GST-MNA2C/GST-MNA2F Network Annunciator
Installation and Operation Manual
Page 7
3.4 External Connection
3.4.1
Power Connection-Class B
Use 16AWG or larger wire. Power supply wires should be connected to the terminal as
shown in Fig.3-3 below.
GST-MNA2 Network Annunciator
Mother Board
+
-
24V IN
GST-IFP4-M
+
-
AUX
Fig.3-3
3.4.2
Network Connection-Class A
The GST-MNA2C has a CAN type interface: Fig.3-4 is for CAN network connection .and
the GST-MNA2 F has a FIB type interface: Fig.3-5 is for Fiber connection.
S
1+
_O
S
1-
_O
S
1-
_I
S
1+
_I
CAN
NETWORK
CARD
FACP
CAN
_H
2
CAN
_L
2
CAN
_L
1
CAN
_H
1
CAN
Annunciator1
CAN
_H
2
CAN
_
L2
CAN
_
L1
CAN
_H
1
CAN
Annunciator
2
MAX 250 nodes
CALSS A
The distance
between two
neighbor nodes is
less than 3000m;
Twisted pair with
cross section
18AWG ;
Maximum 250
Annunciators Or
panels for
networking.
Fig. 3-4