adjust the maximum current value. Because current through the two supplies 

must be equal when they are being used in series, the lowest CURRENT 

control setting will set the maximum 

output current. 

C. Adjust the output voltage to the desired level by using the CH1 

VOLTAGE controls. 

D. Turn off the power supply and the equipment to be powered during 

hook-up. 

E. If “single supply” operation is desired, this allows the power supply to be 

used as twice the voltage and rating current simply by using the negative 

(black) terminal of the CH2 supply and the positive (red) terminal of the 

CH1 supply, the configuration as shown in Fig. 5-3. 

 

 

 

 

Power  

Supply

 

 

 

Fig. 5-3 Single Supply

 

F. If the chassis or common of the equipment being powered is separated 

from both the positive and negative polarity power inputs, the output of 

the CH2 (negative) supply tracking the output of the CH1 (positive) 

supply, the configuration as shown in Fig. 5-4. 

 

 

 

Power 

Supply

 

 

 

Fig. 5-4 Positive and Negative Supply

 

MULTI-OUTPUT POWER SUPPLY 

                                          USER MANUAL 

 

 

17

(3) Parallel Tracking Operation 

In the parallel tracking mode of operation, both supplies are strapped 

together (in parallel). This allows for a rating voltage supply with a double 

rating current capability. Only the CH1 output terminals are used for parallel 

tracking operation. In the parallel tracking mode, the CH2 supply output 

voltage and current track the CH1 supply output voltage and current. 

A. Set the power supplies to the Tracking Parallel mode by engaging both 

Tracking switches. 

B. Output voltage will now be read from the CH1 VOLTAGE display. 

Output current is exactly double the value read from the CH1 CURRENT 

display (because each supply is providing the same amount of current). 

C.Because both voltage and current of the CH2 supply track the CH1 supply, 

the maximum current and voltage are set by using the CH1 controls. Using 

the CH1 supply output jacks, follow the instructions for “Setting Current 

Limit” (5-2 Section). Remember that the actual current output at the CH1 

supply output jack is double the reading on the CH2 indicator meter.     

D.Adjust the output voltage to the desired level by using the CH1 

VOLTAGE controls. 

E.

 

Turn off the power supply and the equipment to be powered during 

hook-up.  

F.

 

Connect the positive polarity of the device being powered to the red (+) 

terminal of the CH1 power supply. 

G. Connect the negative polarity of the device being powered to the black (-) 

terminal of the CH1 power supply. The configuration is shown as Fig. 5-5: 

 

 

 

 

Power 

Supply 

 

Fig. 5-5 Parallel Tracking Operation 

Summary of Contents for GPS-2303

Page 1: ...A 0 2 3mA 0 2 3mA 3mArms 0 5 10mV of the CH1 300mV 0 01 3mV 2mVrms 5Hz 1MHz 5mV 15mV 2mVrms 5Hz 1MHz GPS 4303 1A GPS 3303 3A GPS 4251 2 5A 5mV 10mV 2mVrms 5Hz 1MHz 1A 3 digits 0 5 LED display GPS 4303...

Page 2: ......

Page 3: ...rective 73 23 EEC amended by 93 68 EEC EN 61010 1 2001 IEC 61010 1 2001 MULTI OUTPUT POWER SUPPLY USER MANUAL ii Declaration of Conformity We GOOD WILL INSTRUMENT CO LTD No 7 1 Jhongsing Rd Tucheng Ci...

Page 4: ...c 5 4 Operation Mode 11 11 11 12 13 6 MAINTENANCE 6 1 Fuse Replacement 6 2 Line Voltage Conversion 6 3 Adjustments 6 4 Cleaning 19 19 19 20 24 iv SAFETY TERMS AND SYMBOLS Please take a moment to revie...

Page 5: ...package GPS 4302 GPS 4303 and GPS 4251 consist of four identical independent adjustable DC power supplies while two for GPS 2303 and three for GPS 3303 A front panel switch selects one of three opera...

Page 6: ...n 0 01 3mV Load regulation 0 01 3mV rating current 3A Load regulation 0 02 5mV rating current 3A MULTI OUTPUT POWER SUPPLY USER MANUAL 3 3 Recovery time 100 s 50 load change minimum load 0 5A 4 Ripple...

Page 7: ...m function description Single phase input power is applied to transformer through the input circuit Auxiliary rectifier D1021 1024 provides a bias voltage filtered by capacitor C103 C104 for the prere...

Page 8: ...MULTI OUTPUT POWER SUPPLY USER MANUAL 6 Figure 3 1 Block Diagram MULTI OUTPUT POWER SUPPLY USER MANUAL 7 4 PANEL CONTROLS AND INDICATORS Fig 4 1 Front Panel...

Page 9: ...king operation 7 Current Control Adjust the output current of the CH1 supply and as the adjustment control for the maximum output current of the CH2 supply when either parallel or series tracking oper...

Page 10: ...GPS 2303 3303 28 Output switches ON OFF the output MULTI OUTPUT POWER SUPPLY USER MANUAL 11 29 30 TRACKING Mode Switch Two push button switches that select Independent mode series tracking mode or par...

Page 11: ...oltage Constant Current Characteristics The working characteristic of these series Power Supplies is called a constant voltage constant current automatic crossover type This permits continuous transit...

Page 12: ...CH2 supply voltage is automatically set to the same as the CH1 supply by using the CH1 VOLTAGE controls A Set the power supplies to the Tracking series mode by engaging the left Tracking switch and re...

Page 13: ...allows for a rating voltage supply with a double rating current capability Only the CH1 output terminals are used for parallel tracking operation In the parallel tracking mode the CH2 supply output vo...

Page 14: ...he supply it will cause voltage and current to drop and interfere proper operation of the CH4 supply Under this situation the load on the supply must be decreased so that no more than 1 amp of current...

Page 15: ...been made in a circuit affecting adjustment accuracy or if you have a reason to believe the unit is out of adjustment The recommended calibration device is a multimeter with an accuracy of 0 1 DCV or...

Page 16: ...circuit board VOLTAGE CURRENT CONTROL potentiometer board until the voltage read from the multimeter is the same as it was MULTI OUTPUT POWER SUPPLY USER MANUAL 23 across the CH1 output terminals Retu...

Page 17: ...ff by adjusting the trimmer potentiometer VR803 from the CH4 voltage indicator circuit board located on the meter or A D converter board for a reading of rate voltage on the CH4 C Turn VR601 on the ma...

Page 18: ...MULTI OUTPUT POWER SUPPLY USER MANUAL 26 Fig 6 1 Adjustment Location...

Reviews: