Installation, Commissioning & 

Operating Manual

EN54 APPROVED 2 - 4 ZONE CONVENTIONAL CONTROL 

PANEL

Approved Document UI-ECL-01 Issue 8.0

810a/03

Summary of Contents for Esento Eclipse ECL-2

Page 1: ...Installation Commissioning Operating Manual EN54 APPROVED 2 4 ZONE CONVENTIONAL CONTROL PANEL Approved Document UI ECL 01 Issue 8 0 810a 03 ...

Page 2: ...responsibility of the This fire alarm system requires periodic checks as specified in BS 5839 Part 1 It is the responsibility of the system user to ensure it is regularly serviced and maintained in good working order system user to ensure it is regularly serviced and maintained in good working order Disclaimer Disclaimer No responsibility can be accepted by the manufacturer or distributors of this...

Page 3: ...C 11 INSTALLATION 12 SAFETY 12 ESD PRECAUTIONS 13 GENERAL 13 MOUNTING THE CABINET 13 MAINS CONNECTIONS 14 CONNECTING THE BATTERIES 15 SETUP PROGRAMMING 16 TWIN WIRE MODE 16 LEVEL 3 ENGINEERING OPTIONS 17 ZONE INTERFACE FUNCTION 25 OPERATING 26 PANEL CONTROLS INDICATIONS 26 DISABLE MODE 28 TEST MODE 29 FAULT DIAGNOSIS 30 FUNCTIONALITY DURING A SYSTEM FAULT 31 USER INSTRUCTIONS 31 SERVICE MAINTENANC...

Page 4: ...ccess to the function options The three main buttons RESOUND red SILENCE system and allow access to the function options The three main buttons RESOUND red SILENCE blue and RESET green being much larger and colour coded to assist the end users blue and RESET green being much larger and colour coded to assist the end users Two or four fire zone circuits are provided plus two monitored sounder circu...

Page 5: ...Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 3 ABOUT THIS PANEL CABINET Fire Detection System 57mm 80mm 260mm 308mm 250mm 300mm ...

Page 6: ...ABOUT THIS PANEL CIRCUIT BOARDS Eclipse panels comprise of two circuit boards PSU 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 BATTERY 1 2 3 ON 1 2 3 4 ENTER RESOUND SILENCE RESET TPCA01 E2 E4 2 or 4 zone Master PCB TPCA02 LED Display Controls PCB ...

Page 7: ... 500mA 28v input for power supply Temperature compensation voltage control link Commmon fire VFCO relay unfused Max 3A 30vdc Commmon fault VFCO relay maintained fail safe unfused Max 3A 30vdc Common fire O P Common fault O P Alert pulses sounders Precint class change activates sounders Switched ve inputs Switched ve outputs Max load 40mA To 0 volts Relay Coil Conventional monitored sounder circuit...

Page 8: ...rent 3 amps Input voltage 22vdc to 32vdc 28v 0v power output 28vdc supply output for fire alarm accessory relays etc Max continuous use 400mA Fused 500mA Fuse 500mA resettable fuse Common fire relay Fire relay contact Clean C O Max 3A 30vdc Unfused Common fault relay Maintained fault relay contact Clean C O Max 3A 30vdc Unfused Outputs FR FLT Switched ve voltage outputs for relay control Overload ...

Page 9: ...ample 4 Zone I min 85mA 2 Zone I min 75mA Maximum ripple 120 mV p p Supply and charger fault monitored Min max battery size and type 2 x 3 2Ahr 12volt VRLA Use Yuasa NP range batteries Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval Battery charging voltage 27 3 vdc nominal at 20 deg C Temperature compensated Battery charging output current 1 5A PS...

Page 10: ...giving an actual coverage of 112m2 per device When mounted on a flat ceiling heat detection devices have an individual coverage of 5 3m radius However these radii must overlap to ensure there are no blind spots Therefore individual coverage can be represented by a square measuring 7 5m x 7 5m giving an actual coverage of 56 3m2 per device Call Points A person should not have to travel more than 45...

Page 11: ...and recommended for use with that cable The screen or drain wire of circuits should be bonded to earth at recommended for use with that cable The screen or drain wire of circuits should be bonded to earth at one location only and should be continuous throughout the circuit Drain wires should be terminated in the one location only and should be continuous throughout the circuit Drain wires should b...

Page 12: ...ng Typical Conventional Sounder Circuit Wiring 4K7 OHM END OF LINE RESISTOR 4K7 OHM END OF LINE RESISTOR ZONE 1 SNDR1 R L1 L1 L2 IN OUT R L1 L1 L2 IN OUT R L1 L1 L2 IN OUT APOLLO S65 BASE 45681 201 APOLLO S65 BASE 45681 201 APOLLO S65 BASE 45681 201 MANUAL CALL POINT MCP1A R 470 1 2 3 4 _ _ 470 MOTORISED BELL POLARISED MOTORISED BELL POLARISED ELECTRONIC SOUNDER POLARISED ELECTRONIC SOUNDER POLARI...

Page 13: ...circuit the sounders are connected in reverse polarity to the detectors and call points Note Zone circuit configuration is set to Conventional by default Twin Wire mode must be set using DIL Switch 1 on Main PCB ZONE 1 APOLLO TWIN WIRE BASE 45681 206 APOLLO TWIN WIRE BASE 45681 206 TWIN WIRE CALL POINT MCP1B R TW TWIN WIRE CALL POINT MCP1B R TW 1 2 3 4 _ _ 470 1 2 3 4 _ _ 470 VE VE MOTORISED BELL ...

Page 14: ...er According to the provisions of the Act you are therefore requested to take such steps as are necessary to According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that any appropriate information about this product is made available by you to anyone concerned ensure that any appropriate information about this product is made available by y...

Page 15: ...ssed as extra low voltage and must be segregated away from mains voltage Any junction boxes used should be clearly labelled FIRE ALARM Any ancillary devices e g door retaining magnets must be powered from a separate power source Any coils or solenoids used in the system must be suppressed to avoid damage to the control equipment The site chosen for the location of the panel should be clean dry and...

Page 16: ...ins supply should be brought into the panel via one of the knockouts provided A suitable cable gland must be used to secure the outer sheath of the cable used The earth must first be connected to the primary earth stud peg marked with a symbol using a suitable ring crimp Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block whi...

Page 17: ... doesn t clear after 1 minute check connections The battery charging voltage is factory calibrated to 27 3vdc 0 2v 20o C This should not normally require adjustment Where battery problems are experienced the following information should be considered a If a battery is disconnected from the charger no voltage will appear on the output leads or terminals due to intelligent battery controls b Check t...

Page 18: ...nders and beacons need to be wired in opposite polarity to the detectors and call points i e zone positive wire connects to detector base and call point positive terminals but sounder and beacon negative terminals SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 1 2 3 ON 1 2 3 ON 1 2 3 ON 1 2 3 4 5 6 7 Switch in upward position ON To set Twin Wire mode move switch 1 on the 3 way DIL switch located on the main ...

Page 19: ...R button Then press the ENTER button again and hold for 3 seconds Any disablements or test mode settings will now clear and all engineering option parameters will revert back to factory settings The panel will bleep to acknowledge the reset RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test L...

Page 20: ...nged It is also possible to disable the use of a code entry to enable controls forcing the use of the key switch only Enter the above code and press the ENTER button The Zone Fault Disabled Test LEDs will start to rapidly pulse in sequence to show the currently set code The sequence will be repeated twice after which time the panel will automatically drop out of the set keypad entry mode Whilst th...

Page 21: ... ENTER button again will toggle the status indicated by a rapid or slow pulsing LED see below Then use Button 1 to move to the next zone If the zone has been set to not resound alarms the LED will be off If kept as default new fire condition will resound alarms then the LED will be on steady Rapid Pulse Zone is under selection and is set to have alarms resound default Slow Pulse Zone is under sele...

Page 22: ...the circuit Note Twin Wire mode is not compatible with intrinsically safe operation Detector removal monitoring EN54 The detector removal monitoring can be turned off For use with older non compliant detectors Enter the above code and press the ENTER button The zone 1 fire LED will light This indicates setting the above attributes for zone 1 The amber fault disabled test LEDs will show the current...

Page 23: ...settingoftheattributeisindicated by the amber fault disabled test LED ON or OFF Use button 2 to switch the attribute ON or OFF indicated by the amber fault disabled test LED Then use button 1 to move to the next attribute if required Press the ENTER button to return back to the zone selection indicated by a steady zone fire LED RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer...

Page 24: ... A 470Ω call point will be included in the dependency delay sequence By default this is set to off for all zones To set zones to Type A Dependency enter the above code and press the ENTER button The Aux Output Status LED will pulse slowly Zone Fault Disabled Test LEDs will show their current status see below with Zone 1 pulsing to indicate it is under selection Use Button 1 Disable Mode to move to...

