GV international d1031q Instruction Manual Download Page 9

 

D1021 

- SIL 2 Powered Isolating Driver with Fault Detection Smart-Hart compatible 

G.M. International ISM0022-6 

 

Calibration instruction and Troubleshooting 

In case a calibration check or readjustment is necessary the following equipment is required: 

Adjustable Power Supply Range 0-35 V Resolution 0.1 V, 
Accuracy 1% Output Capability 200 mA  

Current Meter range 20 mA, Resolution 1 µA Accuracy 0.01% 
or Voltage Meter Range 10 V, Resolution 1 mV Accuracy 0.01% 

Current Calibrator range 20 mA, Resolution 1 µA Accuracy 0.01 % 

Agilent  

E3611A 

Agilent 

34410A 

Yokogawa 

7651 

Equipment Required 

Instrument 

• 

Set power supply (PS) at 24.0 V at terminals 3 (+) and 4 (-), the calibrator (CAL) in the function “mA” 20 mA range at terminals 1 (+) and 2 (-), 
the multimeter (DMM) for the reading in DC supply 20 mA range at terminals 14 (+) and 15 (-). 

• 

Verify that green led on the front panel is ON. 

• 

Connect the unit as shown below: 

If the power ON Led is off, check supply voltage, polarity and wiring. 

• 

Set calibrator (CAL) at 4.000 mA and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation 
presented in the section “Technical Data”. 

• 

Set calibrator (CAL) at 20.000 mA and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation 
presented in the section “Technical Data”. 

If the maximum deviation is exceeded, repeat the board calibration and proceed in the following way:  

• 

Set the calibrator (CAL) at 20.000 mA and regulate the current, read by multimeter (DMM), by turning the span trimmer of the unit 
(see “Configuration” section) until reading 20.000 mA ± 5 µA value. 

• 

To execute a linearity test: set the calibrator (CAL) at 4.000, 8.000, 12.000, 16.000, 20.000 mA and verify current output is correspondent with 
a maximum deviation presented in the section “Technical Data”. 

PS 

DMM 

CAL 

Identification 

PS

Supply

=

_

+

CAL

DMM

mA

mA

3 +

In 1

Out 1

MODEL D1021S

=

=

=

14

15

3 +

4 -

1

2

=

=

5

6

7 +

8 -

Summary of Contents for d1031q

Page 1: ...ered Isolating Driver with Fault Detection Smart Hart compatible ISM0022 6 D1021S INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 2 Powered Isolating Driver with Fault Detection Smart Hart compatible DIN Ra...

Page 2: ...61508 for Tproof 1 3 years 10 20 of total SIF PFDavg 1 year 5 18 E 04 SFF 70 66 Output to Zone 0 Zone 20 Division 1 installation in Zone 2 Division 2 4 20 mA Input Output Signal Wide Band Smart Commun...

Page 3: ...ce 50 K Fault signalling voltage free NE SPST optocoupled open collector transistor and voltage free NE SPST relay contact each output is de energized in fault condition Open collector rating 100 mA a...

Page 4: ...ck connections HAZARDOUS AREA SAFE AREA Output Ch 1 for I P Converter Output Ch 1 for I P Converter Not used 13 14 15 16 Input Ch 1 for Source I 1 Input Ch 1 for Source I 2 Power Supply 24 Vdc 3 Power...

Page 5: ...be exceeded 50 of the Co and Lo become the limits which must include the cable such that Ci device C cable 50 of Co and Li device L cable 50 of Lo If the cable parameters are unknown the following va...

Page 6: ...0 Vrms Warning D1021 Associated Apparatus FM Approved under Entity Concept and non incendive field wiring Unclassified Locations or Hazardous Classified Locations Class I Division 2 Groups A B C D T C...

Page 7: ...nted with any orientation over the entire ambient temperature range see section Installation in Cabinet and Installation of Electronic Equipments in Cabinet Instruction Manual D1000 series for detaile...

Page 8: ...tified either by color coding preferably blue or by marking Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts Turn on power the power on green led must b...

Page 9: ...is ON Connect the unit as shown below If the power ON Led is off check supply voltage polarity and wiring Set calibrator CAL at 4 000 mA and verify that the output current read by multimeter DMM is co...

Page 10: ...rs are not running at the maximum current all at the same time the average power consumption of a multitude of isolators can be considered to be only 70 of the value obtained from the section Technica...

Reviews: