Esento Marine 2-4 Installation, Commissioning & Operating Manual
Approved Document UI-ESEN4MAR-01 Issue 6.0
16
SETUP & PROGRAMMING
2
1
2
3
Panel Wide Settings
OPTION 1.
Change / Remove Keypad Access Code
There are 4 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 4 programmable
options are represented by fire zone LEDs 1 - 4.
Use button 1 to move to option required as per table;
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Fire LED Programming Option
1
Change / remove keypad access code
2
Set presence of output card
3
Inhibit muted tone beeps
4
UPS Mode / Disable battery monitoring
The keypad can be used to activate the panel controls instead of using the key switch. The default code
is 1-2-3-4, however, this can be changed. It is also possible to disable the use of a code entry to enable
controls, forcing the use of the key switch only.
With the zone 1 fire LED lit, press the ENTER button. Zone 1 fire LED will pulse to indicate ‘edit mode’ and
the amber, fault LEDs will start to rapidly pulse in sequence to show the currently set code.
Enter the new code slowly and deliberately, one number at a time using buttons 1 - 4
Note: Enable Controls codes must always start with a 1 or 2.
When finished entering the new four digit code, press the ENTER button. The panel will then confirm the
new code with rapidly pulsing LEDs in sequence and zone 1 fire LED will return to steady ‘view mode’.
Changing the keypad code to 1 - 1 - 1 - 1 will disable the use of a keypad to enable controls.
Press button 1 to move to next option or hold button 1 for 3
seconds to exit programming mode 2-1-2-3. (The panel will
confirm the new access code one more time before exiting the
programming mode).
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps