5
Installation fixture of indoor unit
Pipelines can be connected in the directions of
1
,
2
,
3
,
4
and
5
as indicated in Fig. 1. When the pipelines
are connected to the directions of
3
,
4
and
5
, a
groove for the pipes has to be opened at the proper
place on the base stand.
1. Installation of wall-mounting plate
Fix the wall-mounting plate firmly on the wall with screws.
Make sure of the leveling of the plate. Slanted wall-
mounting plate might jeopardize the smooth discharge of
the condensed water.
2. Drill holes on the wall
Drill holes at places slightly below the wall-mounting
plate, with hole diameter of 65mm(2-3/5”) and the outer
edge of the hole 5-10mm(1/5-2/5”) lower (Fig.2) so that
the condensed water can smoothly flow out. Cut the
wall penetrating pipe to proper length according to the
thickness of the wall (3- 5mm(1/10-1/5”) longer than the
wall thickness) and insert the pipe as indicated in Fig.2.
3. Installation of drain pipe
Install the pipelines of the indoor unit in accordance with
the direction of the wall holes. Wrap tightly the drain pipe
and the pipelines with tape. Make sure that the drain pipe
is underneath the pipelines. (Fig.3) (When the drain pipe
passes the room interior, some condensed water might
occur to its surfaces if the humidity is very high).
4. Installation of indoor unit
Pass the connection wires, connecting pipelines and
drain pipe through the wall hole. Hang the indoor unit on
the hooks at the top of the wall-mounting plate so that the
hooks at the bottom of the indoor unit match the hooks of
the wall-mounting plate. (Fig.4)
Fig. 1
Left outlet
Left rear outlet
Rear outlet
Bottom outlet
Right outlet
Fig. 2
Fix with tape
Wall cap
Wall pipe
Interior
Exterior
5-10 mm lower
(1/5-2/5”)
Fig. 3
Pipelines of indoor
unit
Rear pipe
Drain pipe
Top hooks
Bottom hooks
Hook support
Fig. 4