Esento Marine 2-4 Installation, Commissioning & Operating Manual
Approved Document UI-ESEN4MAR-01 Issue 6.0
22
SETUP & PROGRAMMING
4
2
4
2
Common fire outputs cancel on silence alarms
The Common Fire VFCO relay output and the Common Fire switched -ve output, when activated, normally
remain until the panel is RESET.
This option changes these outputs to reset on SILENCE ALARMS. This may be useful for panel interlink
purposes.
Both outputs can be programmed independently.
Enter the above code and press the ENTER button.
The red Zone 1 fire LED will illuminate, this LED represents the Common Fire VFCO relay output.
Pressing Button 1 (Disable Mode) will move to red Zone 2 fire LED which represents the Common Fire
switched -ve output. Subsequent presses will toggle between them.
With the required fire LED lit press the ENTER button and Zone 1, fire LED will pulse.
Press button 2 (Test Mode) to alter the status of the output, represented by the Zone 1, Fault LED either
off or on.
Off = Output cancels on RESET (factory default)
On = Output cancels on SILENCE ALARMS
.
When the output status has been set, press the ENTER button to return to the output selection mode.
PSU
@ +
+
-
-
+ - + -
+ - + - + - + -
28V 0V
C NC NO C NC NO
FIRE
FAULT
FR
FLT
CC
PUL
-OP -OP -IP -IP
SNDR1 SNDR2
ZONE1 ZONE2 ZONE3 ZONE4
Commmon fir
e
VFC
O r
ela
y
Common fir
e O/P
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
When finished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10
seconds and the panel will save the settings and revert back to Level 3 access mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.