2
D1092
- SIL 3 Relay Output Module
G.M. International ISM0091-11
General Description:
The single and dual channel DIN Rail Relay Output, D1092S and D1092D are relay modules suitable for the switching of safety related circuits, up to SIL 3 level
according to IEC61508:2010 Ed.2, for high risk industries. It provides isolation between input and output contacts.
D1092S provides 1 SPST contact for normally energized loads and 1 SPST contact for normally de-energized loads.
D1092D provides 2 SPST contact for normally energized loads and 2 SPST contact for normally de-energized loads.
When the relay is energized, the contacts are closed. When the relay is de-energized, the contacts are open.
Function:
1 or 2 totally independent and isolated relay for safety related circuits, provides isolation between input and output.
D1092S
: SIL 3 Safety Function for NE load (de-energized in safe state) is available at Terminal Blocks 1-2; in this case, the safety function is met when the relay is de-energized (open contact).
SIL 3 Safety Function for ND load (energized in safe state) is available at Terminal Blocks 3-4; in this case, the safety function is met when the relay is energized (closed contact).
D1092D
: SIL 3 Safety Function NE load (de-energized in safe state) is available at Terminal Blocks 1-2 and Terminal Blocks 5-6; in this case, the safety function is met when the relays
are de-energized (open contact). SIL 3 Safety Function for ND load (energized in safe state) is available at Terminal Blocks 3-4 and Terminal Blocks 7-8; in this case the safety function
is met when the relays are energized (closed contact).
Signalling LEDs:
Relay status (yellow).
EMC:
Fully compliant with CE marking applicable requirements.
Functional Safety Management certification:
G.M. International is certified by TUV to conform to IEC61508:2010 part 1 clauses 5-6
for safety related systems up to and included SIL3.
Input:
24 Vdc nom (20.4 to 27.6 Vdc) reverse polarity protected, ripple within voltage limits
≤
5 Vpp.
Current consumption @ 24 V:
50 mA for each channel with relay energized, typical (100 mA for 2 channels D1092D when used as duplicator 1 input / 2 outputs).
Power dissipation:
1.2 W for each channel with 24 V input voltage and relay energized, typical (2.4 W for 2 channels D1092D when used as duplicator).
Max. power consumption:
at 27.6 V input voltage and relay energized, 1.5 W for each channel (3.0 W for 2 channels D1092D when used as duplicator).
Isolation (Test Voltage):
Input/Output 2.5 KV; Input/Input 500 V; Output/Output 2.5 KV; Output A/Output B 1.5 KV.
Output:
voltage free DPST relay contact, normally open.
Contact material:
Ag Alloy (Cd free).
Contact rating:
3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load).
Contact inrush current:
5 A at 30 Vdc, 250 Vac.
DC Load breaking capacity:
Mechanical / Electrical life:
50 * 10
6
/ 1 * 10
5
operation, typical.
Operate / Release time:
5 / 3 ms typical.
Bounce time NO / NC contact:
3 ms.
Frequency response:
10 Hz maximum.
Compatibility:
CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating:
temperature limits –20 to + 60 °C, relative humidity max 95 %.
Storage:
temperature limits - 45 to + 80 °C.
Safety Description:
ATEX:
II 3G Ex nAC IIC T4 Gc;
IECEx:
Ex nAC IIC T4 Gc
FM:
NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4
FM-C:
NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4
EAC-EX:
2Ex nA nC IIC T4 Gc X
UKR TR n. 898:
2ExnAnCIICT4 X
non-incendive electrical apparatus.
-20 °C
≤
Ta
≤
60 °C.
Approvals:
IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15; IECEx IMQ 13.0011X conforms to IEC60079-0, IEC60079-15
FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3611, 3810, ANSI/ISA 12.12.02, ANSI/ISA 60079-0, C22.2 No.142, C22.2 No.213, E60079-0, E60079-15,
C-IT.MH04.B.00306 conforms to GOST R IEC 60079-0, GOST R IEC 60079-15.
C
Ц
16.0034 X conforms to
ДСТУ
7113,
ДСТУ
I
ЕС
60079-15.
TÜV Certificate No. C-IS-236198-03 , SIL 3 conforms to IEC61508:2010 Ed.2.
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety.
DNV No.A-13778 Certificates for maritime applications.
Mounting:
T35 DIN Rail according to EN50022.
Weight:
about 145 g D1092D, 110 g D1092S.
Connection:
by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm
2
.
Location:
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA
T4 installation.
Protection class:
IP 20.
Dimensions:
Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
Technical Data
0.2
0.1
V (V)
I (A)
10
20
30
40
50
100
0.3 0.4 0.5
1
2
3
Resistive
Load
200
125
Characteristics
FSM
SIL 3