SETUP & PROGRAMMING
REPEATER MIMIC DISPLAY MODE
It is possible for the repeater to mimic either the first 12 zones in the network or a particular control panel
in the network. Apart from the first 12 zones it is not possible to choose ranges of zones from different
control panels.
Programmming code 4443 option 7 sets up the repeater’s mimic display mode.
First select the repeater panel for editing and move to option 7 as described on the previous page. Press
the ENTER button to invoke edit mode. The current setting is displayed in a binary code using LEDs 7, 8,
9 & 10 as per table below.
Whilst in edit mode use buttons 2 & 4 respectively to increment or decrement the binary indications to the
required setting as descibed in the table.
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
Option (zone 7 fire LED pulsing)
Zone 7 Fault LED Zone 8 Fault LED Zone 9 Fault LED
Zone 10 Fault LED
Repeat Master Panel
OFF
OFF
OFF
OFF
Repeat Slave Panel 1
ON
OFF
OFF
OFF
Repeat Slave Panel 2
OFF
ON
OFF
OFF
Repeat Slave Panel 3
ON
ON
OFF
OFF
Repeat Slave Panel 4
OFF
OFF
ON
OFF
Repeat Slave Panel 5
ON
OFF
ON
OFF
Repeat Slave Panel 6
OFF
ON
ON
OFF
Repeat Slave Panel 7
ON
ON
ON
OFF
Display first 12 zones
OFF
OFF
OFF
ON