background image

APPLICATION
& ENGINEERING DATA

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage.  No overload capability is available for this rating.  (All ratings in accordance with 
BS5514, ISO3046, ISO8528 and DIN6271). 

QT027

GENERATOR SPECIFICATIONS

TYPE ...........................................................................................................Synchronous
ROTOR INSULATION ..........................................................................................Class H
STATOR INSULATION .........................................................................................Class H
TOTAL HARMONIC DISTORTION ........................................................................... <5%
TELEPHONE INTERFERENCE FACTOR (TIF) ........................................................<50
ALTERNATOR OUTPUT LEADS 3 PHASE ...........................................................4 wire
BEARINGS .................................................................................................... Sealed Ball
COUPLING .................................................................................................. Flexible Disc
LOAD CAPACITY (STANDBY RATING) ................................................................ 27 kW
EXCITATION SYSTEM ........................................................................................... Direct

NOTE:    Generator  rating  and  performance  in  accordance  with 
ISO8528-5,  BS5514,  SAE  J1349,  ISO3046,  and  DIN6271  standards.

GENERATOR FEATURES

 

Revolving field heavy duty generator

 

Directly connected to the engine

 

Operating temperature rise 120 °C above a 40 °C ambient

 

Insulation is Class H rated at 150 °C rise

 

All models are fully prototyped tested

VOLTAGE REGULATOR

TYPE ................................................................................................................Electronic
SENSING ................................................................................................... Single Phase
REGULATION .......................................................................................................... ± 1%
FEATURES ............................................................................................... V/F Adjustable
 

Adjustable Voltage and Gain

LED Indicators

CONTROL PANEL FEATURES

 

SEVEN LED INDICATOR LIGHTS    

ADDITIONAL FUNCTIONS

    • System ready 

• Utility sensing

    • Low fuel pressure 

• Delay on utility failure for engine start

    • Low battery 

• Engine warm-up before transfer

    • Low oil pressure 

• Delay to retransfer to utility

    • High coolant temp/low coolant temp 

• Engine cooldown timer

    • Overspeed 

• Exerciser not set

    • Overcrank 

• Hour meter

 

INTERNAL FUNCTIONS:

    • 3 position switch (auto, off and manual)
    • 2 wire start for any transfer switch
    • Communicates with the Generac RTS transfer switch
    • Built-in 7 day exerciser
    • Selectable engine speed at exercise
    • Governor controller is built into the master control board
    • Temperature range -40 °

C to 70 °C

ENGINE SPECIFICATIONS

MAKE ................................................................................................................ Generac
MODEL .................................................................................................................Inline 4
CYLINDERS ...................................................................................................................4
DISPLACEMENT .................................................................................................2.4 Liter
BORE ........................................................................................................................3.41
STROKE ....................................................................................................................3.94
COMPRESSION RATIO ...........................................................................................8.5:1
INTAKE AIR SYSTEM ....................................................................... Naturally Aspirated
VALVE SEATS ..................................................................................................Hardened
LIFTER TYPE ....................................................................................................Hydraulic

GOVERNOR SPECIFICATIONS

TYPE ................................................................................................................Electronic
FREQUENCY REGULATION ....................................................................... Isochronous
STEADY STATE REGULATION ..............................................................................± 0.25
ADJUSTMENTS FOR:
 

Speed .....................................................................................................Yes

 

Droop ......................................................................................................Yes

ENGINE LUBRICATION SYSTEM

OIL PUMP ................................................................................................................Gear
OIL FILTER ............................................................................. Full flow spin-on cartridge
CRANKCASE CAPACITY ...................................................................................4 Quarts

ENGINE COOLING SYSTEM

TYPE .....................................................................................................................Closed
WATER PUMP .................................................................................................Belt driven
FAN SPEED .............................................................................................................1980
FAN DIAMETER .......................................................................................... 17.75 inches
FAN MODE ........................................................................................................... Pusher           

FUEL SYSTEM

FUEL TYPE ..........................................................................Natural gas, propane vapor
CARBURETOR...............................................................................................Down Draft
SECONDARY FUEL REGULATOR ................................................................... Standard
FUEL SHUT OFF SOLENOID .......................................................................... Standard
OPERATING FUEL PRESSURE ..................................................................5” - 14” H2O

ELECTRICAL SYSTEM

BATTERY CHARGE ALTERNATOR .............................................................12V 30 Amp
STATIC BATTERY CHARGER .............................................................................. 2 Amp
RECOMMENDED BATTERY ............................................................Group 26, 525CCA
SYSTEM VOLTAGE .............................................................................................12 Volts

Summary of Contents for QT027

Page 1: ...erator Sets Standby Power Rating 27 kW 60 Hz Naturally Aspirated Gaseous Fueled Innovative design and fully prototype tested UL2200 Listed Solid state frequency compensated voltage regulator Dynamic and static battery charger Sound attenuated acoustically designed enclosure Quiet test for low noise level exercise Acoustically designed engine cooling system High flow low noise factory engineered ex...

Page 2: ...engine start Low battery Engine warm up before transfer Low oil pressure Delay to retransfer to utility High coolant temp low coolant temp Engine cooldown timer Overspeed Exerciser not set Overcrank Hour meter INTERNAL FUNCTIONS 3 position switch auto off and manual 2 wire start for any transfer switch Communicates with the Generac RTS transfer switch Built in 7 day exerciser Selectable engine spe...

Page 3: ... power 60 Hz cfm 68 SOUND EMISSIONS IN DBA Exercising at 7 meters 61 Normal operation at 7 meters 70 EXHAUST Exhaust flow at rated output 60 Hz cfm 130 Exhaust temp at muffler outlet F 900 ENGINE PARAMETERS Rated synchronous RPM 60 Hz 1800 HP at rated KW 60 Hz 40 POWER ADJUSTMENT FOR AMBIENT CONDITIONS Temperature Deration 3 for every 10 C above C 25 1 65 for every 10 F above F 77 Altitude Deratio...

Page 4: ...READY FUSES AUTO MANUAL OFF OFF ON TIME SET EXERCISE LOW COOLANT LEVEL OVER SPEED OVER CRANK DANGER 28 98 FRONT VIEW 62 2 46 02 DOOR TYP 33 5 SEE INSTALL DWG 0G9370 FOR DETAILS HOURS 1 10 QUARTZ Installation Drawing Ref No 0G0325 Generac Power Systems Inc P O Box 8 Waukesha WI 53187 generac com 2008 Generac Power Systems Inc All rights reserved All specifications are subject to change without noti...