Inv Under Voltage
Alarm Code:33
Indicates that the UPS get
inverter under voltage fault
The UPS transfers to Bypass
mode if supporting the load
Inv Softstart Fail
Alarm Code:34
Indicates that the inverter
could not soft start
successfully
Contact your service
representative
Charger Fail
Alarm Code:15
Indicates that the UPS has
confirmed the charger has
failed
The UPS turns off the
charger until the next power
recycle. Contact your service
representative
Battery Over Voltage
Alarm Code:16
Indicates that the battery
voltage is too high
The UPS will turn off the
charger until the battery
voltage is normal
Fatal eeprom Fault
Alarm Code:A3
Indicates that the UPS could
not read eeprom
successfully
Contact your service
representative
Negative power Fault
Alarm Code:
E1
In parallel system
,
power of
UPS is negative
Redundancy mode
,
the fault
UPS turn to fault mode
without output
Increase mode
,
UPS1&
UPS2 turn to fault mode
Parallel cable loss
Alarm Code:
E2
In parallel system
,
parallel
cable disconnect
Disconnect parallel cable
one turn to fault mode
Parallel system
battery status
Alarm Code:
E6
UPS1 connect battery
,
UPS2 without battery
Check battery connect status
Line input different
Alarm Code:
E7
Parallel system
,
UPS1 line
ok
,
UPS2 line loss
Check the line input
Bypass input different
Alarm Code:
E8
Parallel system
,
UPS1
bypass ok
,
UPS2 Bypass
loss
Bypass different
,
not allow
turn on UPS. Check bypass
input
Power strategy
different
Alarm Code:
E9
Parallel system
,
UPS OP
mode
(
normal
,
converter
,
HE
)
different
Check UPS OP mode, Keep
OP mode be the same
Rate power different
Alarm Code:
EA
Parallel system rate power
different
Rate power different
,
not
allow turn on UPS. Keep rate
power be the same
HE in parallel
Alarm Code:
EB
Parallel system
,
OP mode
set as HE
HE not allow in parallel
system
,
change OP mode