Haes Alarm Sense Plus Quick Start Manual Download Page 10

ASP-R Quick Start Guide

Approved Document Ref: UI-ASP-R-02 Issue 1.0

8

SETUP & PROGRAMMING

2

1

2

3

Panel Wide Settings

There are 6 general, panel wide, settings available.

Enter the above code and press the ENTER button. The 6 programmable 
options are represented by 

fi

 re zone LEDs 1 - 6, Option 2 being the, ‘set 

number of repeater panels’ setting.

Use button 1 to move to option 2

RESOUND

SILENCE

RESET

ENTER

1

2

3

4

Disable

Mode

Test

Mode

Mute

Buzzer

Test

Lamps

RESOUND

SILENCE

RESET

ENTER

1

2

3

4

Disable

Mode

Test

Mode

Mute

Buzzer

Test

Lamps

Fire LED Programming Option

1

Change / remove keypad access code

2

Set number of repeater panels on system

3

Set output delay time (1 - 10 minutes)

4

Turn off battery monitoring

5

Set up internal PCB con

fi

 guration (add extension zone 

card or repeater comms PCB)

6

Change repeater comms monitoring

2. Set Number of Repeater Panels on System

With the zone 2 

fi

 re LED lit, the amber, fault LEDs will show the current quantity of repeaters set 0 - 8. (1 

LED lit = 1 repeater, 2 = 2 etc..).

Press the ENTER button, zone 2 

fi

 re LED will pulse to indicate ‘edit mode’.

Now use buttons 1 & 3 to increase or decrease the quantity. Button 1 increases, button 3 decreases.

When 

fi

 nished press the ENTER button again and the zone 2 

fi

 re LED will return to steady ‘view mode’.

Press button 1 for 3 seconds to exit programming mode 2-1-2-3.

To set the number of repeater panels at the main control panel use:

4

Summary of Contents for Alarm Sense Plus

Page 1: ...Quick Start Guide 12 ZONE FULLY FUNCTIONAL PASSIVE REPEATER PANEL Approved Document UI ASP R 02 Issue 1 0 REPEATER PANEL Full manual available from www haes sysems com...

Page 2: ...res periodic checks as specified in BS 5839 Part 1 It is the responsibility of the This fire alarm system requires periodic checks as specified in BS 5839 Part 1 It is the responsibility of the system...

Page 3: ...e INSTALLATION 2 SAFETY 2 ESD PRECAUTIONS 3 GENERAL 3 MOUNTING THE CABINET 3 CABLING 4 SETUP PROGRAMMING 5 INSTALL COMMS PCB 5 REPEATER PANEL ADDRESSING 5 SETUP NEW INTERNAL PCB CONFIGURATION 6 CHANGE...

Page 4: ...o the provisions of the Act you are therefore requested to take such steps as are necessary to According to the provisions of the Act you are therefore requested to take such steps as are necessary to...

Page 5: ...ow voltage and must be segregated away from mains voltage Any junction boxes used should be clearly labelled FIRE ALARM Any ancillary devices e g door retaining magnets must be powered from a separate...

Page 6: ...ng cabling cannot be configured in a loop as shown it is possible to re programme the panel back to legacy radial circuit comms monitoring This then allows any topology of comms cabling to be utilised...

Page 7: ...ms PCB into the socket instead A socket is provided on the top of the Comms PCB to re connect the display board ribbon cable PSU 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP SNDR1 SNDR2...

Page 8: ...Change repeater comms monitoring 5 Setup Internal PCB Configuration With the zone 5 fire LED lit the amber fault LEDs will show the current configuration setting Each of the 3 possible additional inte...

Page 9: ...est Mode Mute Buzzer Test Lamps 2 1 2 3 Panel Wide Settings There are 6 general panel wide settings available Enter the above code and press the ENTER button The 6 programmable options are represented...

Page 10: ...2 Set number of repeater panels on system 3 Set output delay time 1 10 minutes 4 Turn off battery monitoring 5 Set up internal PCB configuration add extension zone card or repeater comms PCB 6 Change...

Page 11: ...www haes systems com...

Reviews: