5. Description of device function and setting

Information from regulator is available directly through LCD or you can read them with one of

next communication protocols ( Modbus RTU, Advantech-ADAM ). 

5.1. Device setting from the manufacturer 

If  special  setting  was  not  required  in  the  order,  regulator  is  set  from  the  manufacturer  to  the 

following parameters: 

communication protocol: 

Modbus RTU

 

regulator address: 

1

 

communication speed: 

9600Bd, no parity, 2 stop bits

 

Value assigned to Relay1 and Relay2: 

none

 

Password for setting through keys (PASS): 

0000 

LCD display:  

on

 

value shown at first LCD line: 

temperature, temperature / pressure 

– by device type 

value shown at second LCD line: 

relative humidity / dew point temperature 

temperature unit: 

°C 

pressure unit: 

hPa 

correction for altitude: 

0 hPa

 (absolute pressure) 

computed value preset: 

dew point

 

temperature 

relay response for error: 

stay unchanged at previous condition 

signalization of binary inputs status: 

LED diode lights if input contact is open

 

acoustic alarm: 

off

 

5.2. Relay outputs 

Regulator is equipped with two relay outputs. It is possible to assign any input or computed value 

or “Far condition” (see chapter 

6.1.4 

at page 20) to each relay, to set comparing alarm limit, if the 

relay may close if measured value is higher (Hi) or lower (Lo) than preset limit, delay for while must 
be preset condition true before relay close its contact and hysteresis for return to open status. For 
binary inputs: if it is preset to „HI“ then output relay is closed when input contact is opened, if it is 
preset to „Lo“ then output relay is closed when input contact is closed. Each relay status is indicated 
with LED diode and shown on LCD with corresponding symbols „

“ or „

“. 

Terminal block for connecting the relays is equipped with terminals GND, which are connected 

to the power supply of the device (see chapter 

Typical application wiring, connection of terminals

)

When you need to use relays to switching the voltage identical with the supply voltage of the device, 
you can use jumpers J1 and J2 for interconnection the power supply of the device directly with the 
common contacts of the relays. 

This modification is used in devices with serial number higher 

than 16981000 

(the wiring diagram of the relay contacts for devices with serial number lower than 

16981000 is given in the 

Appendix

 D”).  

The devices are equipped with two relays that are not intended for direct switching power circuits 

or mains voltage. If necessary, use suitable type of external relay (an example of wiring is given in 
the “

Appendix A”

). 

5.3. Binary inputs 

It is possible to read status of three galvanically not isolated binary inputs. It is possible to connect 

“open contact” or external voltage. Auxiliary power U terminal can be used to supplying 

of 

external sensors and detectors. 

Visualization of binary inputs is done by three LED diodes placed on 

the left side from LCD. Green one represents input Binary 1, yellow input binary 2 and red input 

Summary of Contents for AR006687

Page 1: ...Temperature humidity and pressure regulator with RS485 serial output AR006687 AR006689 AR006690 AR006688 AR006693 Instruction Manual...

Page 2: ...lator 19 6 1 4 Far controlling of output relays status 20 6 1 5 Output relay alarm condition configuration with using of Modbus communication protocol 2 21 6 2 PROTOCOL COMPATIBLE WITH ADVANTECH ADAM...

Page 3: ...ut the cover Do not use the instrument if it does not work correctly If the instrument seems not to work correctly have it checked by a qualified service person Do not use the instrument in an explosi...

Page 4: ...o Modbus RTU communication protocol If you would like to use different communication protocol then Modbus RTU it is necessary preset them see latter Temperature relative humidity and pressure sensors...

Page 5: ...as far as possible from potential interference sources For devices with RS485 output there is recommended to use shielded twisted copper cable maximal length 1200m The cable must be located at indoor...

Page 6: ...6 3 Typical application wiring connection of terminals 4 Dimensions AR006687...

Page 7: ...7 AR006689 AR006693...

Page 8: ...8 AR006688 AR006690 Probe for compressed air measurement...

Page 9: ...tact and hysteresis for return to open status For binary inputs if it is preset to HI then output relay is closed when input contact is opened if it is preset to Lo then output relay is closed when in...

Page 10: ...information about Relay1 and then Relay2 setting step by step Information about Relay1 are indicated with symbol for Relay2 with symbol at right top corner of LCD It is possible to edit parameters af...

Page 11: ...n measured value decrease under high limit value minus the hysteresis value See example High limit HI Delay s Hysteresis Low limit Lo the relay closes when measured value falls below preset low limit...

