63mm diameter hole using a hole saw 2 Fix the detector by pushing both springs upward then insert them into the hole 3 Wire the detector according to the recommended connection diagram or plug into the klik system marshalling box 4 Mount the protective cover over the terminals and screw the cable clamp 5 Set potentiom...

Page 4: ...llation distance from ground 2 5m 3 5m In offices the detector must be installed above the workstation When associating several detectors detection areas shall overlap Keep away from environmental disturbances heat sources partitions houseplants ventilation da white da orange black Normally open retractive switch Polarity free digital output blue brown Live 230 V 50Hz supply Neutral L Connection t...