hager EE880 Manual Download Page 3

3

6LE001319A

5

Description of the product and settings

The EE880 motion detector is sensitive to infrared 

radiation emitted as heat from a moving body. The 

detector switches on the load connected to it when a 

heat-emitting body moves within in its detection area. 

The load remains lit for the period of time to which the 

detector has been set and until it no longer detects 

movement in its surveillance area. This detector has 

been specially designed to meet the needs of corridors.

Implementation

In order to obtain optimum detection conditions, the 

following recommendations should be followed:
-  Recommended installation height: 3 metres.
-  The arrow engraved on the lens 

3

 and the arrow 

marked on the housing 

5

 must be aligned, in order 

for the detector to operate correctly.

EE880

max.

min.

Installation advice

For installation in damp locations, a drain hole 

8

 

needs to be drilled in the protective cover.

There is a cable feedthrough that can be broken open 

if necessary 

9

 on the protective cover.

Surface mounting of the EE880

1. Loosen the screws 

retaining the lid 

5

.

2. Remove the lid 

5

.

3.  Use 2 screws to fix the box 

6

 to the ceiling or wall 

(diameter 4.5 mm and length 50 mm).

4.  Wire the detector in accordance with the connection 

diagrams (see "Connections").

5. Refit the lid 

5

.

6.  Correctly tighten the two screws 

4

 retaining the lid 

5

 in order to ensure a good seal.

7. 

 

Adjust the potentiometers (see "potentiometer 

settings").

8.  Fit the protective cover 

7

. Be sure to press on the 

cover to ensure that it clips in place correctly

Important 

The detector requires 10 seconds to initialize after 

the power is switched on.

Potentiometer settings 

1

Adjustable potentiometer 

1

luminosity threshold

2

min.

max.

Adjustable potentiometer 

2

duration of operation

With a screwdriver, potentiometers 

1

 and  

2

 can 

be adjusted to set the luminosity threshold and the 

duration of operation:
•  

Luminosity threshold: 

2 to 2000 lux. 

Potentiometer 

1

 is preset to a default value of 

approximately 2000 lux.

•  

Duration of operation: 

5 s to 15 min. 

Potentiometer 

2

 is preset to a default value of 

approximately 5 s.

Z

Test Procedure

To test the operation, set the luminosity threshold 

to maximum, 

y

, and the duration of operation to 

minimum, 5 seconds; this will cause the detector 

to trigger immediately, allowing you to check the 

operation.

Learning mode

When the ambient light has reached the value at which 

the detector will turn on the light in the event of 

movement, turn potentiometer 

1

 to  . At the end of 

10 seconds, the ambient luminosity is saved. In this 

mode the red indicator LED flashes twice per second.

Functions

pulse function

On potentiometer 

2

, the pulse function applies a 

voltage to the output for 2 seconds. This function is 

not used to directly control the loads, but to control a 

stairwell timer, for example.
If a switch is installed on the detector circuit (see 

Connection), in addition to switching on and off, it has 

the following functions:

Important 

The switch needs to be actuated rapidly, between 

0.5 s and 1 s.

Operation with detector

1. To turn on the light (if the lamp is at OFF)
• 

 

Actuate the switch in the following manner 

"OFF" - "ON" i.e. 1 x OFF and ON.

The lamp remains lit for the duration set.

OFF

ON

5 s - 15 min

2. To turn off the light (if the lamp is at ON)
• 

 

Actuate the switch in the following manner 

"OFF" - "ON" i.e. 1 x OFF and ON.

The lamp turns off or returns to detection mode.

Constant lighting (4 hr)

1. To activate constant lighting
• 

 

Actuate the switch in the following manner 

"OFF" - "ON" - "OFF" - "ON" i.e. 2 x OFF and ON.

This process must be completed in less than 1.5 s.
The lamp then switches to constant lighting for 4 hours

(the red LED remains lit). It then returns automatically

to detection mode (the red LED goes off).

OFF

ON

OFF

ON

4 h

1. Deactivating constant lighting:
• 

 

Actuate the switch in the following manner 

"OFF" - "ON" i.e. 1 x OFF and ON.

The lamp turns off or returns to detection mode.

Use/maintenance

The detector is designed for automatic switching 

of lighting. However, it is not intended for use with 

antiintrusion alarms, because it is not protected 

against vandalism.
If the surface gets dirty, clean it with a damp cloth (do 

not use detergent).

Connection in parallel

Parallel implementation is possible, but care must be

taken not to exceed the maximum power that can be

connected to a detector. Moreover, all the devices

must be connected to the same phase.

Technical characteristics

 Supply  voltage 

230 V

v

  50 / 60  Hz

 Detection area

 

20 m x 4 m

 Standby  consumption 

1 W

 Duration of lighting output operation 

 

  

5  s … 15  min

 Luminosity threshold 

2… 2000 lux

 Recommended installation height 

 

3 m

 Accessoires de fixation 

  

2 screws 4.5 mm Ø and length 50 mm

 Operating temperature

 

-20 °C 

  +50 °C

 Storage temperature 

 

-35 °C 

  +70 °C

 Insulation class

 

II

 Protection rating 

IP54

 Standards  

EN 60669-2-1 

 Upstream protection 

10 A (T ≤ +35 °C)

  

6 A (+35 °C < T < +50 °C)

 Maximum installation altitude  

2000 m

 Pollution degree 

2

 Connection 

  

max 1,5 mm²

What to do if … ?

After a power cut

•  The detector continues to operate with the luminosity 

threshold indicated by potentiometer 

1

.

•  When potentiometer 

1

 is in learning mode the 

luminosity level set before the power cut is still in 

memory, the detector does not resume learning mode.

•  If it was in constant lighting mode, then the detector 

returns to detection mode.

Erratic
Detection 

Animals are moving in the detection 

area.
- Check the detection area.

The detector 

has no 

voltage

-  Upstream protection defective, 

device not in the circuit. Check 

the cable using a voltage tester, 

restore the upstream protection, 

reset the switch.

-  Short circuit 

Check the connections.

-  Additional change over switch set 

to OFF. 

Switching on.

The detector 

does not 

switch on the 

lamp

-  Faulty bulb: change the bulb.
-  During the day, the twilight setting 

is in the night position. Readjust.

-  Additional change over switch set 

to OFF. 

Switching on.

The detector 

does not 

switch off the 

lamp

-  Constant lighting activated (red 

LED lit): switch off constant 

lighting.

-  Another detector connected in 

parallel and still active: wait for the 

delay time of the other detector.

This device is to be installed only by a 

professional electrician fitter according to 

local applicable installation standards.

Usable in all Europe

 

å

 

and in Switzerland

The CE declaration can be consulted on the site: 

www.hagergroup.net

 