Chapter 3 Installation and Wiring GK600 User Manual
- 40 -
Drive model
Power terminal
Ground terminal
Cable
requiremen
t (mm
2
)
Screw
Torque
(kgf.cm)
Cable
requireme
nt (mm
2
)
Screw
Torque
(kgf.cm)
GK600-4T110G/132L
110G
120
M12
440
±0.5
70
M12
440±0.5
132L
120
70
GK600-4T132G/160L
132G
120
M12
440
±0.5
70
M12
440±0.5
160L
150
95
GK600-4T160G/185L
160G
150
M12
440
±0.5
95
M12
440±0.5
185L
185
95
GK600-4T185G/200L
185G
185
M12
440
±0.5
95
M12
440±0.5
200L
185
95
GK600-4T200G/220L
200G
185
M12
440
±0.5
95
M12
440±0.5
220L
240
120
GK600-4T220G/250L
220G
240
M16
690
±0.5
120
M16
690±0.5
250L
120x2
120
GK600-4T250G/280L
250G
120x2
M16
690
±0.5
120
M16
690±0.5
280L
120x2
120
GK600-4T280G/315L
280G
120x2
M16
690
±0.5
120
M16
690±0.5
315L
150x2
150
GK600-4T315G/355L
315G
150x2
M16
690
±0.5
150
M16
690±0.5
355L
185x2
95x2
GK600-4T355G/400L
355G
185x2
M16
690
±0.5
95x2
M16
690±0.5
400L
240x2
120x2
GK600-4T400G/450L
400G
240x2
M16
690
±0.5
120x2
M16
690±0.5
450L
240x2
120x2
GK600-4T450G/500L
450G
240x2
M16
690
±0.5
120x2
M16
690±0.5
500L
240x2
120x2
GK600-4T500G
240x2
M16
690
±0.5
120x2
M16
690±0.5
GK600-4T560G
300x2
M16
690
±0.5
150x2
M16
690±0.5
GK600-4T630G
300x2
M16
690
±0.5
150x2
M16
690±0.5