QT027
kW RATING
27
ENGINE SIZE
2.4 Liter Inline 4
GENERATOR OUTPUT VOLTAGE/KW - 60Hz
KW Nat. Gas AMP
KW LPG
AMP CB Size (Both)
120/208V, 3-phase, 0.8 pf
25
87
27
94
100
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208 3-phase
43
ENGINE FUEL CONSUMPTION
(Natural Gas) (Propane)
Natural Gas (25 kW)
Propane (27 kW)
(ft
3
/hr.)
(gal/hr.)
cu ft/hr
Exercise cycle
42
0.44
16
25% of rated load
108
1.2
44
50% of rated load
197
2.2
81
75% of rated load
287
3.2
118
100% of rated load
359
4.1
147
ENGINE COOLING
Air flow
(inlet air including alternator and combustion air)
ft
3
/min.
2,400
System coolant capacity
US gal.
2.5
Heat rejection to coolant
BTU/hr.
120,000
Max. operating air temp. on radiator
°C (°F)
60 (150)
Max. ambient temperature
°C (°F)
50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz
cfm
68
SOUND EMISSIONS IN DBA
Exercising at 7 meters
61
Normal operation at 7 meters
70
EXHAUST
Exhaust flow at rated output 60 Hz
cfm
130
Exhaust temp. at muffler outlet
°F
900
ENGINE PARAMETERS
Rated synchronous RPM
60 Hz
1800
HP at rated KW
60 Hz
40
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration
3% for every 10 °C above - °C
25
1.65% for every 10 °F above - °F
77
Altitude Deration
1% for every 100 m above - m
183
3% for every 1000 ft. above - ft.
600
ENCLOSURE
Material
Aluminum
Color
PMS 422 (Bisque)
OPERATING DATA
QT027
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings
apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is
no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.