ASP-R Quick Start Guide
Approved Document Ref: UI-ASP-R-02 Issue 1.0
7
SETUP & PROGRAMMING
With the zone 6
fi
re LED lit, the amber, fault LEDs will show the current setting.
LED 1 OFF = fault tolerant monitoring (default). LED 1 ON = legacy, radial circuit monitoring.
Press the ENTER button, zone 6
fi
re LED will pulse to indicate ‘edit mode’.
Now use button 2 to change the setting (LED 1 ON or OFF).
When
fi
nished press the ENTER button again and the zone 6
fi
re LED will return to steady ‘view mode’.
Press button 1 for 3 seconds to exit programming mode 2-1-2-3.
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
2
1
2
3
Panel Wide Settings
There are 6 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 6 programmable
options are represented by
fi
re zone LEDs 1 - 6, Option 6 being the,
‘change repeater comms monitoring type’ setting.
Use button 1 to move to option 6
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Fire LED Programming Option
1
Change / remove keypad access code
2
Set number of repeater panels on system
3
Set output delay time (1 - 10 minutes)
4
Turn off battery monitoring
5
Set up internal PCB con
fi
guration (add extension zone
card or repeater comms PCB)
6
Change repeater comms monitoring
6. Repeater Comms Monitoring Type
To change the Comms monitoring type at the main control panel use:
3