System Description 
H3C S3600 Series Ethernet Switches 

Chapter 2  Hardware Description  

 

2-2 

Table 2-1 

LEDs on the front panel of the S3600-28P-SI 

LED 

Mark 

Color 

Indicates 

Power 
LED 

PWR 

Solid green 

The system passes the 
Power-On Self-Test 
(POST) and is operating 
normally. 

Flashing green (1 Hz) 

The system POST  is 
running. 

Solid red  

The POST of the system 
fails or a serious fault is 
detected. 

Flashing yellow (1 Hz) 

Some ports fail to pass 
the POST and some 
functions are disabled. 

OFF 

The power is 
disconnected. 

Mode 
LED 

Mode 

Speed 

Solid green 

The port LEDs are 
showing the speed (for 
the 10/100 Mbps ports), 
port state (for the 1000 
SFP ports or fabric 
ports). 

OFF 

–– 

Duplex 
and data 
transmissi
on 

Solid yellow 

The port LEDs are 
showing the duplex 
mode. 

OFF 

–– 

PoE mode 

–– 

–– 

OFF 

–– 

Summary of Contents for S3600-28FEI

Page 1: ...2 2 3 Attributes of the FE Ports 2 10 2 2 4 Attributes of 1000 Mbps SFP Ports 2 11 2 2 5 Attributes of the GE Ports 2 11 2 2 6 Power Subsystem 2 12 2 2 7 Cooling Subsystem 2 12 2 3 S3600 52P SI Ether...

Page 2: ...e FE Ports 2 37 2 7 4 Attributes of 1000 Mbps SFP Ports 2 37 2 7 5 Power System 2 38 2 7 6 PoE 2 38 2 7 7 Cooling System 2 38 2 8 S3600 52P EI Ethernet Switch 2 38 2 8 1 Appearance 2 38 2 8 2 Console...

Page 3: ...uting Features 3 5 3 3 1 Static Routing and Default Routing 3 5 3 3 2 RIP 3 6 3 3 3 OSPF 3 6 3 4 Multicast Features 3 6 3 4 1 IGMP Snooping 3 6 3 4 2 IGMP 3 7 3 4 3 PIM DM 3 7 3 4 4 PIM SM 3 7 3 4 5 M...

Page 4: ...3 12 1 QinQ 3 18 3 12 2 QinQ BPDU Tunnel 3 19 3 13 GARP GVRP 3 19 3 13 1 GARP 3 19 3 13 2 GVRP 3 20 Chapter 4 System Maintenance and Management 4 1 4 1 Simple and Flexible System Maintenance 4 1 4 1...

Page 5: ...System Description H3C S3600 Series Ethernet Switches Table of Contents v Chapter 6 Guide to Purchase 6 1 6 1 Purchasing the Switch 6 1 6 2 Purchasing the SFP Interface Module 6 2...

Page 6: ...of service ports Number of 100 Mbps ports Number of 1000 Mbps uplink ports Console port H3C S3600 28P SI AC input 28 24 10 100 Mbps electrical 4 SFP 1 H3C S3600 28TP SI AC input 28 24 10 100 Mbps ele...

Page 7: ...t Resilient Framework IRF feature where the IRF supported switches that are of the same type called units are connected to form a device union or a fabric Trough a fabric you can 1 manage multiple dev...

Page 8: ...ports S3600 28P EI 24 x 10 100 Mbps electrical ports 4 x 1000 Mbps SFP ports S3600 28F EI 24 x 100 Mbps SFP ports 2 x 1000 Mbps ports 2 x 10 100 1000 Mbps electrical ports S3600 28P PWR EI S3600 28P P...

Page 9: ...5W PoE 300W 820W DC Dissipated power 80W PoE 740W Operating temperature 0 to 45 o C Operating humidity non condensin g 10 to 90 1 3 Service Features The software of the S3600 series is designed based...

Page 10: ...uting Information Protocol 1 2 RIP 1 2 Open Shortest Path First OSPF 3 Equal Cost Multi Paths ECMPs Multicast Support up to 255 multicast groups SI Series switches only support layer 2 multicast IGMP...

Page 11: ...mote port mirroring MAC address table Address self learning IEEE 802 1D standard Up to 16K MAC addresses Up to 1k static MAC addresses Flow control IEEE 802 3x full duplex Back pressure based flow con...

Page 12: ...Traffic rules every 8 100M ports share 160 rules each 1000M port supports 80 rules Limitation on packet receiving sending rate on ports with the granularity of 64 kbps Packet redirection Committed Acc...

Page 13: ...ing limits and binding MAC addresses with ports SSH Denial of Service DoS attack prevention Port isolation MAC address black hole Password recovery BOOTROM access control RADIUS authentication of mana...

Page 14: ...source discovery protocol MSDP Supported DNS Client Supported Huawei group management protocol HGMP Supported QinQ Supported GARP VLAN registration protocol GVRP Supported Fault detection and alarm Po...

Page 15: ...anel one power input Figure 2 2 illustrates the S3600 28P SI Figure 2 1 The S3600 28P SI 2 1 2 Console Port and LEDs I Console port The S3600 28P SI provides one EIA TIA 232 compliant console port for...

Page 16: ...green 1 Hz The system POST is running Solid red The POST of the system fails or a serious fault is detected Flashing yellow 1 Hz Some ports fail to pass the POST and some functions are disabled OFF T...

Page 17: ...d on it data is being received transmitted Solid yellow The port is operating in half duplex mode and on it data is being received transmitted Flashing yellow 3 Hz The port fails POST OFF No data is b...

Page 18: ...ort is connected and the device is in a non loop chain fabric Flashing Data is being received or and sent on the port Flashing green at 3Hz Fabricing fault occurs Flashing yellow at 3 Hz The port fail...

Page 19: ...duplex MDI MDI X auto sensing Standard IEEE 802 3u Transmission segment over the selected medium 100 m 328 08 ft over the category 5 unshielded twisted pair UTP cable 2 1 4 1000 Mbps SFP Port Attribut...

Page 20: ...lable 1000 Mbps SFP modules are subject to changes For information on the latest module options contact your sales agent 2 1 5 Power Subsystem Following are the input voltage specifications of the S36...

Page 21: ...Ds on the front panel of S3600 28TP SI LED Mark and Position Color Indicates Power LED PWR Solid green The system passes the Power On Self Test POST and is operating normally Flashing green 1 Hz The s...

Page 22: ...and for a standalone unit 1 10 100B ase TX port mode LED Speed Green ON A 100 Mbps link is present Flas h Data is being received transmitted on the port Yellow ON A 10 Mbps link is present Flas h Data...

Page 23: ...nt Flas h Data is being received transmitted on the port Flashing yellow 3 Hz The port fails POST OFF No link is present Duplex Green ON The port is operating in full duplex mode Flas h Data is being...

Page 24: ...resent Duplex Green ON The port is operating in full duplex mode Flas h Data is being received transmitted on the port Yellow ON The port is operating in half duplex mode Flas h Data is being received...

Page 25: ...ype of ports is optional SFP modules allow for great flexibility in networking because they are hot swappable and user configurable Table 2 6 lists the available SFP modules Note The available 1000 Mb...

Page 26: ...e AC input voltage specifications of the S3600 28TP SI Rated voltage 100 to 240 VAC 50 to 60 Hz Max tolerance 90 to 264 VAC 50 to 60 Hz 2 2 7 Cooling Subsystem The S3600 28TP SI is cooled by one fan 2...

Page 27: ...te 10 Mbps half duplex full duplex 100 Mbps half duplex full duplex MDI MDI X auto sensing Standard IEEE 802 3u Transmission segment over the selected medium 100 m 328 08 ft over the category 5 unshie...

Page 28: ...Switch 2 4 1 Appearance The S3600 28P EI has 24 x 10Base T 100Base TX Ethernet ports four 1000 Mbps SFP ports and one console port on its front panel and on its rear panel one AC input and one DC inp...

Page 29: ...a fault is detected Flashing yellow 1 Hz Some ports fail to pass the POST and are disabled OFF The power is disconnected DC input LED RPS Solid green Both the internal AC power supply and the DC inpu...

Page 30: ...ating in half duplex mode and on it data is being received transmitted Flashing yellow 3 Hz The port fails POST OFF No data is being received transmitted on the port PoE mode OFF 1000Bas e SFP port mo...

