www.h2flow.net
2.
technical data
This manual will assist you in installing, using and maintaining your flow meter. It is your responsibility to make sure that all
operators have access to adequate instructions about safe operating and maintenance procedures.
Main Power
120-240VAC 50Hz - 60Hz / 24-36VDC
Power Consumption
<15W (and set with sensor supporting power consumption)
Display and Push Buttons
English and Chinese display can display the instantaneous flow, total flow and percentage of flow as well as
alarm display, four soft-touch buttons, which are used for data set.
Accumulator
Forward total quantity, reverse total quantity
Output Signal
Analog output
Bi-directional, isolation 0-10mA / 4-20mA
Frequency
output
Forward and reverse flow output with frequency range set between 1 - 5000Hz. The external
voltage must be lower than 35V and the max output current is 50mA when the transistor is
turned on.
Alarm output
Two outputs from the collectors of photoelectric isolate transistors are for alarm signals.
The external voltage must be lower than 35V and the max output current is 250mA when
the transistor is turned on. Alarm status: Activates when the measured pipes are empty, the
excitation circuits are broken, or the volume of flow rate exceeds the value designed limits.
Pulse output
For pulse output in forward and reverse flow measurement, upper frequency of pulse output
can be up to 5000 CP/S relevant value of pulse is from 0.0001 to 1.0 M3/P. The width of
pulse can be set to 20ms or squired wave form automatically. The collector of transistor with
photoelectric is open circuited. The external voltage must be lower than 35V and maximum
output current is 250mA when the transistor is turned on.
Accuracy
±0.5% of the value displayed
Damping Time Constant
Continuous variable from 0-100 s (90%) can be selected by group
Communication
RS232, RS485 or HART Communication are optional, with lightning resistance
Power Failure
An anti-failure clock is designed in the flow meter which can save the power failure records for 16 times (10
years)
Protection Grade
NEMA 4 / IP65
Nominal Diameter
0.5” - 120” (DN15 - DN3000)
Nominal Pressure
0.6 - 4.0MPa
Output Signal
Analog output, Frequency output, Alarm output, Pulse output
Liner Material
Neoprene, Urethane Rubber, Polysilicone Rubber, PTFE, F46, PFA
Electrode Type
General Type, scraper type, replaceable type
Electrode Material
SUS316, Hastelloy B, Hastelloy C, Titanium, Tantalum, Platinum-iridium alloy, Stainless Steel covered with
Tungsten Carbide
Medium Temperature
Integrated Type -4°F - +158°F (-20°C - +70°C)
Remote Type
Neoprene & Polyurethane
Liner
-4°F - +140°F (-20°C - +60°C)
PTFE Liner / PFA Liner / F46
Liner
-40°F - +356°F (-40°C - +180°C)
Ambient Temperature
-13°F - +140°F (-25°C - +60°C)
Ambient Humidity
5 - 100% RH (relative humidity)
Medium Electrical Conductivity
≥20us/cm
Measuring Range
1500:1, flow rate <15m/s
Structure Type
Integral Type, Remote Type, Submersible Type, ex-proof Type
Connection Type
Flange Type / Clamp Type (optional on certain models)
Protection Grade
NEMA4 (IP65), NEMA 6 (IP67), NEMA 6P (IP68)
Product Standard
JB/T 9248-1999 Electromagnetic Flowmeter