30310465                                                                                                                                                                  Issue 1.05 

                                       

 

 

Features 

 

Normally  closed  input,  normally  open  input  can 
be set through a hand held programmer.

     

 

Electronically  addressing.  Addresses  can  be 
modified in field.   

 

Built-in  microprocessor  processes  messages 
intelligently. 

 

Input  terminals  apply  AD  sampling  with  precise 
testing.   

 

DIN-Rail mounted or Wall mounted. 

 

Standard: EN 54-18:2005 

Description 

DI-9300E  Digital  Single  Input  Module  (the module) is 
used  for  receiving  normally  open  or  normally  closed 
switch  signal  from  fire  suppression  devices,  and 
transmits these  messages  to  fire  alarm  control  panel 
(FACP). When  a  device  of  this  kind  is  activated,  the 
module can send the output signal through signal loop 
to FACP to alarm or activate relative devices. 

Connection and Cabling 

Terminals of the module are shown in Fig. 1. 

 

Fig. 1 

 

(Z1,  Z2)  IN  & OUT:  Connecting  with  the loop of 

FACP, polarity-insensitive. 

 

I,  G:  Connect  with  normally-open  contact  of  an 

input devices that closes when the device is in alarm 
or changes state. It may also be set to normally-closed 
checking input by a hand-held programmer. 

 

CODE: Connect with the programmer. 

Recommended  Wiring:  minimum  1.0mm

2

.  Subject  to 

local codes. 

 

 

 

 

Installation   

Warning: Before installing the module, disconnect 
power from the loop and verify that the guide rail 
is securely installed.   

(1) 

Before installation, make sure the enclosure is in 
good condition and markings are complete. 

(2) 

The  module  can  be  mounted  on  a  35mm 
DIN-Rail as shown in Fig. 2. 

(3) 

The module can also be wall mounted by 4 
mounting screws as shown in Fig. 3. Minimum 

mounting space is 67 mm. 

 

Fig. 2 

 

Fig. 3 

Application 

The  module  may  be  used  to  monitor  status  of  fire 
suppression  devices,  such  as  water  flow  indicator, 
pressure  switch,  position  switch,  signal  valve,  and 
devices that can feedback the ON/OFF signal.   

548m/04 

2831-CPR-F2020 

GST-0018-01 

 

18 

DI-9300E 

  Digital Single Input Module

   

 