Page 31: ...he port is connected and the device is in a non loop chain fabric Flashin g Data is being received or and sent on the port Flashing green 3Hz Fabricing fault occurs Flashing yellow 3 Hz The port fails...

Page 32: ...f the FE Ports Table 2 9 Attributes of the FE ports on the S3600 28P EI Attribute Description Connector RJ 45 Number of ports 24 Rate 10 Mbps half duplex full duplex 100 Mbps half duplex full duplex M...

Page 33: ...of the S3600 28P EI Rated voltage 100 to 240 VAC 50 to 60 Hz Max tolerance 90 to 264 VAC 50 to 60 Hz II DC input power DC input voltage range 36 VDC to 72 VDC 2 4 6 Cooling Subsystem The S3600 28P EI...

Page 34: ...system is going through the POST or is downloading software Solid red The POST of the system fails or a fault is detected Flashing yellow 1 Hz Some ports fail to pass the POST and are disabled OFF Th...

Page 35: ...Data is being received transmitted on the port Yellow ON The port is operating in half duplex mode Flash Data is being received transmitted on the port Flashing yellow 3 Hz The port fails POST OFF No...

Page 36: ...ort is connected and the device is in an IRF loop chain fabric Flash Data is being received transmitted on the port Flashing green 3 Hz Fabricing fault occurs Flashing yellow 3 Hz The port fails POST...

Page 37: ...10 100 Mbps link is present Flash Data is being received transmitted on the port Flashing yellow 3 Hz The port fails POST OFF The port is not connected Duplex Green ON The port is operating in full d...

Page 38: ...z Fabricing fault occurs Flashing yellow 3 Hz The port fails POST OFF The port is not connected Duplex Green ON The port is operating in full duplex mode Flash Data is being received transmitted on th...

Page 39: ...of 1000 Mbps SFP Ports The S3600 28F EI has two 1000 Mbps SFP ports which are numbered as 25 and 26 optical or electrical the number or type of ports is optional SFP modules allow for great flexibilit...

Page 40: ...ry 5 unshielded twisted pair UTP cable 2 5 6 Power Subsystem I AC input power Rated voltage 100 to 240 VAC 50 to 60 Hz Max tolerance 90 to 264 VAC 50 to 60 Hz II DC input power Rated voltage 48 to 60...

Page 41: ...the front panel of S3600 28P PWR EI LED Mark and Position Color Indicates Power LED PWR Solid green The system passes the Power On Self Test POST and is operating normally Flashing green 1 Hz The syst...

Page 42: ...Flashing green 1 Hz PoE information on 10 100M port 7 segment display Unit POST running PWR flashes green The POST test ID in the range 1 to 9 POST failed PWR flashes yellow POST test ID of the faile...

Page 43: ...plex Green ON The port is operating in full duplex mode Flash Data is being received transmitted on the port Yellow ON The port is operating in half duplex mode Flash Data is being received transmitte...

Page 44: ...oE Flashing green 3 Hz The port fails POST OFF 1000Base SFP fabric port status LED Speed Green ON The device is in IRF mode Flash Data is being received transmitted on the port Yellow ON The device is...

Page 45: ...over the selected medium 100 m 328 08 ft over the category 5 unshielded twisted pair UTP cable 2 6 4 Attributes of 1000 Mbps SFP Ports The S3600 28P PWR EI has four 1000 Mbps SFP ports which are numbe...

Page 46: ...0 28P PWR EI supports IEEE802 3af standard and is also compatible with PDs that is not conformed to this standard The S3600 28P PWR EI provides power through 24 fixed Ethernet electrical ports and thu...

Page 47: ...the front panel of S3600 28P PWR SI LED Mark and Position Color Indicates Power LED PWR Solid green The system passes the Power On Self Test POST and is operating normally Flashing green 1 Hz The syst...

Page 48: ...Flashing green 1 Hz PoE information on 10 100M port 7 segment display Unit POST running PWR flashes green The POST test ID in the range 1 to 9 POST failed PWR flashes yellow POST test ID of the faile...

