background image

HTTP://WWW.HOMBI.RU

 

30304559                                                 

                               

 Issue 2.01

 

commission and kept well before installation, taken 
corresponding measures for dust-proof, damp-proof 
and corrosion-proof.

 

2.  The dust cover cannot be removed until the project 
has been plunged into usage. Otherwise it can’t alarm 
normally.

 

3.  Clean the detector at least once a year to ensure 
normal operation of the system.

 

4.  Before cleaning, notify the proper authorities that 
the system is undergoing maintenance and will 
temporarily be out of service. Disable the zone or 
system undergoing maintenance to avoid unwanted 
alarms.

 

5.  The detector should be tested again after cleaning 
and reinstallation.

 

6.  Protect the metal component on the PCB against 
damp and improper distortion. 

 

7.  Fire simulation test should be made to the detector 
at least once half a year.

 

Specification 

Operating Voltage

 

Loop 24V   

 

Standby Current

 

0.8mA

 

Alarm Current

 

5mA

 

Fire LED

 

Red, Flashes in polling, and 
illuminates in alarming.

 

Remote indicator 
output

 

Directly connect to remote 
indicator (built in 5.1k resistor in 
series, output voltage is 4.3V); 
not lit in polling, constantly 
illuminated in alarming. 

 

Sensitivity I: 58

 

Sensitivity II: 66

 

Action Temperature 

Sensitivity III: 72

 

Response Velocity 

3

/min

 

Programming

 

Electronically addressed.

 

Programming Range

 

Occupying one address within 
1

242.

 

Ingress Protection 
Rating 

IP22 

Environmental 
Temperature

 

-

10

~+

50

 

Relative Humidity

 

95%, non-condensing

 

Material and Color of 
Enclosure

 

ABS, white (RAL 9016)

 

Dimension

 

Diameter: 100mm 

Height: 41mm (without base)

 

Mounting Hole 
Distance

 

45mm

75mm

 

Weight About 

90g 

 

 

 

 

 

 

 

 

 

Accessories and Tools 

Mode Name 

Remark 

P-9910B

Hand Held 
Programmer

Supplied separately 

DB-01 Orientation 

Base 

Supplied separately 

Limited Warranty 

GST

 warrants that the product will be free from defects 

in design, materials and workmanship during the 
warranty period. This warranty shall not apply to any 
product that is found to have been improperly installed 
or used in any way not in accordance with the 
instructions supplied with the product. Anybody, 
including the agents, distributors or employees, is not 
in the position to amend the contents of this warranty. 
Please contact your local distributor for products not 
covered by this warranty.

 

 

GST China 
Gulf Security Technology Co., Ltd. 

No. 80, Changjiang East Road, 
QETDZ, Qinhuangdao, Hebei,   
P. R. China 066004 
Tel: +86 (0) 335 8502528     
Fax: +86 (0) 335 8508942 

   

[email protected] 
www.gst.com.cn 

GST UK 
Global System Technology PLC 

Lion Court, Staunton Harold Hall,   
Melbourne Road, Ashby de la Zouch, 
Leicestershire, England LE65 1RT 
Tel: +44 1283 225 478 
Fax: +44 1283 220 690 
[email protected]   
www.gst.uk.com

GST Dubai 
Global System Technology PLC 

PO Box 17998 Unit ZA04   
JEBEL ALI Free Zone,   
Dubai, UAE 
Tel: +971 (0) 4 8833050     
Fax: +971 (0) 4 8833053 
[email protected]   
www.gst.uk.com 

This document is subject to change without notice. Please contact GST for more information or questions. 