Page 12: ...h the software 5 5 2 Setting with using regulator keys If Actual regulator preset is displayed see chapter Actual regulator preset at page 10 it is possible to enter into edit mode and edit displayed...

Page 13: ...ount four screws in the corners of the box and remove the lid 3 closed jumper placed nearby keys 4 press and keys together and keep them down 5 connect power supply to regulator you should see message...

Page 14: ...elay2 stays unchanged in previous status Relay1 switch OFF Relay1 switch On stays unchanged in previous status Relay2 switch OFF Relay2 switch On Change of Password for setting through keys PASS This...

Page 15: ...ation of inputs is done by three LED diodes This option defines at which binary input status should LED diode indication lights LED diode lights if binary input is OPEN or CLOSED LED lights if binary...

Page 16: ...le to set corresponding pressure offset for this altitude It is possible to change it after SET key pressing Pressure correction value is then automatically added to measured pressure value See chapte...

Page 17: ...line see Computed value selection below It is possible to change it after SET key pressing show value on LCD don t show value on LCD Show barometric pressure at LCD display This item provides to choic...

Page 18: ...re pressure by device type value shown at second LCD line relative humidity dew point temperature temperature unit C pressure unit hPa correction for altitude 0 hPa absolute pressure computed value pr...

Page 19: ...on of jumper is as follows Jumper opened device memory is protected from writing from device side it is only enabled to read measured value writing to memory is disabled no change of settings is enabl...

Page 20: ...address 0x31 or 0x30 Status word 16b value return bite description Bit0 0 1 jumper open closed Bit1 unused Bit2 0 always 0 Bit3 0 1 Relay1 open closed Bit4 0 1 Relay2 open closed Bit5 0 1 internal aco...

Page 21: ...d into device memory confirm change Then registers 0x004F 79 and 0x0044 68 are automatically cleared zero It automatically unlocks the keyboard too Whole setting process can be cancelled by writing va...

Page 22: ...on examples are listed in a separate document entitled Description of communication protocols 6 2 Protocol compatible with Advantech ADAM standard Control units communicate on master slave principle i...

Page 23: ...means manufacturer setting of communication protocol is done For communication with device which measure more than one value there is necessary to add at the end of command number of communication cha...

Page 24: ...appears in case of Measured temperature is lower than approximately 210 C i e low resistance of temperature sensor probably short circuit Relative humidity is lower than 0 i e damaged sensor for meas...

Page 25: ...nly value number without corresponding unit 9 Preventive maintenance and calibration Pay heed to recommended calibration interval Do not subject the device to mechanical stress 10 Technical specificat...

Page 26: ...emperature compensated at entire temperature range Accuracy 2 5 RH from 5 to 95 RH at 23 C 73 4 F Range 0 to 100 RH Resolution 0 1 RH Measuring temperature and humidity range is limited in accordance...

Page 27: ...emperature probe model Resolution 0 1 C 0 2 F Accuracy 0 2 C 0 4 F without probe 10 1 7 AR006693 temperature relative humidity and barometric pressure regulator Temperature and relative humidity param...

Page 28: ...temperature Range 60 to 80 C 76 to 176 F Accuracy 1 5 C 2 7 F at ambient temperature T 25 C 77 F and relative humidity RH 30 for more details see graphs below Absolute humidity Range 0 to 400 g m3 Acc...

Page 29: ...dity and temperature restriction 10 2 Operating conditions Operating temperature and relative humidity electronics 30 to 80 C 22 to 176 F 0 to 100 RH without condensation probe AR006690 30 to 105 C 22...

Page 30: ...over downwards Not allowed manipulations It is not allowed to operate the device under conditions other than specified in technical parameters Devices are not designed for locations with chemically ag...

Page 31: ...nd pin 8 B The pull up pull down and termination resistors are part of the transmitter These internal resistors can be connected to the bus by connecting the corresponding pins of CANON connector for...

Page 32: ...g valve 3 probe 4 flow chamber SH PP 5 closing valve 6 outlet tube sampling 1 end of the tube placed in the centre of pressure pipelines distribution of moisture in the pipe cross section is not homog...

Page 33: ...ins basic information about connection of the detectors optional accessories to binary inputs of regulator The detectors install in accordance with the attached instructions for use SP008 power detect...

Page 34: ...is used connect the terminals ALARM to the terminals GND and IN1 If the detector is powered from the regulator it is necessary to use power supply of 12Vdc for power supplying the regulator Notice Th...

Reviews: