oPeratIon
oPeratIon
Programming
Programming
>
Volt menu
1 2
threshold detection starts from the loss of source
or source return sequence.
>
Frequency Menu
1 2
threshold detection starts from the loss of source
or source return sequence.
LCD
Denomination / Definition
Setting range
Default
values
1 2
Network over voltage threshold
From 102 to 120 % 115 %
1 2
Network over voltage threshold hysteresis
From 101 to 119 %
(< ou)
110 %
1 2
Network under voltage threshold
From 80 to 98 %
85 %
1 2
Network under voltage threshold hysteresis
From 81 to 99 %
(> uO)
95 %
1 2
Network over voltage threshold
From 102 to 120 % 115 %
1 2
Network over voltage threshold hysteresis
From 101 to 119 %
(< ou)
110 %
1 2
Network under voltage threshold
From 80 to 98 %
85 %
1 2
Network under voltage threshold hysteresis
From 81 to 99 %
(> uu)
95 %
LCD
Denomination / Definition
Setting range
Default
values
1 2
Network over voltage threshold
From 101 to 120 % 105 %
1 2
Network over voltage threshold hysteresis
From 100,5 to
119,5 % (< oF)
103 %
1 2
Network under voltage threshold
From 80 to 99 %
85 %
1 2
Network under voltage threshold hysteresis
From 80,5 to
99,5 %
(> uF)
97 %
1 2
Network over voltage threshold
From 101 to 120 % 105 %
1 2
Network over voltage threshold hysteresis
From 100,5 to
119,5 % (< oF)
103 %
1 2
Network under voltage threshold
From 80 to 99 %
95 %
1 2
Network under voltage threshold hysteresis
From 80,5 to
99,5 %
(> uF)
97 %
Values definition: % of nominal values.
Hysteresis values range is limited by thresholds values.
Values definition: % of nominal values.
Hysteresis values range is limited by thresholds values.