D1092 

- SIL 3 Relay Output Module  

G.M. International ISM0091-11 

 

Model:  

D1092 

1 channel 

2 channels 

Ordering information 

 

D1092 

1  2  3  4 

9  10  11  12 

16 

15 

14 

13 

5  6  7  8 

CH. 1 
CH. 2 

Front Panel and Features 



SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 14 / 20 years  (

10% / >10 % of total SIF) with NE Load. 



SIL 3 according to IEC 61508:2010 Ed.2 for Tproof = 9 / 20 years (

10% / >10 % of total SIF) with ND Load. 



PFDavg (1 year) 7.02 E-06, SFF 99.03 % with NE Load. 



PFDavg (1 year) 1.03 E-05, SFF 97.61 % with ND Load. 



SIL 3 Systematic capability. 



Installation in Zone 2, Division 2. 



2 fully independent channels. 



1 SPST contact for NE load and 1 SPST contact for ND load for each channel. 



5 A inrush current at 30 Vdc / 250 Vac. 



Input/Output isolation. 



EMC Compatibility to EN61000-6-2,  

EN61000-6-4, EN61326-1. 



ATEX, IECEx, FM & FM-C, EAC-EX, UKR TR n. 898, TÜV Certifications. 



Type Approval Certificate DNV for maritime applications. 



TUV Functional Safety Certification. 



High Reliability, SMD components. 



High Density, two channels per unit. 



Simplified installation using standard DIN Rail and plug-in terminal blocks. 

+ Input Ch 1 connects to terminal 13 

Terminal block connections 

SAFE AREA 

SAFE AREA 

+ Input Ch 2 connects to terminal 15 

- Input Ch 1 connects to terminal 14 

- Input Ch 2 connects to terminal 16 

+ Input Ch 1 

- Input Ch 1 

+ Input Ch 2 

- Input Ch 2 

9

 

10

 

11

 

12

 

13

 

14

 

15

 

16

 

Output Ch 1-A for NE Load 

1

 

Output Ch 1-A for NE Load 

2

 

Output Ch 1-B for ND Load 

3

 

Output Ch 1-B for ND Load 

4

 

Output Ch 2-A for NE Load 

5

 

Output Ch 2-A for NE Load 

6

 

Output Ch 2-B for ND Load 

7

 

Output Ch 2-B for ND Load 

8

 

DIN-Rail accessories: 
DIN rail stopper MOR016 

Summary of Contents for D1092S

Page 1: ...D1092 SIL 3 Relay Output Module ISM0091 11 D1092S D1092D INSTRUCTION SAFETY MANUAL SIL 3 Relay Output Module DIN Rail Models D1092S D1092D...

Page 2: ...relay energized typical 2 4 W for 2 channels D1092D when used as duplicator Max power consumption at 27 6 V input voltage and relay energized 1 5 W for each channel 3 0 W for 2 channels D1092D when us...

Page 3: ...t Output isolation EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 ATEX IECEx FM FM C EAC EX UKR TR n 898 T V Certifications Type Approval Certificate DNV for maritime applications TUV Function...

Page 4: ...t 1 A NE Load 3 4 Out 1 B ND Load 15 16 In 2 5 6 Out 2 A NE Load 7 8 Out 2 B ND Load 9 11 10 12 MODEL D1092S 13 14 In 1 1 2 Out 1 A NE Load 3 4 Out 1 B ND Load Relay contact shown in de energized posi...

Page 5: ...from Siemens Standard SN29500 Failure rate table Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 99 with determination of SIL supposing mo...

Page 6: ...ssuming Proof Test coverage of 99 with determination of SIL supposing module contributes 10 of total SIF dangerous failures PFDavg vs T Proof table assuming Proof Test coverage of 99 with determinatio...

Page 7: ...ct to earth ground D1092 series must be installed operated and maintained only by qualified personnel in accordance to the relevant national international installation standards e g IEC EN60079 14 Ele...

Page 8: ...ring always ND loads for Model D1092D in addition to channel 1 connections above use terminals 7 and 8 of channel 2 as two poles of relay output contact used to enable or disable the second load circu...