Features   

 

Input  port is provided with Class B pathway 
supervision when connects with 4.7

KΩ  EOLR 

(Part Number 3010786).   

 

Input  port can be programmed  to monitor  either 
normally open or  normally  closed dry  contact 
input.   

 

Input can also be programmed 

as 

“self-answering”, which means that the Input port 
monitoring is disabled, and the  module  will 
directly send a “status” signal to FACP when the 
dry-contact output changes state. 

 

Addressable unit. Address can be programmed 
in field. 

 

Input  port utilizes AD sampling  technology  for 
precise testing. 

 

Compatible with GST-M200 and GST-IFP4M Fire 
Alarm Control Panels (FACP). 

 

Guide rail for easy installation. 

 

Standard: UL864, NFPA [70, 72]. 

Description 

With a microprocessor, DI-M9301 Digital Single Input 
and Output Module can communicate with fire alarm 
control panel (FACP). On receiving start command 
from the FACP, it will close the output relay and 
illuminate the Active indicator. 

Connection and Cabling 

Terminals of the module are shown in Fig. 1. 

 

Fig. 1 

 

(Z1, Z2) IN & OUT: Connecting with the Signaling 
Line Circuit (SLC)  loop of FACP,  polarity 
insensitive. 

 

I, G: Connecting with normally open dry contact 
of an input device that closes when the device is 
in alarm or changes state. It may also be set to 
normally closed input by hand held programmer. 

 

COM, NO, NC: Dry contact output terminals

.

 

 

CODE: Connecting with the programmer. 

Recommended Wiring: minimum 17 AWG. Subject to 
local codes. 

 

 

 

 

 

 

 

 

 

 

Installation 

Warning: 

Before installing the module,  disconnect power 
from the loop.   

1) 

Before installation, make sure the enclosure is in 
good condition and markings are complete. 

2) 

The  module shall either  be installed in a  North 
America standard metal electrical box. Minimum 
size is 4 in. square, 2-1/8 in depth (in this case, 
standard box cover is required), or in a UL 
Signaling 

Listed enclosure that provides 

minimum wiring entries and spacing as shown on 
Fig 2 and Fig  3.  Minimum mounting space is 
67×40.5mm.

 

 
 

 

 

 

 

 

 

 

 

 

 

Fig 2 

DI-M9301 

Digital Single Input and Output Module 

 

 

Fire Alarm   
Equipment 
47AU 

30310199                                                                                Issue 1.06

 