Page 25: ...ith their relevant Sav Wire bases the above compatibility mode must be switched on Enter the code 2 1 3 4 Zone 1 fire LED will pulse Pressing the ENTER button will illuminate zone 1 Enter the code 2 1 3 4 Zone 1 fire LED will pulse Pressing the ENTER button will illuminate zone 1 Fault Disabled Test LED indicating that the compatibility mode is set to on Pressing the ENTER button again will toggle...

Page 26: ...uent presses will toggle between them With the required fire LED lit press the ENTER button and Zone 1 fire LED will pulse Press button 2 Test Mode to alter the status of the output represented by the Zone 1 Fault Disabled Test LED either off or on Off Output cancels on RESET factory default On Output cancels on SILENCE ALARMS When the output status has been set press the ENTER button to return to...

Page 27: ...other conventional SNDR1 SNDR2 and Twin Wire zone sounders will operate as normal A fire 470Ω signal to any other zone will operate ALL conventional SNDR1 SNDR2 and Twin Wire sounder circuits including the sounders connected to the interface zone as normal ZONE INTERFACE FUNCTION 1 2 3 ON 1 2 3 4 5 6 7 ZONE2 ZONE3 ZONE4 C NC NO NO C NC FIRE FAULT optional PANEL 1 PANEL 2 470Ω 3K3Ω Example connecti...

Page 28: ...is enabled by default but can be disabled in the engineering functions To activate the controls using the key switch turn the key clockwise to the On position The Access Level indicator LED will light and all buttons on the keypad will now be operational To deactivate the controls turn the key back to the Off position and the Access Level indicator LED will extinguish If the key switch is in the O...

Page 29: ...ing correctly This function is operational without the need to activate controls Also has the numeric value 4 for code entry ENTER This button is used to confirm code entries It can also be used for fault diagnosis see FAULT DIAGNOSIS section LED On LED Pulsing Zones in Fire 1 4 N A Indicates alarm condition in zone Zone Fault Disabled Test 1 4 Indicates zone circuit is disabled or in test mode In...

Page 30: ...ove the selection back to Zone 1 again When the desired circuit or output to be disabled is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the circuit between disabled and enabled Then use Disable Mode button again to move to the next circuit Any or all circuits can be disabled simultan...

Page 31: ...ction back to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the zone between in and out of test Then use Test Mode button again to move to the next zone Any or all zones can be in test mode simultaneously When at the sounder status pos...

Page 32: ...not active The following table shows details of the indications in fault diagnosis mode RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps LED Indicator State before pressing ENTER LED Pulsing after pressing ENTER LED Steady after pressing ENTER LED Off after pressing ENTER Location Zone 1 Fire LED off Sounder circuit 1 short circuit Sounder circuit 1 open circuit OK...

Page 33: ... 4 In the event of a false alarm look for the device that has caused the alarm A detector will have a In the event of a false alarm look for the device that has caused the alarm A detector will have a red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer red LED lit or check to see if a call point glass is broken if so replace the glass or call an ...

Page 34: ...onger compliant with this part of BS 5839 THE NEED FOR MAINTENANCE ROUTINE MAINTENANCE TESTING DUTIES OF THE RESPONSIBLE PERSON The system user needs to appoint a single named member of the premises management to supervise all matters pertaining to the fire detection and fire alarm system The role of this person is to ensure that the system is tested and maintained in accordance with the recommend...

Page 35: ... normally be a qualified electrical contractor or fire alarm specialist Inspection servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warrant servicing on a more regular basis The maximum period between inspections must not exceed six months Recommendations of BS5839 1 for periodic service visits include Every device on the system should be test...

Page 36: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 34 ...

Page 37: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 35 ...

Page 38: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 36 ...

Page 39: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 37 ...

Page 40: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 38 ...

Page 41: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 39 ...

Page 42: ... ALARMS FAULTS ENGINEERS VISITS Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 40 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details ...

Page 43: ... ALARMS FAULTS ENGINEERS VISITS Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 41 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details ...

Page 44: ... ALARMS FAULTS ENGINEERS VISITS Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 42 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details ...

Page 45: ...arm look for the device that has caused the alarm A detector will have a In the event of a false alarm look for the device that has caused the alarm A detector will have a red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer 5 5 When fully satis...

Page 46: ......

Page 47: ......