Central Module » Installation
G&D DVICenter DP64 ·
4
Installation
The following pages describe the configuration of the
Dynamic Ports
(optional) and
the installation of the devices of the KVM system.
Power supply
Main Power:
Plug one of the supplied power cable in this interface. Connect the
power cable with a power outlet and turn the power button on.
Red. Power:
If required, plug one of the supplied power cable in this interface to
establish a redundant power supply. Connect the power cable with a power outlet of
another
power circuit and turn the power button on.
NOTE:
When choosing a place for the device, please ensure to comply with the
ambient temperature limit (see
on page 29) close to the device. The
ambient temperature limit must not be influenced by other devices.
When installing the devices, make sure to only place a maximum of three devices
directly on top of each other. This provides sufficient circulation of air and mutual
thermal interference can be avoided. After having installed three devices, provide
for a distance of at least 3cm.