Page 49: ...plex Green ON The port is operating in full duplex mode Flash Data is being received transmitted on the port Yellow ON The port is operating in half duplex mode Flash Data is being received transmitte...

Page 50: ...oE Flashing green 3 Hz The port fails POST OFF 1000Base SFP fabric port status LED Speed Green ON The device is in IRF mode Flash Data is being received transmitted on the port Yellow ON The device is...

Page 51: ...over the selected medium 100 m 328 08 ft over the category 5 unshielded twisted pair UTP cable 2 7 4 Attributes of 1000 Mbps SFP Ports The S3600 28P PWR SI has four 1000 Mbps SFP ports which are numbe...

Page 52: ...3600 28P PWR SI supports IEEE802 3af standard and is also compatible with PDs that is not conformed to this standard The S3600 28P PWR SI provides power through 24 fixed Ethernet electrical ports and...

Page 53: ...see Table 2 1 II LEDs You can learn the operating state of the S3600 52P EI by reading the LEDs on its front panel see Table 2 11 2 8 3 Attributes of the FE Ports Table 2 17 Attributes of the FE ports...

Page 54: ...able 1000 Mbps SFP modules are subject to changes For information on the latest module options contact your sales agent 2 8 5 Power Subsystem I AC input power Following are the AC input voltage specif...

Page 55: ...operating state of the S3600 52P PWR EI by reading the LEDs on its front panel see the following table 2 9 3 Attributes of the FE Ports Table 2 18 Attributes of the FE ports on the S3600 52P PWR EI A...

Page 56: ...available 1000 Mbps SFP modules are subject to changes For information on the latest module options contact your sales agent 2 9 5 Power Subsystem I AC input power Rated voltage 100 to 240 VAC 50 to...

Page 57: ...system The S3600 52P PWR EI is cooled by five fans 2 10 S3600 52P PWR SI Ethernet Switch 2 10 1 Appearance The S3600 52P PWR SI has 48 x 10Base T 100Base TX Ethernet ports four 1000 Mbps SFP ports and...

Page 58: ...over the selected medium 100 m 328 08 ft over the category 5 unshielded twisted pair UTP cable 2 10 4 Attributes of 1000 Mbps SFP Ports The S3600 52P PWR SI has four 1000 Mbps SFP ports which are num...

Page 59: ...reless access points AP Security Bluetooth AP through the twisted pair cable As the power sourcing equipment PSE S3600 52P PWR SI supports IEEE802 3af standard and is also compatible with PDs that is...

Page 60: ...support manual link aggregation and dynamic link aggregation through the link aggregation control protocol LACP IEEE802 3ad based LACP dynamically aggregates and de aggregates links A LACP enabled po...

Page 61: ...ning tree protocol RSTP prunes a loop L2 switching network into a loop free tree all data on the L2 switching network must travel along the spanning tree thereby avoiding network broadcast storms caus...

Page 62: ...lay before the port can transit to the forwarding state RSTP can converge fast But it still has the following drawback like STP There is only one spanning tree in the LAN All the bridges in the LAN sh...

Page 63: ...if not the switch sends the packet to the upper layer modules For the relay of BOOTP DHCP broadcast packets the system sends the response to a request by unicast rather than broadcast unless required...

Page 64: ...A static route is a route that is manually configured by a network administrator For a routing switch on a simple network static routes are adequate for the switch to operate normally The proper confi...

Page 65: ...SPF router collects and broadcasts its link state information throughout the AS with the flooding algorithm to synchronize the link state databases LSDBs of other OSPF routers With its LSDB the router...

Page 66: ...s The protocol independent multicast dense mode PIM DM is applied to a multicast environment where multicast group members are dense In PIM DM a router assumes that all other routers agree to forward...

Page 67: ...cted through fabric ports for centralized management Support the feature includes DDM Distributed Device Management Support Dynamic link aggregation through Link Aggregation Control Protocol LACP on o...

Page 68: ...icing polices the traffic matching a traffic classification rule on the port where the packets are received so that the traffic can effectively use the assigned network resources such as bandwidth Tra...

Page 69: ...le to the monitor port for network detection and trouble shooting 3 6 7 Remote Port Mirroring The remote port mirroring feature introduces a new concept mirroring group to port mirroring Multiple mirr...

