background image

 

30310465                                                                                                                                                              Issue 1.05 

Parameters  can  be  programmed  through  P-9910B 
programmer. 

  Programming Parameters: 

In  standby  state  of  the  programmer,  Inputting  “456” 
and then pressing “Clear” can unlock the programmer, 
press 

Fn

 and then number “3”, “—”will be popped up 

on  the  screen  to  indicate  it  is  in  programming mode. 
Write a parameter and then press “Program”, a “P” will 
show  on  the  screen  meaning  the  parameter  is 
programmed.   
Parameters used for setting includes: 

normally-closed 

others(default) 

normally-open 

The  relationship  between  the  I/G  port  resistance  and 
the product state is shown in the following table:

 

Detection mode 

I/G port   
resistance 

Input state 

Normally-open 

< 1 kΩ 

Active 

> 11.7 kΩ 

Fault 

other   

Normal 

Normally-closed 

< 1 kΩ 

Fault 

> 11.7 kΩ 

Active 

other 

Normal 

 

Connection  of  the  module  to  field  devices  with 

normally open dry contact is shown in Fig. 3. 

 

Z1                                       Z2

I                                            G

Z1

Z2

DI-9300E

4.7

KΩ 

End-of-line

Resistor

Normally Open Contact

Field Device

FAC

P

   

Fig. 3

 

Connection of the module to field devices with 
normally closed dry contact is shown in Fig.4.

 

Z1                                       Z2

I                                         G

Z1

Z2

DI-M9300

Normally Closed Contact

Field Device

F

A

C

P

4.7

KΩ 

End-of-line

Resistor

 

Fig. 4 

Specification 

Operating Voltage 

Loop 24VDC (16V - 28V) 

Standby Current 

  0.26mA 

Action Current 

  0.5mA 

Programming 

Electronically addressing 

Address Range 

Occupy one address from 1 
to 242. 

LED 

ACTIVE LED: Red. It lights 
on  activation,  quiet  in  loop 
power down, and flashes in 
other states. 
FAULT  LED:  Yellow.  It 
lights  0.5s  on  and  0.5s  off 
as  there  is  input  fault.  It 
turns off in other states.   

Ingress  Protection 
Rating 

IP30 

Operating 
Temperature 

-

10

°

C - +55°C 

Relative Humidity 

  95%

non-condensing 

Compatible 
DIN-Rail 

35mm DIN-Rails 

Materials  of  the 
Enclosure 

ABS, white (RAL9016)   

Dimension 
(L×W×H) 

78mm×45.3mm×28.5mm 

Weight 

About 36.8g 

Accessories and Tools 

Model 

Name 

Remark 

P-9910B 

Hand 

Held 

Programmer 

Supplied 
separately 

RT-0.25W-4.7kΩ
±5%-25mm 

End  of  Line 
Resistor 

Provided 

Limited Warranty   

GST

 warrants that the product will be free from defects 

in  design,  materials  and  workmanship  during  the 
warranty  period. This  warranty  shall  not  apply to  any 
product that is found to have been improperly installed 
or  used  in  any  way  not  in  accordance  with  the 
instructions  supplied  with  the  product.    Anybody, 
including the agents, distributors or employees, is not 
in the position to amend the contents of this warranty. 
Please  contact  your  local  distributor  for  products  not 
covered by this warranty.   

Product warnings and disclaimers 

THESE PRODUCTS ARE INTENDED FOR SALE TO, 
AND INSTALLATION BY, AN EXPERIENCED 
SECURITY PROFESSIONAL. UTC FIRE & 
SECURITY CANNOT PROVIDE ANY ASSURANCE 
THAT ANY PERSON OR ENTITY BUYING ITS 
PRODUCTS, INCLUDING ANY “AUTHORIZED 
DEALER”, IS PROPERLY TRAINED OR 

Reviews: