Fig. 4
b)
Smoke test
Taking a smoldering cotton rope close to the
detector, blow the smoke into the detector until the
detector generates alarm.
c)
Temperature test
Approach a heater (such as a hair drier) to the
thermistor of the detector until it alarms.
3) After testing, reset the detector. Notify the proper
authorities that the system is back to normal
operation.
If a detector fails in testing, clean it by the steps in
Maintenance
, and retest it. If it still fails, return it for
repair.
Maintenance
The detector should be installed just before
commissioning and kept well before installation,
taken corresponding measures for dust-proof,
damp-proof and corrosion-proof.
The dust-proof cover should not be removed until
the project is plunged into usage. Otherwise it may
not report alarm properly.
Clean the detectors regularly, at least once a year
to ensure normal operation of the system.
If unwanted alarms are often found of the detector
on site, the sensing chamber should be cleaned.
Power must be removed from the detector before
cleaning.
Steps for chamber cleaning:
a) Open the top cover of detector, and draw out
the sensing chamber by slightly lifting its two
sides using a straight screwdriver, as shown in
Fig. 5.
Fig. 5
b) Clean the internal of the chamber by alcohol
cotton swab with tweezers or using clean water
and brush. Make sure not to leave any fiber in
the chamber.
c) Put back the chamber and the top cover.
Before cleaning, notify the proper authorities that
the system is under maintenance and will
temporarily be out of service. Disable the automatic
controls relating to the zone or system under
maintenance to avoid unwanted actions.
The detector should be tested after re-installed to
ensure normal operation.
Fire simulation test should be done to the detector at
least every 6 months.
Specification
Operating Voltage
loop 24V(16V
~
28V)
Standby Current
≤
0.8mA
Alarm Current
≤
1.8mA (without remote indicator)
≤
3.8mA (with remote indicator)
Fire LED
Red. Flashes in polling, and
illuminates in alarm
Remote
Indicator
Output
Polarized output. Directly connect
to remote indicator (built in 10k
resistor in series, output current is
2mA); Flash in alarming and do
not illuminate in normal.
Programming Method
Electronically programming
Code Range
one address within 1
~
242
Wiring
Non-polarized 2-core for loop.
Polarized
2-core
for
remote
indicator.
Setting of sensitivity
and range
The sensitivity can be set by
programmer with two levels: Level
1(default), level 2.
Detector Class
A2R
Action Temperature
62
℃
Environment
Temperature
-10
℃~
50
℃
Relative Humidity
≤
95%, non condensing
Material of Enclosure
ABS
Ingress
Protection
Rating
IP2X
Dimensions
Diameter: 100mm
Height: 54.5mm (with base)
Mounting
Hole
Distance
45mm
~
75mm
Weight
About 110g
Accessories and Tools
Model
Name
Remark
P-9910B
Hand held programmer
Order separately
DB-01
Base
Order separately
T-MT
Commission Tool
Order separately
WEEE Information
2012/19/EU (WEEE directive): Products marked
with this symbol cannot be disposed of as unsorted
municipal waste in the European Union. For proper
recycling, return this product to your local supplier
upon the purchase of equivalent new equipment, or
dispose of it at designated collection points.
Limited Warranty
GST
warrants that the product will be free of charge for repairing
or replacing from defects in design, materials and workmanship
during the warranty period. This warranty does not cover any
product that is found to have been improperly installed or used
in any way not in accordance with the instructions supplied with
the product. Anybody, including the agents, distributors or
employees, is not in the position to amend the contents of this
warranty. Please contact your local distributor for products not
covered by this warranty.
This document is subject to change without notice. Please contact GST for more information or questions.
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
www.gst.com.cn