Page 70: ...occurs and the high priority queues are occupied for a long time however the packets in the lower priority queues are starved before obtaining services II WRR In WRR there are four or eight egress que...

Page 71: ...SP WFQ SP WRR 3 6 9 Traffic Shaping Traffic shaping is to control traffic output rate as such that packets can be output at an even rate Normally traffic shaping is applied on a device to adapt its o...

Page 72: ...tion In the diagram the PC is a user on a LAN attached to the switch The Web Cache is a server that stores the frequently visited internet websites of the WAN users Once web cache redirection is enabl...

Page 73: ...icating Ethernet frames and packets from the upper layers the S3600 series support ACL with which information is filtered at layers 2 through 4 such as based on port by source destination MAC address...

Page 74: ...uthenticates and controls the connected customer premises equipment CPE at the port level If the CPE connected to a port passes authentication it is allowed to access the LAN resources Otherwise it is...

Page 75: ...tion enabled the switch filters out all the traffic of a connected device once it detects that the device is unauthorized 3 9 10 MAC Address Black Hole On a S3600 series switch you can enable the blac...

Page 76: ...enhanced security protocol based on TACACS RFC 1492 Similar to the RADIUS protocol HWTACACS adopts the server client mode to implement authentication authorization and accounting AAA of different acce...

Page 77: ...t 3 11 1 HGMP HGMP implements centralized management of devices that is HGMP uses one device to manage multiple devices Currently HGMP includes two versions HGMPv1 and HGMPv2 The S3600 series support...

Page 78: ...k to distribute transmit and register a kind of information such as VLAN information and multicast group address information GARP members which can be terminal workstations or routing switches exchang...

Page 79: ...receive VLAN registration information from other routing switches and update the local VLAN registration information including the information about the current VLAN members and the ports though whic...

Page 80: ...agement 4 1 2 System Maintenance The S3600 series provide diverse management and maintenance functions LEDs are available on the switch and optional modules indicating the board running status Telnet...

Page 81: ...k equipment operation and maintenance The system supports automatic topology discovery reflecting the real time changes in network topology and equipment status 4 2 2 Configuration Management With the...

Page 82: ...based network management allows you to manage and maintain a switch through Web It is implemented as follows The switch provides a built in Web server and runs a Web based network management program o...

Page 83: ...Convergence layer Community building access layer Corridor access layer S3026 S3026 S2000 series Local service center ICP ICP GSR L3 S3600 series ICP ICP GSR L3 S3600 series Data center MAN backbone C...

Page 84: ...00M S3600 series FE 100M S2000 S3026 series Rotuer PC PC PC PC Internet Internet GE 1000M FE 100M S3900 FE 100M GE 1000M FE 100M S3900 FE 100M Internet Internet Internet Enterprise network server Inte...

Page 85: ...serv er PC L2 L3 L3 L2 serv er serv er PC PC PC L2 L3 L3 L2 serv er PC PC PC L2 L3 L3 L2 serv er serv er PC Department serv er serv er serv er PC PC PC L2 L3 L3 S3600 series S2000 S3026 series L2 S36...

Page 86: ...System Description H3C S3600 Series Ethernet Switches Chapter 5 Networking Applications 5 4 series series 3600 3600 3000 series series Figure 5 4 IRF Network diagram...

Page 87: ...both directions Desired scalability Service reliability Transmission segment II Power system Make sure you want a DC powered or an AC powered switch Table 6 1 Switch purchase list Switch model Quanti...

Page 88: ...e mode fiber 80 km 49 71 mi 0 to 24 Option al 1000Base SX SFP 850 nm LC 62 5 125 m multi mode fiber 550 m 1804 46 ft 0 to 4 Option al 62 5 125 m multi mode fiber 275 m 902 23 ft 0 to 4 Option al 1000B...

Page 89: ...mi 0 to 4 Option al 1550nm Single mode fiber 10 km 6 21 mi 0 to 4 Option al 1570nm Single mode fiber 10 km 6 21 mi 0 to 4 Option al 1590nm Single mode fiber 10 km 6 21 mi 0 to 4 Option al 1610nm Sing...

Reviews: