Features
During normal standby, Output port (O1, O2) is
provided with Class B pathway supervision
when connects with 47K
Ω EOLR (Part Number
30108524).
Occupying one address. It can be modified in
filed.
Output port utilizes AD sampling technology for
precise testing.
Guide rail for installation, easy for construction.
Compatible with GST-M200 and GST-IFP4M Fire
Alarm Control Panels (FACP).
Standard: UL864, NFPA [70, 72].
Description
With a microprocessor, DI-M9305 Digital Single
Riser Output Module can communicate with a FACP.
The module is designed to switch on/off 24VDC
power at its output.
Connection and Cabling
Fig. 1 shows terminals on the module.
Fig. 1
(Z1, Z2) IN & OUT: Connecting with loop of FACP,
polarity-insensitive.
(I1, I2) IN & OUT: Power input terminals. For
connecting with 24VDC power from Listed FACP or
power supply.
O1, O2: Output terminals to 24VDC powered devices
CODE: connecting with P-9910B programmer.
Recommended Wiring
17 AWG or above fire cable for all terminals, and
subject to local codes.
Installation
Warning:
Before installing the module, disconnect
power from the loop and verify that the
guide rail is securely installed.
1)
Before installation, make sure the enclosure is
in good condition and markings are complete.
2)
The module shall either be installed in a North
America standard metal electrical box.
Minimum size is 4 in. square, 2-1/8 in depth (in
this case, standard box cover is required), or in
a UL Signaling Listed enclosure that provides
minimum wiring entries and spacing as shown
on Fig 2 and Fig 3. Minimum mounting space is
67×40.5mm.
3)
The module can be mounted on a guide rail as
shown on Fig 4.
4)
The module can also be installed in the
enclosure by 4 mounting screws as shown in
Fig.5.