background image

 

30309533

               

                                                                                                     

       

  Issue 1.04

 

Test Zone

 

Fig. 4 

b) 

Smoke test 

Taking  a  smoldering  cotton  rope  close  to  the 
detector, blow the smoke into the detector until the 
detector generates alarm. 
c) 

Temperature test 

Approach  a  heater  (such  as  a  hair  drier)  to  the 
thermistor of the detector until it alarms. 

3) After  testing,  reset  the  detector.  Notify  the  proper 

authorities  that  the  system  is  back  to  normal 
operation. 

If  a  detector  fails  in  testing,  clean  it  by  the  steps  in 

Maintenance

,  and  retest  it.  If  it  still  fails,  return  it  for 

repair. 

Maintenance 

 

The  detector  should  be  installed  just  before 
commissioning  and  kept  well  before  installation, 
taken  corresponding  measures  for  dust-proof, 
damp-proof and corrosion-proof. 

 

The  dust-proof  cover  should  not  be  removed  until 
the project is plunged into usage. Otherwise it may 
not report alarm properly.

 

 

Clean the detectors regularly, at least once a year 
to ensure normal operation of the system.

 

 

If unwanted alarms are often found of the detector 
on  site,  the  sensing  chamber  should  be  cleaned. 
Power  must  be  removed  from  the  detector  before 
cleaning.

 

Steps for chamber cleaning: 

a)  Open  the  top  cover  of  detector,  and  draw  out 

the  sensing  chamber  by  slightly  lifting  its  two 
sides using a straight screwdriver, as shown in 
Fig. 5.   

   

Fig. 5 

b)  Clean  the  internal  of  the  chamber  by  alcohol 

cotton swab with tweezers or using clean water 
and brush. Make sure not to leave any fiber in 
the chamber. 

c)  Put back the chamber and the top cover. 

 

Before  cleaning,  notify  the  proper  authorities  that 
the  system  is  under  maintenance  and  will 
temporarily be out of service. Disable the automatic 
controls  relating  to  the  zone  or  system  under 
maintenance to avoid unwanted actions. 

 
 
 
 
 
 

 

The  detector  should  be  tested  after  re-installed  to 
ensure normal operation.

 

 

Fire  simulation  test  should  be  done  to  the  detector  at 
least every 6 months.

 

Specification

 

Operating Voltage 

loop 24V(16V

28V)   

Standby Current 

0.8mA 

Alarm Current 

1.8mA (without remote indicator) 

≤ 

3.8mA (with remote indicator) 

Fire LED 

Red.  Flashes  in  polling,  and 
illuminates in alarm 

Remote 

Indicator 

Output 

Polarized  output.  Directly  connect 
to  remote  indicator  (built  in  10k 
resistor in series, output current is 
2mA);  Flash  in  alarming  and  do 
not illuminate in normal. 

Programming Method 

Electronically programming 

Code Range 

one address within 1

242 

Wiring 

Non-polarized 2-core for loop. 
Polarized 

2-core 

for 

remote 

indicator. 

Setting  of  sensitivity 
and range 

The  sensitivity  can  be  set  by 
programmer with two levels: Level 
1(default), level 2. 

Detector Class 

A2R 

Action Temperature 

62

 

Environment 
Temperature 

-10

℃~

50

 

Relative Humidity 

95%, non condensing 

Material of Enclosure 

ABS 

Ingress 

Protection 

Rating 

IP2X 

Dimensions 

Diameter: 100mm   
Height: 54.5mm (with base) 

Mounting 

Hole 

Distance 

45mm

75mm 

Weight 

About 110g 

Accessories and Tools

 

Model 

Name 

Remark 

P-9910B 

Hand held programmer 

Order separately 

DB-01 

Base 

Order separately 

T-MT 

Commission Tool 

Order separately   

WEEE Information 

2012/19/EU  (WEEE  directive):  Products  marked 
with this symbol cannot be disposed of as unsorted 
municipal waste in the European Union. For proper 
recycling, return  this  product to  your local  supplier 
upon the purchase of equivalent new equipment, or 
dispose of it at designated collection points. 

Limited Warranty

 

GST

 warrants that the product will be free of charge for repairing 

or replacing from defects in design, materials and workmanship 
during  the  warranty  period.  This  warranty  does  not  cover  any 
product that is found to have been improperly installed or used 
in any way not in accordance with the instructions supplied with 
the  product.  Anybody,  including  the  agents,  distributors  or 
employees, is not in the position to amend the contents of this 
warranty.  Please  contact  your local  distributor for  products not 
covered by this warranty. 

 

This document is subject to change without notice. Please contact GST for more information or questions. 