STRuCTuRE

6

ADICOS HOTSPOT-X20

410-2410-016 EN21

3  Structure

3.1  Overview

No.

Description

Detector enclosure

Signal dome

Explosion-proof cable gland

Pre-assembled ADICOS connection cable

3.2  Cable assignment

Wire

Color

Signal

Signal limit contact

1

black

Operating voltage

24 ... 40 V DC non-polarized

1

white

2

black

Relay output X6 e

Alarm NO

1

2

white

Relay output X6 a

Alarm NO

1

3

black

Relay output X7 a

fault NC

3

white

Relay output X7 e

fault NC

4

black

M-bus

max. 40 V non-polarized

4

white

1

 with series resistor, standard 680 Ω

Summary of Contents for DICOS HOTSPOT-X20

Page 1: ...EN GTE Industrieelektronik GmbH Helmholtzstr 21 38 40 41747 Viersen Germany 49 2162 3703 0 info gte de HOTSPOT X20 Supplementary Instruction Manual for X20 Detectors IR Temperatur Detector ...

Page 2: ...mholtzstr 21 38 40 41747 Viersen GERMANY Support hotline 49 2162 3703 0 E Mail support adicos gte de 2020 GTE Industrieelektronik GmbH This document and all figures contained may not be copied changed or distributed without explicit approval by the manufacturer Subject to technical changes ADICOS and GSME are registered trademarks of GTE Industrieelektronik GmbH ...

Page 3: ...The detector units are connected to the ADICOS Central Software with aid of the M Bus It allows the parameterization of each individual detector and the storage of all sensor data for statistical evaluation The ADICOS HOTSPOT 1000 is an IR fire detector used for optical and spatially resolved fire and heat detection It is well suited for these applications Detection of hot surfaces Detection of fl...

Page 4: ...ualification 5 2 4 Handling electrical voltage 5 2 5 Modification 5 2 6 Accessories and spare parts 5 3 Structure 6 3 1 Overview 6 3 2 Cable assignment 6 3 3 Display elements 7 4 Installation 8 4 1 Mounting with ADICOS Mounitng Plate 8 4 2 Installation on Mounting Bracket 9 4 3 Wiring 10 5 Commissioning 10 6 Operation 10 7 Maintenance 11 7 1 Detector replacement 11 8 Specifications 11 9 Appendix 1...

Page 5: ...al features a continuous structure for best possible comprehension The following labels are used Warning signs This manual uses the following information types NOTE This information type provides information directly important for further system operation WARNING This information type signals a danger that can lead to fatal or severe injuries DANGER This information type signals a danger that dire...

Page 6: ...ntext the operating parameters described in Chap 8 Specifications must be met Any deviating use requires prior consultation with the manufacturer Compliance with this manual as well as all applicable country specific provisions is also part of the intended use 2 2 Standards and regulations The safety and accident prevention regulations applicable for the specific application must be observed durin...

Page 7: ... maintenance may only be performed by authorized and respectively trained personnel 2 4 Handling electrical voltage DANGER The electronics of ADICOS HOTSPOT X20 works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres Do not open enclosure Switch off the entire detector system and secure against unintentionally reactivation for all wiring work 2 5 Modific...

Page 8: ...ICOS connection cable 3 2 Cable assignment Wire Color Signal Signal limit contact 1 black Operating voltage 24 40 V DC non polarized 1 white 2 black Relay output X6 e Alarm NO1 2 white Relay output X6 a Alarm NO1 3 black Relay output X7 a Fault NC 3 white Relay output X7 e Fault NC 4 black M bus max 40 V non polarized 4 white 1 with series resistor standard 680 Ω ...

Page 9: ...e Color Auxiliary relay 5 black 5 white NC 6 black NO 6 white C 3 3 Display elements Signal Dome The signal dome is a translucent element It includes the status LED to indicate the operating condition of the X20 detectors Normal operation green Alarm red Fault yellow vv ...

Page 10: ... ADICOS HOTSPOT X20 410 2410 016 EN21 4 Installation 4 1 Mounting with ADICOS Mounitng Plate WARNING ADICOS HOTSPOT X20 detectors must be mounted with closed enclosure Do not open enclosure Use ADICOS Mounting Plate ...

Page 11: ...OS HOTSPOT X20 410 2410 016 EN21 Installation 4 2 Installation on Mounting Bracket WARNING ADICOS HOTSPOT X20 detectors must be mounted with closed enclosure Do not open enclosure Use ADICOS Mounting Bracket ...

Page 12: ...explosion proof connection boxes with respective approval Do not bend connection cable Observe minimum bending radius Chap 8 Specifications 5 Commissioning DANGER The electronics of ADICOS HOTSPOT X20 detectors require an electrical volt age that can trigger an explosion in potentially explosive atmospheres Prior to switching on check that all detectors are properly mounted and wired 6 Operation D...

Page 13: ... and secure against unintentionally reactivation for all disassembly work Replace the closed detector including connection cable only 8 Specifications Specifications regarding explosion protection HOTSPOT X20 Explosion protection class Ex ta IIIC 105 C Da IP6x Surface temperature C 105 Device group II category 1D Type approval Certificate accorting to 2014 34 EU Bending radius connection cable mm ...

Page 14: ...Appendix 12 ADICOS HOTSPOT X20 410 2410 016 EN21 9 Appendix 9 1 ADICOS mounting plate A A 1 5 0 1 5 0 1 3 0 1 3 0 6 4 A A ...

Page 15: ...13 ADICOS HOTSPOT X20 410 2410 016 EN21 Appendix 9 2 ADICOS Mounting Bracket 150 105 8 50 102 76 4x ...

Page 16: ......

Reviews: