Note: this is a control system which must be cleaned and maintained on a regular basis (see maintenance guide and record MGRG-1000).
4
Guardian Equipment
1440 N North Branch
Chicago, IL 60642
312 447 8100
telephone
312 447 8101
facsimile
gesafety.com
rev. 0114 / © 2014 Guardian Equipment
Installation, Operation and Maintenance Guide
G3600 Series Thermostatic Mixing Valves
STOP
6820
PORT SLEEVE ASSY.
TAG-1M
Instructions for Dismantling Valve
Turn off hot and cold supplies to this valve. Remove four cover
screws MU-2C, lift off cover and thermostat group 6810 (fig. 1).
After installing new parts, it will be necessary to reset Pointer to
obtain correct temperature range from Cold to Hot. See page 2
instructions “TO RESET ADJUSTABLE HIGH TEMPERATURE LIMIT
STOP.”
To Clean Port Sleeve Assembly:
To clean port sleeve assembly TAG-1M (fig. 2.): Remove base
stud TA-5. Back off port sleeve nut 3402 as far as it will go into
base. Slide TAG-1M port sleeve assembly toward port sleeve
nut and lift out of valve base. Clean part TAG-1M with a soft
cloth; DO NOT use abrasives such as emery cloth or sandpaper.
After cleaning, wash parts in clean water and reassemble in
valve base. When reassembling port sleeve assembly BE SURE
TO INSTALL WITH SHORT SLOT END IN BASE AND LONG SLOT
END AT PORT SLEEVE NUT. Locate one set of port slots facing
directly toward front of the valve. Tighten port sleeve nut 3402
just enough to hold port sleeve in place, (do not cramp or dis-
tort port sleeve by exerting excess size pressure when tighten-
ing port sleeve nut).
To Clean Thermostat Group:
To clean thermostat group 6810 (DWG 1.), remove handle
68240 by loosening lock screw and pull off. Remove stop re-
taining ring MU-13D and stop 6820. Remove thermostat group
by pushing rod through cover. BE CAREFUL NOT TO PULL COILS
OUT OF SHAPE. If deposit has collected on thermostat coil,
clean it off with a brush in cleaning solution and wash well
before reassembly. Cleaning solution should be non-corrosive
and grit free. To reassemble: be sure, port sleeve assembly is
in place and is working freely from side to side. Reinstall base
stud TA-5, then place thermostat group 6810 on base stud and
BE SURE DRIVING BALL ON PORT SLEEVE ASSEMBLY TAG-1M IS
INSERTED IN HOLE ON LOWER COIL BRACKET (DWG 3.) Move
thermostat back and forth to be sure all parts are free. Replace
cover on valve base, install the four cover screws, and turn on
hot and cold water supplies. See instructions below “To Reset
High Temperature Limit Stop” to properly reset limit stop.
After installation, adjustment, and cleaning, always check the
temperature of the valve when turned to full HOT per the
warning on the front page, using a thermometer. Also check
and if necessary adjust the temperature of the hot water
source. EXCESSIVELY HOT WATER (OVER 90ºF) IS DANGEROUS
AND MAY CAUSE SCALDING!!
HANDLE
68240