30310465 Issue 1.05
Parameters can be programmed through P-9910B
programmer.
Programming Parameters:
In standby state of the programmer, Inputting “456”
and then pressing “Clear” can unlock the programmer,
press
Fn
and then number “3”, “—”will be popped up
on the screen to indicate it is in programming mode.
Write a parameter and then press “Program”, a “P” will
show on the screen meaning the parameter is
programmed.
Parameters used for setting includes:
1
normally-closed
others(default)
normally-open
The relationship between the I/G port resistance and
the product state is shown in the following table:
Detection mode
I/G port
resistance
Input state
Normally-open
< 1 kΩ
Active
> 11.7 kΩ
Fault
other
Normal
Normally-closed
< 1 kΩ
Fault
> 11.7 kΩ
Active
other
Normal
Connection of the module to field devices with
normally open dry contact is shown in Fig. 3.
Z1 Z2
I G
Z1
Z2
DI-9300E
4.7
KΩ
End-of-line
Resistor
Normally Open Contact
Field Device
FAC
P
Fig. 3
Connection of the module to field devices with
normally closed dry contact is shown in Fig.4.
Z1 Z2
I G
Z1
Z2
DI-M9300
Normally Closed Contact
Field Device
F
A
C
P
4.7
KΩ
End-of-line
Resistor
Fig. 4
Specification
Operating Voltage
Loop 24VDC (16V - 28V)
Standby Current
≤
0.26mA
Action Current
≤
0.5mA
Programming
Electronically addressing
Address Range
Occupy one address from 1
to 242.
LED
ACTIVE LED: Red. It lights
on activation, quiet in loop
power down, and flashes in
other states.
FAULT LED: Yellow. It
lights 0.5s on and 0.5s off
as there is input fault. It
turns off in other states.
Ingress Protection
Rating
IP30
Operating
Temperature
-
10
°
C - +55°C
Relative Humidity
≤
95%
,
non-condensing
Compatible
DIN-Rail
35mm DIN-Rails
Materials of the
Enclosure
ABS, white (RAL9016)
Dimension
(L×W×H)
78mm×45.3mm×28.5mm
Weight
About 36.8g
Accessories and Tools
Model
Name
Remark
P-9910B
Hand
Held
Programmer
Supplied
separately
RT-0.25W-4.7kΩ
±5%-25mm
End of Line
Resistor
Provided
Limited Warranty
GST
warrants that the product will be free from defects
in design, materials and workmanship during the
warranty period. This warranty shall not apply to any
product that is found to have been improperly installed
or used in any way not in accordance with the
instructions supplied with the product. Anybody,
including the agents, distributors or employees, is not
in the position to amend the contents of this warranty.
Please contact your local distributor for products not
covered by this warranty.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO,
AND INSTALLATION BY, AN EXPERIENCED
SECURITY PROFESSIONAL. UTC FIRE &
SECURITY CANNOT PROVIDE ANY ASSURANCE
THAT ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY “AUTHORIZED
DEALER”, IS PROPERLY TRAINED OR