ABOUT THIS PANEL
General Specification
Enclosure
Steel IP30. Epoxy powder coated Interpon Radon, silver grey
Temperature range
-5 deg C to +55 deg C max RH 95%
Vibration
IEC 60068-2-6 Test F
Inclination
IEC 60092-501 22.5
o
Number of conventional detection circuits
2 or 4
Detector compatibility
Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
TECHNICAL SPECIFICATION
Electrical Specification Inputs & Outputs - TPCA01-H2/H4
Cabling
Fire resistant screened cable, minimum
size 1mm
2
. Max cable length 1Km (20
Ohm). FireBurn, FP200 or equivalent
(max capacitance 1uF, max inductance 1
millihenry).
Suitable cable glands must be used.
Terminal capacity
0.5mm
2
to 2.5mm
2
solid or stranded wire.
PSU @ output
Power supply voltage control line.
For temperature compensation control.
PSU Input + -
28vdc supply input. Diode protected for
reversal and independent short circuit.
Max current 3 amps.
Max input current 3 amps. Input voltage
22vdc to 32vdc.
28v+, 0v- power output
28vdc supply output for fire alarm
accessory relays etc. Max continuous
use = 400mA.
Fused @ 500mA. Fuse = 500mA
resettable fuse.
Common fire relay
Fire relay contact. Clean C/O.
Max 3A @ 30vdc
Unfused
Common fault relay
Maintained fault relay contact. Clean
C/O. Max 3A @ 30vdc
Unfused
Outputs; FR, FLT
Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52vdc.
Current limited 680R. Max load = 40mA
Inputs; CC, PUL
Switched -ve inputs, connect to 0v to
trigger. Max input voltage = 28vdc. Non
latching, max resistance 100R.
Protected via 10K Ohm impedance, 3v6
zener diode.
SNDR 1 - 2
28vdc polarity reversal monitored
sounder outputs to fire alarm devices.
4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 0.9A is not
exceeded.
Zone 1 - 4
Fire alarm zone circuits. Conventionally
wired detection circuit. 4K7 Ohm 5%
0.25W EOL resistor.
Maximum detector load 3.5mA per zone,
Typical qty 40-50 Apollo marine optical
detectors, Note:- Max 32 detectors with
line continuity diode bases fitted
Summary of Contents for ESEN-2MAR