background image

 

D1092 

- SIL 3 Relay Output Module  

G.M. International ISM0091-11 

General Description:

 The single and dual channel DIN Rail Relay Output, D1092S and D1092D are relay modules suitable for the switching of safety related circuits, up to SIL 3 level 

according to IEC61508:2010 Ed.2, for high risk industries. It provides isolation between input and output contacts. 
D1092S provides 1 SPST contact for normally energized loads and 1 SPST contact for normally de-energized loads. 
D1092D provides 2 SPST contact for normally energized loads and 2 SPST contact for normally de-energized loads. 
When the relay is energized, the contacts are closed. When the relay is de-energized, the contacts are open. 

Function:

 1 or 2 totally independent and isolated relay for safety related circuits, provides isolation between input and output. 

D1092S

: SIL 3 Safety Function for NE load (de-energized in safe state) is available at Terminal Blocks 1-2; in this case, the safety function is met when the relay is de-energized (open contact). 

SIL 3 Safety Function for ND load (energized in safe state) is available at Terminal Blocks 3-4; in this case, the safety function is met when the relay is energized (closed contact). 

D1092D

: SIL 3 Safety Function NE load (de-energized in safe state) is available at Terminal Blocks 1-2 and Terminal Blocks 5-6; in this case, the safety function is met when the relays 

are de-energized (open contact). SIL 3 Safety Function for ND load (energized in safe state) is available at Terminal Blocks 3-4 and Terminal Blocks 7-8; in this case the safety function 
is met when the relays are energized (closed contact). 

Signalling LEDs: 

Relay status (yellow). 

EMC: 

Fully compliant with CE marking applicable requirements. 

Functional Safety Management certification:

G.M. International is certified by TUV to conform to IEC61508:2010 part 1 clauses 5-6  

for safety related systems up to and included SIL3. 

Input: 

24 Vdc nom (20.4 to 27.6 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp. 

Current consumption @ 24 V: 

50 mA for each channel with relay energized, typical (100 mA for 2 channels D1092D when used as duplicator 1 input / 2 outputs). 

Power dissipation: 

1.2 W for each channel with 24 V input voltage and relay energized, typical (2.4 W for 2 channels D1092D when used as duplicator). 

Max. power consumption: 

at 27.6 V input voltage and relay energized, 1.5 W for each channel (3.0 W for 2 channels D1092D when used as duplicator). 

Isolation (Test Voltage): 

Input/Output 2.5 KV; Input/Input 500 V; Output/Output 2.5 KV; Output A/Output B 1.5 KV. 

Output: 

voltage free DPST relay contact, normally open. 

Contact material: 

Ag Alloy (Cd free). 

Contact rating: 

3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load). 

Contact inrush current: 

5 A at 30 Vdc, 250 Vac. 

DC Load breaking capacity: 

Mechanical / Electrical life: 

50 * 10

6

 / 1 * 10

5

 operation, typical. 

Operate / Release time: 

5 / 3 ms typical. 

Bounce time NO / NC contact: 

3 ms. 

Frequency response: 

10 Hz maximum. 

Compatibility: 

 
CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions: 

Operating:

 temperature limits –20 to + 60 °C, relative humidity max 95 %. 

Storage:

 temperature limits - 45 to + 80 °C. 

Safety Description: 

ATEX: 

II 3G Ex nAC IIC T4 Gc; 

IECEx: 

Ex nAC IIC T4 Gc 

FM: 

NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4 

FM-C: 

NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4 

EAC-EX:

 2Ex nA nC IIC T4 Gc X 

UKR TR n. 898:

 2ExnAnCIICT4 X 

non-incendive electrical apparatus. 
-20 °C 

 Ta 

 60 °C. 

Approvals: 

IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15; IECEx IMQ 13.0011X conforms to IEC60079-0, IEC60079-15  
FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3611, 3810, ANSI/ISA 12.12.02, ANSI/ISA 60079-0, C22.2 No.142, C22.2 No.213, E60079-0, E60079-15, 
C-IT.MH04.B.00306 conforms to GOST R IEC 60079-0, GOST R IEC 60079-15. 
C

Ц

 16.0034 X conforms to 

ДСТУ

 7113, 

ДСТУ

 I

ЕС

 60079-15. 

TÜV Certificate No. C-IS-236198-03 , SIL 3 conforms to IEC61508:2010 Ed.2. 
TÜV Certificate No. C-IS-236198-09, SIL 3  Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 
DNV No.A-13778 Certificates for maritime applications. 

Mounting: 

T35 DIN Rail according to EN50022. 

Weight:

 about 145 g D1092D, 110 g D1092S. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

Location:

 Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA 

T4 installation. 

Protection class:

 IP 20. 

Dimensions:

 Width 22.5 mm, Depth 99 mm, Height 114.5 mm. 

 

 

 

Technical Data 

0.2

0.1

V (V)

I (A)

10

20

30

40

50

100

0.3 0.4 0.5

1

2

3

Resistive 

Load

200

125

Characteristics 

FSM

SIL 3

Summary of Contents for D1092S

Page 1: ...D1092 SIL 3 Relay Output Module ISM0091 11 D1092S D1092D INSTRUCTION SAFETY MANUAL SIL 3 Relay Output Module DIN Rail Models D1092S D1092D...

Page 2: ...relay energized typical 2 4 W for 2 channels D1092D when used as duplicator Max power consumption at 27 6 V input voltage and relay energized 1 5 W for each channel 3 0 W for 2 channels D1092D when us...

Page 3: ...t Output isolation EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 ATEX IECEx FM FM C EAC EX UKR TR n 898 T V Certifications Type Approval Certificate DNV for maritime applications TUV Function...

Page 4: ...t 1 A NE Load 3 4 Out 1 B ND Load 15 16 In 2 5 6 Out 2 A NE Load 7 8 Out 2 B ND Load 9 11 10 12 MODEL D1092S 13 14 In 1 1 2 Out 1 A NE Load 3 4 Out 1 B ND Load Relay contact shown in de energized posi...

Page 5: ...from Siemens Standard SN29500 Failure rate table Failure rates table according to IEC 61508 2010 Ed 2 PFDavg vs T Proof table assuming Proof Test coverage of 99 with determination of SIL supposing mo...

Page 6: ...ssuming Proof Test coverage of 99 with determination of SIL supposing module contributes 10 of total SIF dangerous failures PFDavg vs T Proof table assuming Proof Test coverage of 99 with determinatio...

Page 7: ...ct to earth ground D1092 series must be installed operated and maintained only by qualified personnel in accordance to the relevant national international installation standards e g IEC EN60079 14 Ele...

Page 8: ...ring always ND loads for Model D1092D in addition to channel 1 connections above use terminals 7 and 8 of channel 2 as two poles of relay output contact used to enable or disable the second load circu...