47
Maintenance, service and fault tracing
4
Winter drainage
It is extremely important to remember to winter drain
the machine before winter storage! The guarantee does
not cover damage to the titanium heat exchanger due to
freezing! Drainage is easy to perform, by unscrewing the pipe
connections on the inlet and outlet pipes. Check that the
machine is really drained. It is a good idea to flush out the
heat exchanger in connection with winter drainage using,
e.g. a garden hose to remove any chlorine residue.
Maintenance
Clean the pool/spa filter regularly to ensure sufficient
;
circulation.
Check that the area surrounding the unit provides good
;
drainage and ventilation.
It is a good idea to clean the heat exchanger to promote
;
good function and energy savings. This is easily done
with winter drainage. Flush the heat exchanger using e.g.
a garden hose and drain thoroughly. This will reduce the
risk of chlorine deposit build up.
Check the power supply and cable connections regularly.
;
If the unit does not function as designed, shut it down
and contact the installation engineer.
Check that the evaporator is clean. Use a brush and
;
vacuum to remove any dust or leaves. Don’t use a high
pressure jet! Regular cleaning will guarantee maximum
efficiency.
Clean the surface using a sponge or the like. To minimize
;
ageing of the surface, it’s recommended to apply wax at
least once every year.
Ahead of the winter – drain and cover!
;
Fault tracing
If a fault should occur you should always contact the
installation engineer who carried out the installation. If he/
she in turn considers it to be a question of a material or
manufacturing fault, he/she will contact us for inspection
and action to rectify the problem. Always state the product’s
manufacturing number. Information can be gained from the
following fault tracing guide. Frequently asked questions
with answers are also presented in the section 6. Always read
through this section before contacting your dealer.
Operating disturbance
Error message
Cause
Action
Sensor error inlet (INWT)
PP01
Sensor not connected, broken
cable or short circuit
Check or replace the sensor
Sensor error outlet (OUTWT)
PP02
Sensor not connected, broken
cable or short circuit
Check or replace the sensor
Sensor error evaporator
(PIPE1)
PP03
Sensor not connected, broken
cable or short circuit
Check or replace the sensor
Sensor error hot gas sensor
(PIPE2)
PP04
Sensor not connected, broken
cable or short circuit
Check or replace the sensor
Sensor error outdoor sensor
(ROOMT)
PP05
Sensor not connected, broken
cable or short circuit
Check or replace the sensor
Too high temp. difference
between inlet and outlet
PP06
Insufficient water flow, 12 degrees
difference between inlet and outlet
Check the water flow
Anti-freeze protection
PP07
Inlet under 4 °C and outdoor air 0
°C or colder
Automatic heating mode
Flow switch
EE03
Low flow or no water in the system
Check the water flow, adjust the
bypass, replace the flow switch
High pressure or low pressure
pressostat
EE04
Gas quantity too high or low.
Contact installer.
Communication error
EE08
No contact with the control unit
Check the connection between
the control unit and display
Error code table
In the event of any uncertainty before winter
drainage, contact your dealer! An iced-up heat
exchanger due to forgotten winter drainage is
not covered by the guarantee!
!