Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment).

6

Guardian Equipment 
1140 N North Branch St 
Chicago, IL 60642

312 447 8100 

telephone

 

312 447 8101 

facsimile 

gesafety.com

rev. 1215 / © 2015  Guardian Equipment

Installation, Operation and Maintenance Guide

G3900LF Series Thermostatic Mixing Valves

Flow Capacities

System Pressure Drop (PSI)

0

12.5

25

37.5

50

Flow Rate (GPM)

50

60

70

80

90

100

110

120

130

CAUTION: ALL THERMOSTATIC MIXING VALVES HAVE 

LIMITATIONS. THEY WILL NOT PROVIDE THE DESIRED 

ACCURACY OUTSIDE OF THEIR FLOW CAPACITY 

RANGE. CONSULT THE CAPACITY CHART AND DO NOT 

OVERSIZE. MINIMUM FLOW MUST BE NO LESS THAN 

SHOWN ABOVE. 

IMPORTANT: THESE SYSTEMS ARE DESIGNED TO 

PROVIDE MIXED WATER FROM 60 TO 90°F 

(

15 TO 

32°C

)

 FOR EMERGENCY EQUIPMENT APPLICATIONS  

ONLY IN ACCORDANCE WITH ASSE 1071.

G3900LF/G3950LF

MODEL

IN

OUT

MINIMUM 

FLOW 

(GPM)

INTERNAL 

COLD WATER 

BYPASS 

MINIMUM

SYSTEM PRESSURE DROP

5

10

15

20

25

30

35

40

45

PSI

L/MIN

.3

.7

1.0

1.4

1.7

2.1

2.4

2.8

3.1

BAR

G3900LF 

G3950LF 1-1/4"

1-1/2"

3

40

53

64

72

81

90

99

108

117

126

GPM

11

151

201

242

273

307

341

374

409

443

477

L/MIN

MAXIMUM FLOW CAPACITY

Limited Warranty

Guardian Equipment warrants the original purchaser that its products will be free from defects in materials and workmanship under normal usage conditions, 

and when properly installed and maintained according to manufacturer's instructions for a period of two years from date of shipment. During the warranty 

period, Guardian Equipment will (at its discretion) repair or replace any product or part thereof, which shall be returned, freight prepaid to Guardian's factory 

and determined by the manufacturer to be defective in materials or workmanship. There are no warranties, expressed or implied, which extend beyond verbiage 

contained herein. There are no implied warranties of merchantability or 

fi

tness for a particular purpose. Guardian Equipment will not be held liable for labor, 

incidental or consequential damages. Any alteration or improper installation or improper use of the product will void this limited warranty.

Summary of Contents for G3900LF Series

Page 1: ... be easily cleaned adjusted or repaired 2 Inlets are clearly marked on valve body casting Connect hot water to inlet marked HOT and cold water to inlet marked COLD 3 Included angle checkstops must be installed on both supply lines 4 Use solder or pipe cement sparingly Flush supply pipes before connecting valve Flush outlet pipe and valve once valve is connected Maximum operating pressure is 125 PS...

Page 2: ...screw Remove snap cap pointer screw washer and pointer 2 Activate emergency fixture 3 Temporarily place pointer on pointer rod and turn handle to the left allowing cold water to flow Then slowly adjust handle to the right until the required maximum temperature is reached Note Temperatures above 90 F are not recommended Consult a medical advisor for correct temperature settings 4 Once maximum tempe...

Page 3: ...y thermostatic mixing valve on the G3950LF 2 Activate emergency equipment and allow temperature to reach set point 3 Turn primary thermostatic mixing valve to full cold and wait ten seconds 4 Turn primary thermostatic mixing valve to full hot and wait ten seconds 5 Verify outlet temperature does not exceed 90 F 32 C 6 Turn primary thermostatic mixing valve to full cold and wait ten seconds 7 If ne...

Page 4: ... with non corrosive agent and soft cloth DO NOT USE ABRASIVES Wash parts thoroughly after cleaning and reassemble Install port sleeve with elongated holes nearest the check nut and tighten port sleeve nut against port sleeve assembly DO NOT OVERIGHTEN Tighten check nut against valve body Driving ball on thermostat group should then be inserted into ball socket for final reassembly Figure 1 To Repl...

Page 5: ...nters Repair kit Includes parts to repair both hot and cold checkstops 2 1 3 4 6 8 7 5 9 10 11 12 13 14 16 16 24 25 25 26 26 22 23 TM 36 PointerSetScrew 17 17 18 18 20 20 21 19 15 Item Part No Description 1 57 L Snap Cap 2 TM 29 29A Pointer Screw 3 TM 25C Pointer 4 30 Friction Spring 5 617 Dial Plate 6 TM 25D Stop Screw 7 TM 16 Cover Screws 6 8 TM 15B 125 Cover 9 TM 21 125 Flange Packing 10 TGM 2 ...

Page 6: ...YSTEM PRESSURE DROP 5 10 15 20 25 30 35 40 45 PSI L MIN 3 7 1 0 1 4 1 7 2 1 2 4 2 8 3 1 BAR G3900LF G3950LF 1 1 4 1 1 2 3 40 53 64 72 81 90 99 108 117 126 GPM 11 151 201 242 273 307 341 374 409 443 477 L MIN MAXIMUM FLOW CAPACITY Limited Warranty Guardian Equipment warrants the original purchaser that its products will be free from defects in materials and workmanship under normal usage conditions...

Reviews: