GateKeeper Interface 

 

Relay Terminals 

These terminals are for signalling the access control device. For loads over 2A, we do not 
recommend connecting directly. Use a secondary relay as a buffer instead.  

NO

 Relay normally open contact

 

COM

 Relay common terminal 

NC

 Relay normally closed contact 

As access control devices are often inductive, switching off the current can cause a voltage spike 
on the wires to the access control, damaging the reader. A snubber should be fitted near any 
switch or relay contacts, for DC circuits a silicon rectifier diode such as IN4001 (supplied) is well 
suited.  Please note that the wire diode in the wrong direction (polarity) will cause a short circuit 
and damage the power supply.  

 

The diode

 MUST 

be

 

wired correctly according to the diagram,

 

otherwise it may cause 

damage to the GateKeeper board or the device power supply. 

 

 

EPIC Sanctuary 
78-106 Manchester St 
Christchurch 8011 
New Zealand 

PO Box 13352 
Armagh Mail Centre 
Christchurch 8011 
New Zealand 

www.gymmastersoftware.com 

NZ 03 974 9169 
AU 03 9111 0323 
US 415 678 1270

 

Page 5 

 

Summary of Contents for GateKeeper h4.2

Page 1: ...ructions v4 GateKeeper h4 2 Technical Support support gymmastersoftware com USA 415 678 1270 Australia 03 9111 0323 New Zealand 03 974 9169 Copyright 2018 Treshna Enterprises All rights reserved 15 Oc...

Page 2: ...afe with Emergency Exit 12 Combinations of Relay Units 13 Bi Directional 13 Normally Open Contacts 13 Normally Closed Contacts 13 GateKeeper Status 14 What Do the Lights Mean 14 Troubleshooting 15 Tes...

Page 3: ...reader with Standard USB type A data cable Wall mounted card reader with diodes supplied with stub wiring for bench testing You will also need the following items Internet Connection Router or Networ...

Page 4: ...onents Desktop PCs and other computer devices are high power drain and should not be connected to the UPS The UPS will assist in maintaining normal member access and system operation in the event of a...

Page 5: ...maintain constant power for the GateKeeper door readers Internet router and all network components Door lock MUST have its own separate power supply Do NOT use the GateKeeper or the GateKeeper power...

Page 6: ...ging the reader A snubber should be fitted near any switch or relay contacts for DC circuits a silicon rectifier diode such as IN4001 supplied is well suited Please note that the wire diode in the wro...

Page 7: ...s between the reader terminals and readers are Terminal Wire Colour A Green B White VCC Red GND Black The RFID reader must be mounted in a location where the electrical noise is quiet If there is a lo...

Page 8: ...ner The left LED shows whether the cable is correctly inserted The right LED shows network activity When powered and connected to the router you would normally expect to see a solid left LED and a fli...

Page 9: ...the power goes off Fail Safe locks will leave the door UNLOCKED when the power goes off Check with your local fire regulations as to which you should use Door lock door lock power supply and any Push...

Page 10: ...e EPIC Sanctuary 78 106 Manchester St Christchurch 8011 New Zealand PO Box 13352 Armagh Mail Centre Christchurch 8011 New Zealand www gymmastersoftware com NZ 03 974 9169 AU 03 9111 0323 US 415 678 12...

Page 11: ...rgency Exit EPIC Sanctuary 78 106 Manchester St Christchurch 8011 New Zealand PO Box 13352 Armagh Mail Centre Christchurch 8011 New Zealand www gymmastersoftware com NZ 03 974 9169 AU 03 9111 0323 US...

Page 12: ...EPIC Sanctuary 78 106 Manchester St Christchurch 8011 New Zealand PO Box 13352 Armagh Mail Centre Christchurch 8011 New Zealand www gymmastersoftware com NZ 03 974 9169 AU 03 9111 0323 US 415 678 127...

Page 13: ...gency Exit EPIC Sanctuary 78 106 Manchester St Christchurch 8011 New Zealand PO Box 13352 Armagh Mail Centre Christchurch 8011 New Zealand www gymmastersoftware com NZ 03 974 9169 AU 03 9111 0323 US 4...

Page 14: ...sharing wiring pattern above The wiring pattern you should use depends on which relay contacts are being used Normally Open Contacts In arrangements where the normally open NO contacts are used wire...

Page 15: ...e on 3 Power On Off Power to the GateKeeper unit 4 Error Red Off There is an error 5 Reader 1 Reader 2 On Off Reader s are connected 6 Database On Off Connection to the cloud server 7 Internet On Off...

Page 16: ...lip straighten it and then bend it as depicted below Connect the paperclip into the two holes where the two wires connect to the magnet lock You should be able to see the door lock activate or deactiv...

Page 17: ...ecome unengaged unlocked after the paperclip is connected If that does not happen it means that the wiring has not been done correctly on the lock mechanism Please check power supply for the lock and...

Reviews: