GV international d1031q Instruction Manual Download Page 7

 

D1021 

- SIL 2 Powered Isolating Driver with Fault Detection Smart-Hart compatible 

G.M. International ISM0022-6 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. 

For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1021 associated 
apparatus shall be accomplished via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the 

CEC. Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 

D1021 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation 

standards (e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas 
(other than mines), BS 5345 Pt4, VDE 165, ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, 

National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, and the Canadian Electrical Code CEC) following the established installation 

rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 

De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous 
Locations or unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. 

Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the 
enclosure to avoid electrical shock when connected to live hazardous potential

Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is 
known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 

The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. 
Any unauthorized modification must be avoided. 

Operation 

 D1021 isolates and transfers a 4-20 mA signal from a controller located in Safe Area/Non Hazardous Locations to an I/P converter, displays or 

similar equipment located in Hazardous Area/Hazardous Locations. The circuit allows bi-directional communication signal for smart/hart converters. 
A field open circuit or short circuit presents a high impedance to the control device and de-energize the fault signalation outputs (relay and 

open-collector transistor). An input over or under range also de-energize the fault segnalation output. 

A “POWER ON” green led lits when input power is present, a “FAULT” red led lits when fault condition is present. 

Installation 

 D1021 is a powered isolating driver smart/hart compatible with field fault detection and signalation, housed in a plastic enclosure suitable for 

installation on T35 DIN Rail according to EN50022. D1021 unit can be mounted with any orientation over the entire ambient temperature range, 
see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet" Instruction Manual D1000 series for detailed 

instructions. 

Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged 

in/out into a powered unit without suffering or causing any damage 

(for Zone 2 or Division 2 installations check the area to be nonhazardous 

before servicing)

The wiring cables have to be proportionate in base to the current and the length of the cable. 

On the section “Function Diagram” and enclosure side a block diagram identifies all connections. 

Identify the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example: 
Connect 24 Vdc power supply positive at terminal “3” and negative at terminal “4”. 

Connect positive input at terminal “1” and negative input at “2”. 

Connect fault relay output contact at terminal “5” and “6”. 

Connect fault open collector output positive at terminal “7” and negative at terminal “8”. 
Connect signal output at terminal “14” for positive and “15” for negative. 

 

Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international 

installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas 
(other than mines), BS 5345 Pt4, VDE 165, ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, 

National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, and the Canadian Electrical Code CEC), make sure that conductors are well 

isolated from each other and do not produce any unintentional connection. 

Connect SPST fault relay contacts checking the load rating to be within the contact maximum rating (2 A, 250 V, 500 VA 80 W resistive load). 
Connect SPST fault transistors checking the load rating to be within the maximum rating (100 mA, 35 V resistive load). 

The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for 

indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) 

consistent with the effective operating environment of the specific installation. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 

If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D1021 must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 
According to EN61010, D1021 must be connected to SELV or SELV-E supplies. 

Relay output contact must be connected to loads non exceeding category I, pollution degree I overvoltage limits. 

Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the 
enclosure to avoid electrical shock when connected to live hazardous potential

 

 

Summary of Contents for d1031q

Page 1: ...ered Isolating Driver with Fault Detection Smart Hart compatible ISM0022 6 D1021S INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 2 Powered Isolating Driver with Fault Detection Smart Hart compatible DIN Ra...

Page 2: ...61508 for Tproof 1 3 years 10 20 of total SIF PFDavg 1 year 5 18 E 04 SFF 70 66 Output to Zone 0 Zone 20 Division 1 installation in Zone 2 Division 2 4 20 mA Input Output Signal Wide Band Smart Commun...

Page 3: ...ce 50 K Fault signalling voltage free NE SPST optocoupled open collector transistor and voltage free NE SPST relay contact each output is de energized in fault condition Open collector rating 100 mA a...

Page 4: ...ck connections HAZARDOUS AREA SAFE AREA Output Ch 1 for I P Converter Output Ch 1 for I P Converter Not used 13 14 15 16 Input Ch 1 for Source I 1 Input Ch 1 for Source I 2 Power Supply 24 Vdc 3 Power...

Page 5: ...be exceeded 50 of the Co and Lo become the limits which must include the cable such that Ci device C cable 50 of Co and Li device L cable 50 of Lo If the cable parameters are unknown the following va...

Page 6: ...0 Vrms Warning D1021 Associated Apparatus FM Approved under Entity Concept and non incendive field wiring Unclassified Locations or Hazardous Classified Locations Class I Division 2 Groups A B C D T C...

Page 7: ...nted with any orientation over the entire ambient temperature range see section Installation in Cabinet and Installation of Electronic Equipments in Cabinet Instruction Manual D1000 series for detaile...

Page 8: ...tified either by color coding preferably blue or by marking Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts Turn on power the power on green led must b...

Page 9: ...is ON Connect the unit as shown below If the power ON Led is off check supply voltage polarity and wiring Set calibrator CAL at 4 000 mA and verify that the output current read by multimeter DMM is co...

Page 10: ...rs are not running at the maximum current all at the same time the average power consumption of a multitude of isolators can be considered to be only 70 of the value obtained from the section Technica...